Skip to content

Concepts

This page explains, in plain words, the objects you build a computation from, what happens when you call solve, and what a result contains. Read it once to get the overall picture; the quickstart shows the same in code, and the engines page explains the numerical methods.

Position in the software family

  groundmeas   ──▶   groundinsight   ◀──   groundfield
  (measurements)     (reduced network       (field model,
                      model)                 reference)

groundfield is the field-theoretical reference of the family. It computes the potential field of earthing systems in layered soil from their geometry and material data and compresses the solution into reduced models — impedance functions \(Z(\rho, f)\), multiport matrices — that groundinsight uses as building blocks of a network model, and against which groundmeas measurements can be interpreted. The field model is a reference, not the end product: every solution exposes the quantities the reduction needs.

The data model

A computation separates the physics (what is in the ground) from the numerics (how it is solved). The physics lives in a World, the numerics in an Engine; world.solve(engine) returns a FieldResult.

Object What it is Created with
soil model horizontal layers of constant resistivity: HomogeneousSoil(rho), TwoLayerSoil(rho_1, rho_2, h_1), MultiLayerSoil(layers); depth \(z\) positive into the soil the class itself
World the physical model: one soil, and the electrodes, junctions, conductors and sources in it create_world
electrode a thin wire in contact with the soil: rod, ring, strip, polyline, star, mesh, grid; optionally encased in concrete (concrete shells) create_electrode
junction a node without soil contact: a cable joint, an instrument terminal create_junction
conductor a branch between two nodes: an ideal bond, or a cable with resistance, optionally leaking into the soil along its length and optionally inductive create_conductor
source a current or voltage source that drives a node against a second node or against remote earth (sources and measurement) create_source
Engine the numerics: backend, frequencies, segment length, source kernel, earth-return model, backend options create_engine
FieldResult potentials, leakage currents and impedances per frequency, the sources for evaluating the field, and the metadata that reproduces the solve world.solve(engine)

Two ideas recur everywhere:

  • Cluster. Electrodes joined by ideal conductors (a conductor without a cross_section) are one galvanic cluster with one potential. A cable with a cross-section is a branch with its own resistance between two clusters.
  • Node. Electrodes and junctions are the nodes of the conductor network. Conductors connect nodes; sources inject current at a node.

What happens in a solve

world.solve(engine)
 1. check        the backend's capabilities (soil layers, kernel, concrete shells)
                 and the resource limit, before anything is allocated
 2. discretise   every wire into straight segments of at most segment_length,
                 split at layer interfaces
 3. soil         the reaction matrix: the potential every segment's current
                 causes at every other segment (Green's function of the soil)
 4. network      the nodal equations: soil matrix + Kirchhoff's current law at
                 every node + Ohm's law along every conductor + the sources
 5. result       one solution per frequency: potentials, currents, impedances,
                 point sources for the field, metadata

Below 1 kHz the soil behaves as a pure conductor: no displacement current, and a skin depth large against a low-voltage network. Step 3 is therefore the stationary current field of the electrodes in a horizontally layered half-space; it does not depend on frequency and is computed once per world. Frequency enters in step 4 through the conductors: their resistance (optionally with skin effect), partial inductances and the earth-return impedance make the network equations complex. A purely galvanic world is solved once and reused for every frequency; a world with inductive conductors is solved once per frequency, which is cheap against step 3. The engines page gives the equations, the earth-return page the conductor impedance.

The engines differ in steps 2 and 3: how many unknown currents a wire carries (one per straight wire, or one per segment) and how the Green's function is evaluated (closed-form image series, numerical Sommerfeld quadrature, or a finite-element volume mesh instead).

What a result contains

Access Meaning Unit
result.frequencies the frequencies of the engine, in their order Hz
result.input_impedance(source) the voltage at a source over its current: what a fault or an earth tester sees Ω
result.cluster_impedance(electrode) the potential of a cluster over the current it leaks itself Ω
result.grounding_impedance(electrode) the potential of a cluster over one electrode's leakage current Ω
result.electrode_potentials[name] the potential of an electrode against remote earth (the EPR for the source current) V
result.electrode_currents[name] the current an electrode leaks into the soil A
result.potential(points) the potential at any points in or on the soil (homogeneous and two-layer soil) V
result.metadata backend, effective backend, kernel, version, segments, solve time, series controls, provenance —

Every quantity is a complex RMS phasor with one value per frequency (units and conventions). Touch and step voltages, current sharing, plots, sweeps and reduced models are functions that take a result: touch_voltage, step_voltage, cluster_current_balance, plot_surface_potential, sweep, fit_rho_f_standard and others (postprocess). save_result and load_result store a result with its provenance.

The three impedances coincide for a single electrode and differ in a network: the input impedance is what the feeding point sees (and what a measurement approaches), the cluster impedance is the local spreading impedance of the fed cluster. The input impedance is the default of the sweeps and fits since 2026.11; the sources page has the definitions.

Modelling assumptions

  • Quasi-static field for \(f \lesssim 1\) kHz: stationary current flow in the soil, no displacement current; the soil permittivity is inert.
  • Horizontally layered soil with piecewise constant resistivity; layer stacks are canonicalised (equal adjacent layers merged).
  • Thin wires: the wire radius is small against the segment length and the distance to other wires; the current flows on the axis, the potential is observed on the surface.
  • Current model: uniform leakage per unit length per straight wire of an electrode (and layer) in the image family — impedance-grade, not field-grade near grids and stars (image); one current per segment in the mom family.
  • Remote earth as the potential reference.
  • Conductor impedance from partial inductances and an earth-return correction; the Sommerfeld/Pollaczek kernel by default, Carson's series as a fast approximation for long parallel lines.

The reduced model

The objective of a field computation is not only a number but a model that a network calculation can use. For one feeding point the reduced model is the impedance as a function of soil resistivity and frequency. The standard form exported to groundinsight is

\[ Z(\rho, f) = k_0 + k_1\rho + (k_2 + jk_3)\,f + (k_4 + jk_5)\,f\rho , \]

with the resistance \(k_0\) that does not scale with \(\rho\) (the share of a lower soil layer, or the series resistance of conductors), the spreading resistance \(k_1\rho\), the soil-independent loop terms \(k_2 f\), \(k_3 f\) and Carson-type earth-return terms \(k_4 f\rho\), \(k_5 f\rho\). It is fitted by weighted linear least squares to a family of solves that spans both \(\rho\) and \(f\), with relative weights by default; max_relative reports the worst pointwise error and a fit above 5 % warns. Where the six-term form cannot follow the data (strongly layered soils), a vector fit of the frequency response per \(\rho\) is the alternative. For several feeding points the reduced model is the multiport matrix of the earthing systems (solve_mutual_matrix): its entry \(Z_{ij}\) is the potential of cluster \(i\) per ampere leaking from cluster \(j\). Together with the branch admittances \(\mathbf{Y}_L\) of the network and \(\mathbf{Y}_G = \mathbf{Z}^{-1}\) it forms the nodal system \((\mathbf{Y}_L + \mathbf{Y}_G)\,\mathbf{u} = \mathbf{i}\) of the AP1 catalogue, with the node voltages \(\mathbf{u}\) and the injected currents \(\mathbf{i}\).

Typical questions

groundfield is built for the dissertation questions on interconnected earthing systems of medium- and low-voltage networks:

  1. How strongly does a remote current injection influence an earthing measurement, and how is the measurement loop to be modelled?
  2. How important are coupling and return-path effects below 1 kHz?
  3. Which robust statements hold for typical distribution-network configurations, and how do they reduce to a small set of parameters?
  4. Which touch voltages arise in the fault case, and over which spectrum?

The tutorials walk through these computations; this explanation section gives the theory and the evidence behind them.