Simulation of grounding systems in electrical power grids.

groundinsight is an open-source Python package for analysing networked grounding systems during single-phase-to-ground faults. It computes the earth potential rise (EPR), branch (shield) currents, reduction factors and the resulting grounding impedance at the fault location for arbitrary bus/branch topologies including line, ring and mesh networks.

PyPI version License: MIT Python

What groundinsight does

Modern medium-voltage distribution networks are meshed through shared grounding conductors (cable shields, overhead-line earth wires, substation grounding grids). During a single-phase-to-ground fault, current returns to the source via this grounding network. To assess touch-voltage safety and EMC effects, two questions have to be answered for a given fault location:

  • How much of the fault current actually flows through the local earth (as opposed to returning through the cable shield)? This is captured by the reduction factor \(r\).
  • What earth-potential rise does the grounding grid reach, and what is the effective grounding impedance \(Z_G\) seen at the fault bus?

groundinsight answers both questions by assembling a nodal-admittance model from user-defined frequency- and \(\rho_E\)-dependent impedance formulas and solving it for every harmonic of interest.

Governing equation

All computations happen per frequency \(f\) in the phasor domain:

\[ Y(f)\,\underline{u}(f) = \underline{i}(f) \quad\Longrightarrow\quad \underline{u}(f) = Y(f)^{-1}\,\underline{i}(f) \]

where \(Y\) is the nodal admittance matrix (bus grounding admittances on the diagonal, branch self-admittances off-diagonal), \(\underline{u}\) is the EPR vector and \(\underline{i}\) combines injected source currents and the Norton equivalents of the mutual coupling between phase and shield conductors.

Minimal example

import groundinsight as gi

net = gi.create_network(name="Demo", frequencies=[50])

bus_type = gi.BusType(
    name="SubstationBus", system_type="Substation", voltage_level=20,
    impedance_formula="rho * 0.01 + j * f * 1/50 * 0.1",
)
cable_type = gi.BranchType(
    name="MSCable", grounding_conductor=True,
    self_impedance_formula="(0.25 + j * f * 0.012) * l",
    mutual_impedance_formula="(0.0  + j * f * 0.012) * l",
)

gi.create_bus(name="src", type=bus_type, network=net)
gi.create_bus(name="flt", type=bus_type, network=net)
gi.create_branch(
    name="c1", type=cable_type,
    from_bus="src", to_bus="flt", length=5.0, network=net,
)
gi.create_source(name="infeed", bus="src", values={50: 1000.0}, network=net)
gi.create_fault(name="f1", bus="flt", scalings={50: 1.0}, network=net)

gi.run_fault(network=net, fault_name="f1")
print(net.res_all_impedances())

See the Quickstart for the full walkthrough.

Feature overview

  • Bus, branch, source and fault objects modelled as Pydantic v2 classes
  • Symbolic impedance formulas in \(\rho_E\), \(f\) and line length \(l\), evaluated through SymPy
  • Sparse LU solver for every frequency (SciPy splu)
  • Mutual coupling treated as Norton sources along the path from source to fault
  • Two reduction factors, both reported: the EPR ratio with and without mutual coupling at the fault bus (value), and the share of the fault current returning through earth (value_current) — the EN 50522 quantity, and the one that responds to the electrode at the fault bus, see Concepts
  • Phase currents from a solve on the phase-conductor network (phase_current_mode="auto"), so rings, meshes and parallel cables no longer collapse onto enumerated paths; BranchType.phase_impedance_formula describes the faulted conductor
  • Splitting the network at the fault (gi.Cut, gi.analyze_cuts) — what each direction contributes, from source-free current division, see Fault-location decomposition
  • Parameter sweeps (run_sweep, rho_f_points) into long-format frames, with summarize and classify for statistics and user-supplied limit bands, see Parameter sweeps
  • Characterising a location without its electrode (bus_response): two solves determine the response for every electrode impedance, see Location response
  • Closed-form reference cases (run_reference_cases) — six configurations checked against results derived from first principles, see Reference cases
  • SQLite persistence and JSON export/import of networks and type libraries
  • Polars DataFrames for result access; Matplotlib helpers for bar plots
  • Time-domain transient simulation (FFT and modified-nodal-analysis state-space solvers) on top of the same Pydantic network, see Transient simulation
  • Import of external distribution networks from pandapower — the topology via from_pandapower, and a solved short-circuit case as IEC 60909 quantities via read_shortcircuit_results / apply_shortcircuit_characteristics, see I/O
  • Conductor thermal-limit check (check_conductor_limits): the IEC 60909 thermally equivalent current \(I_{th}\) against the IEC 60949 adiabatic limit \(k\,S/\sqrt{t_k}\), per grounding branch, see Analysis

Where to go next

  • Installation — how to get groundinsight onto your system.
  • Quickstart — end-to-end walkthrough of a minimal network.
  • Concepts — the physical and numerical model behind the code.
  • Transient simulation — FFT and state-space solver paths for time-domain studies on top of the stationary network.
  • Examples — notebooks covering the minimal case, stationary and transient MV ring studies, a pandapower import and a fault sweep across an MV cable line.
  • API reference — function-by-function documentation.