References¶
groundfield.references collects the closed-form results of the
classical literature that the numerical backends are validated
against. They are independent of the solver code: every engine and
every new geometry is checked against at least one of them (see the
validation page).
| Module | Source | Content | Used to check |
|---|---|---|---|
dwight1936 |
Dwight, Calculation of Resistances to Ground, AIEE Trans., Dec. 1936, Table I | rod, two rods (close / far), horizontal wire, right-angle wire, 3/4/6/8-point star, buried ring, strip, round and vertical plate, hemisphere | grounding resistance of the image and MoM families in homogeneous soil |
ieee80 |
IEEE Std 80-2013, Eq. 53 (Sverak; Eq. 57 of the 2000 edition) | resistance of a horizontal grid | grids; the Annex H benchmark grids are reproduced in tests/test_ieee80_benchmark.py |
oeding |
Oeding and Oswald, Elektrische Kraftwerke und Netze (Springer, 2016), ch. 9 | loop self and mutual inductance per unit length, internal inductance | Neumann inductance of distributed conductors |
carson |
Carson, Bell Syst. Tech. J. 5(4), 1926; Tleis, Power Systems Modelling and Fault Analysis, 2008 | worked examples and tabulated values | the Carson correction \(P, Q\) |
earth_return |
Carson's line impedance in engineering form | self and mutual earth-return impedance per unit length, equivalent depth \(D_e\), \(R' = \omega\mu_0/8\) | the assembled Sommerfeld/Pollaczek stack |
pollaczek |
Pollaczek (1926), Sunde (1968), Tsiamitros et al. (2005) | earth-return impedance of buried conductors in two-layer soil (self, mutual, conductor–earth loop) | layered earth return |
Mathematical and physical context¶
All formulas assume the same physics as the solver — quasi-static fields, linear isotropic soil — but in idealised geometries where the boundary-value problem has a closed or semi-closed solution. Two examples:
- Driven rod of length \(L\) and radius \(a\), top at the surface of a homogeneous soil (Dwight 1936): \(R = \dfrac{\rho}{2\pi L}\left(\ln\dfrac{4L}{a} - 1\right)\).
- Buried conductor at depth \(d\) in two-layer soil (Pollaczek, Sunde): the self impedance per unit length is a spectral integral with the effective vertical wavenumber of the layered earth; it reduces to Carson's line impedance for \(\rho_1 = \rho_2\) and lies between the two homogeneous Carson values otherwise.
Each reference states its own accuracy: Dwight's rod and ring formulas are asymptotic in \(a/L\) and accurate to well below 1 % for thin electrodes; Sverak's grid formula is an empirical estimate that IEEE 80 quotes to a few per cent for typical substation grids.
Example¶
import groundfield as gf
from groundfield.references import dwight1936, ieee80
def resistance(kind, **geometry):
"""Grounding resistance in Ω of one electrode in 100 Ω·m soil."""
world = gf.create_world(soil=gf.HomogeneousSoil(rho=100.0))
electrode = gf.create_electrode(world, kind, name="e", **geometry)
gf.create_source(world, attached_to="e", magnitude=1.0)
return gf.create_engine().solve(world).input_impedance()[0].real, electrode
R_rod, rod = resistance("rod", position=(0.0, 0.0, 0.0), length=3.0) # 35.99 Ω
R_grid, grid = resistance(
"grid_mesh", corner=(-10.0, -10.0, 0.5), size=(20.0, 20.0), n_x=5, n_y=5
) # 2.31 Ω
R_dwight = dwight1936.rod(rho=100.0, length=3.0, radius=0.005) # 35.99 Ω
R_sverak = ieee80.grid_resistance_sverak(
rho=100.0, total_conductor_length=grid.total_length(), area=400.0, depth=0.5
) # 2.54 Ω
assert abs(R_rod / R_dwight - 1) < 1e-3 # closed form: agreement to 0.01 %
assert abs(R_grid / R_sverak - 1) < 0.10 # empirical estimate: 9 % for this small grid
API reference¶
dwight1936 ¶
Grounding resistances of simple geometries after Dwight (1936).
Source
Dwight, H. B.: Calculation of Resistances to Ground. Electrical Engineering / AIEE Transactions, Vol. 55, No. 12, December 1936, pp. 1319-1328 (Paper 36-129). In particular the summary Table I on p. 1325.
Conventions
- All lengths are given in metres (Dwight uses cm; the SI conversion is lossless because only dimensionless ratios and the prefactor \(\rho/(\dots\pi L)\) appear).
- \(\rho\) is the resistivity of the homogeneous soil in \(\Omega\,\mathrm{m}\).
- For buried electrodes Dwight's Table I uses \(s\) for the image
distance, i.e. twice the burial depth: \(s = 2\,t\), where
\(t\) is the depth of the centre of the electrode below the
surface. The functions defined here take
depth(= \(t\)) and convert internally to \(s = 2\,t\). - Wire parameters:
ais the wire radius (not the diameter); for geometries that use the wire diameter \(d\) in Table I (the ring), the conversiond = 2*aapplies.
Range of validity
All formulas assume homogeneous soil in the low-frequency
(quasi-static) regime. Dwight quotes a few-percent accuracy for most
expressions (Howe's average-potential method). The rod formula is
within < 1 %; the star geometries within a few percent
(Dwight 1936, p. 1324, "equations 23 to 26").
Notes
The functions are pure Python scalars (NumPy scalars also work). They are intentionally not vectorised — comparison tests need clarity, not performance.
buried_ring ¶
Buried wire ring, Table I, Eq. (29). $$ R = \frac{\rho}{2\pi^2\,D}\, \Bigl(\ln\tfrac{8D}{d} + \ln\tfrac{4D}{s}\Bigr) $$
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
ring_diameter
|
float
|
Ring diameter \(D\) in m. |
required |
wire_diameter
|
float
|
Wire diameter \(d\) in m (i.e. |
required |
depth
|
float
|
Burial depth \(t\) in m; \(s = 2\,t\). |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Notes
Validity: \(d \ll s \ll D\). Outside this regime the error grows quickly.
Source code in src/groundfield/references/dwight1936.py
hemisphere ¶
Hemispherical electrode of radius \(A\) at the soil surface. $$ R = \frac{\rho}{2\pi A} $$ (Dwight, p. 1320: hemisphere + image = full sphere, \(C_{\text{full sphere}} = A\), hence \(R = \rho/(2\pi C) = \rho/(2\pi A)\).)
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
radius
|
float
|
Hemisphere radius \(A\) in m. |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/dwight1936.py
horizontal_round_plate ¶
Horizontal round plate, Table I (Eqs. 32 + 36). $$ R = \frac{\rho}{8 a} + \frac{\rho}{4\pi s}\, \Bigl(1 - \tfrac{7 a^2}{12 s^2} + \tfrac{33 a^4}{40 s^4}\Bigr) $$ Assumption: plate plane parallel to the soil surface; image distance \(s = 2\,t\) ≫ plate radius \(a\) for the series to converge.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
radius
|
float
|
Plate radius \(a\) in m. |
required |
depth
|
float
|
Burial depth \(t\) of the plate in m; internally \(s = 2t\). |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Source code in src/groundfield/references/dwight1936.py
horizontal_strip ¶
Buried strip electrode (rectangular cross-section), Table I, Eq. (31). $$ R = \frac{\rho}{4\pi L}\, \Bigl(\ln\tfrac{4L}{a} + \tfrac{a^2 - \pi a b}{2(a+b)^2} + \ln\tfrac{4L}{s} - 1 + \tfrac{s}{2L} - \tfrac{s^2}{16 L^2} + \tfrac{s^4}{512 L^4}\Bigr) $$
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
length
|
float
|
Half the strip length \(L\) in m (total length |
required |
width
|
float
|
Strip width \(a\) in m. |
required |
thickness
|
float
|
Strip thickness \(b\) in m. Validity: \(b < a/8\). |
required |
depth
|
float
|
Burial depth \(t\) in m; \(s = 2\,t\). |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Notes
The constant is \(-1\), not the \(-2\) of the round-wire form
horizontal_wire(), because the strip bracket already carries
the cross-section term \((a^2 - \pi a b)/(2(a+b)^2) \to 1/2\) as
\(b \to 0\):
i.e. a vanishingly thin strip of width \(a\) is the round wire of
radius equal to the strip's self-GMD \(a\,e^{-3/2}\). That is the
consistency check: for \(b \to 0\) this function equals
horizontal_wire(rho, L, a*exp(-1.5), depth) up to the \(O(b/a)\)
residual of the cross-section term (8.6e-6 relative at
\(a = 30\) mm, \(b = 1\) µm; 8.6e-9 at \(b = 1\) nm). Corrected in
0.15.0 (finding F37): the \(-2\) used up to 0.14.1 made the bracket
one full unit too small, i.e. \(R\) low by \(\rho/(4\pi L)\) —
10 % at \(a = 30\) mm, 13 % at \(a = 300\) mm for \(L = 10\) m,
\(t = 0.8\) m.
Source code in src/groundfield/references/dwight1936.py
380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 | |
horizontal_wire ¶
Buried horizontal wire of total length \(2L\), Table I. $$ R = \frac{\rho}{4\pi L} \Bigl(\ln\tfrac{4L}{a} + \ln\tfrac{4L}{s} - 2 + \tfrac{s}{2L} - \tfrac{s^2}{16 L^2} + \tfrac{s^4}{512 L^4}\Bigr) $$
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
length
|
float
|
|
required |
radius
|
float
|
Wire radius \(a\) in m. |
required |
depth
|
float
|
Burial depth \(t\) in m. The image distance is \(s = 2\,t\). |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Source code in src/groundfield/references/dwight1936.py
n_point_star ¶
n-point star (star of \(n\) equal-length arms). Table I. $$ R = \frac{\rho}{2 n \pi L}\, \Bigl(\ln\tfrac{2L}{a} + \ln\tfrac{2L}{s} + c_0 + c_1\tfrac{s}{L} + c_2\tfrac{s^2}{L^2} + c_3\tfrac{s^4}{L^4}\Bigr) $$
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
arm_length
|
float
|
Length of a single arm \(L\) in m. |
required |
radius
|
float
|
Wire radius \(a\) in m. |
required |
depth
|
float
|
Burial depth \(t\) in m; internally \(s = 2\,t\). |
required |
n_arms
|
int
|
Number of arms. Supported values: 3, 4, 6, 8 (Dwight, Eqs. 23-26). |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/dwight1936.py
right_angle_wire ¶
Right-angle wire: two arms of length \(L\), Table I, Eq. (22).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
arm_length
|
float
|
Length \(L\) of each arm in m. |
required |
radius
|
float
|
Wire radius \(a\) in m. |
required |
depth
|
float
|
Burial depth \(t\) in m; internally \(s = 2t\). |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Source code in src/groundfield/references/dwight1936.py
rod ¶
Vertical driven rod (single ground rod), Eq. (13) / Table I. $$ R = \frac{\rho}{2\pi L}\,\bigl(\ln\tfrac{4L}{a} - 1\bigr) $$ Assumptions: rod starts at the soil surface and extends \(L\) downwards; the rod is treated together with its image in the half-space. Wire radius \(a \ll L\).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
length
|
float
|
Rod length \(L\) in m. |
required |
radius
|
float
|
Rod radius \(a\) in m. |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/dwight1936.py
two_rods_close ¶
Two parallel rods, axis spacing \(s < L\). Table I, Eq. (21). $$ R = \frac{\rho}{4\pi L}\Bigl(\ln\tfrac{4L}{a} + \ln\tfrac{4L}{s} - 2 + \tfrac{s}{2L} - \tfrac{s^2}{16 L^2} + \tfrac{s^4}{512 L^4}\Bigr) $$ Suitable for closely-spaced rods, \(s \ll L\).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
length
|
float
|
Length \(L\) of each rod in m. |
required |
radius
|
float
|
Rod radius \(a\) in m. |
required |
spacing
|
float
|
Horizontal axis-to-axis distance \(s\) in m. |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance of the two rods in parallel, in Ω. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/dwight1936.py
two_rods_far ¶
Two parallel rods, axis spacing \(s > L\). Table I, Eq. (20).
$$
R = \frac{\rho}{4\pi L}\bigl(\ln\tfrac{4L}{a} - 1\bigr)
+ \frac{\rho}{4\pi s}\,
\Bigl(1 - \tfrac{L^2}{3 s^2}
+ \tfrac{2 L^4}{5 s^4}\Bigr)
$$
Assumption: spacing is the horizontal axis-to-axis distance.
The series is an expansion for large s/L and is usable for
\(s/L \gtrsim 1\).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
length
|
float
|
Length \(L\) of each rod in m. |
required |
radius
|
float
|
Rod radius \(a\) in m. |
required |
spacing
|
float
|
Horizontal axis-to-axis distance \(s\) in m. |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance of the two rods in parallel, in Ω. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/dwight1936.py
vertical_round_plate ¶
Vertical round plate, Table I (Eqs. 32 + 38). $$ R = \frac{\rho}{8 a} + \frac{\rho}{4\pi s}\, \Bigl(1 + \tfrac{7 a^2}{24 s^2} + \tfrac{99 a^4}{320 s^4}\Bigr) $$ Assumption: plate plane perpendicular to the soil surface; image distance \(s = 2\,t\) ≫ plate radius \(a\) for the series to converge.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Resistivity of the homogeneous soil in Ω·m. |
required |
radius
|
float
|
Plate radius \(a\) in m. |
required |
depth
|
float
|
Burial depth \(t\) of the plate centre in m; internally \(s = 2t\). |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grounding resistance in Ω. |
Notes
Same leading image term \(\rho/(4\pi s)\) as
horizontal_round_plate() — the orientation of the plate is
invisible in the far field, so the two must agree to
\(O(a^2/s^2)\); only the sign and size of the \(a^2\) correction
differ (Eq. 38 vs Eq. 36), because the vertical plate presents its
edge, not its face, to the image. (Corrected in 0.15.0 — finding
F38; up to 0.14.1 the divisor carried an extra factor 2, halving
the image term, because s had been read as the burial depth
rather than as the plate-to-image distance it already is.)
Source code in src/groundfield/references/dwight1936.py
ieee80 ¶
IEEE Std 80 grounding-grid reference formulas.
Source
IEEE Std 80, IEEE Guide for Safety in AC Substation Grounding. The grid grounding-resistance estimate implemented here is Sverak's equation, IEEE Std 80-2000 Eq. (57) — identical to IEEE Std 80-2013 Eq. (53) — which refines the earlier Laurent–Niemann expression by an explicit burial-depth term.
Conventions
- SI units throughout: resistivity in Ω·m, lengths in m, areas in m².
depthis the burial depth \(h\) of the horizontal grid below the soil surface; ground rods (if any) are folded intototal_conductor_length.
Range of validity
Sverak's formula assumes uniform soil and a horizontal grid. IEEE
Std 80 states it for burial depths \(0.25\,\mathrm{m} \le h \le
2.5\,\mathrm{m}\) and quotes an accuracy of a few percent for typical
substation grids; the groundfield image backend reproduces it to
well under 1 % (tests/test_ieee80_benchmark.py).
Notes
Pure-Python scalars, intentionally not vectorised — comparison tests
need clarity, not performance (mirrors
groundfield.references.dwight1936).
grid_resistance_sverak ¶
grid_resistance_sverak(rho: float, total_conductor_length: float, area: float, depth: float) -> float
Grid grounding resistance after Sverak (IEEE Std 80 Eq. 57).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Uniform soil resistivity \(\rho\) in Ω·m. |
required |
total_conductor_length
|
float
|
Total buried length \(L_T\) of all grid conductors (plus any ground rods) in metres. |
required |
area
|
float
|
Area \(A\) of ground occupied by the grid in m². |
required |
depth
|
float
|
Burial depth \(h\) of the grid in metres. IEEE Std 80 states the formula for \(0.25 \le h \le 2.5\) m. |
required |
Returns:
| Type | Description |
|---|---|
float
|
Grid grounding resistance \(R_g\) in Ω. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Notes
In the two limits the formula behaves as expected: \(h \to \infty\) removes the second bracket term (deep grid, no surface image boost) while \(h \to 0\) doubles it (grid at the surface). The \(1/L_T\) term is the conductor's own spreading contribution and vanishes for a very dense grid.
Source code in src/groundfield/references/ieee80.py
oeding ¶
Inductance formulas from Oeding/Oswald 2016, Elektrische Kraftwerke und Netze, chapter 9 (overhead lines) and chapter 16 (cables).
This module collects the per-unit-length loop self- and mutual
inductance formulas that the standard German power-engineering
reference uses to characterise long, parallel conductor systems.
They are the textbook results that the segment-based Neumann
implementation in groundfield.coupling.inductance must
reproduce in the limit \(\ell \to \infty\).
All formulas assume:
- straight, parallel conductors,
- conductor radius small compared to inter-conductor distance,
- non-magnetic conductors (\(\mu_r = 1\)),
- DC / quasi-static current distribution
(uniform across the cross section, internal-field contribution
\(\mu_0 / (8\pi)\) per wire, see
include_internalknobs).
The earth-return path is not included here — those corrections (Carson, Pollaczek) live in their own reference modules in a later release.
References
Oeding, D. & Oswald, B. R. (2016). Elektrische Kraftwerke und Netze, 8th ed., Springer.
- §9.3, Eq. (9.8) / (9.9): mutual-inductance per unit length between two two-wire loops, with mean geometric distances.
- §9.3, Eq. (9.13b) / (9.13c): self-inductance per unit length of a two-wire loop.
- Anhang A.7: mean geometric distances for typical cross-sectional geometries (rod with itself: \(g_{11} = r \cdot e^{-1/4}\)).
MU_0
module-attribute
¶
Vacuum permeability μ0 = 4π · 10⁻⁷ H/m (the conventional value).
internal_inductance_per_length ¶
Internal-field inductance per unit length of a single round conductor with uniform DC current distribution and \(\mu_r = 1\).
Closed-form result \(L'_\text{int} = \mu_0 / (8\pi)\) — the classical textbook value, independent of the wire radius.
Returns:
| Name | Type | Description |
|---|---|---|
L_per_length |
float
|
\(5.0 \cdot 10^{-8}\) H/m, to numerical precision. |
Source code in src/groundfield/references/oeding.py
loop_mutual_inductance_per_length ¶
Mutual-inductance per unit length between two two-wire loops.
Implements Oeding/Oswald 2016 Eq. (9.8):
Loop I consists of wires 1 and 2 (carrying currents \(+I\) and
\(-I\)); loop II consists of wires 3 and 4. The arguments are
centre-to-centre distances between the indicated wire pairs;
they must all be positive (no wire pair coincides — the
self-inductance limit is handled by
loop_self_inductance_per_length() instead).
The same formula applies — with appropriate mean-geometric distances \(g_{ij}\) in place of the centroid distances \(s_{ij}\) (Oeding/Oswald: Schwerpunktabstände) — to wires of finite cross section (Eq. 9.9 in Oeding/Oswald 2016). For circular cross sections with \(r \ll s\) the difference is negligible.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
s13
|
float
|
Centre-to-centre distances in metres. |
required |
s14
|
float
|
Centre-to-centre distances in metres. |
required |
s23
|
float
|
Centre-to-centre distances in metres. |
required |
s24
|
float
|
Centre-to-centre distances in metres. |
required |
Returns:
| Name | Type | Description |
|---|---|---|
L_per_length |
float
|
Mutual inductance per unit length in H/m. Sign follows the
wire-numbering convention (positive when both loops carry
currents in the conventional |
Raises:
| Type | Description |
|---|---|
ValueError
|
If any of the four distances is not positive. |
Source code in src/groundfield/references/oeding.py
loop_self_inductance_per_length ¶
loop_self_inductance_per_length(distance: float, wire_radius: float, *, include_internal: bool = True) -> float
Self-inductance per unit length of a two-wire loop.
Implements Oeding/Oswald 2016 Eq. (9.13c):
valid for two long, straight, parallel wires of radius \(r\) at centre-to-centre distance \(d\), with \(d \gg r\).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
distance
|
float
|
Centre-to-centre distance \(d\) between the two wires (m). |
required |
wire_radius
|
float
|
Wire radius \(r\) (m). |
required |
include_internal
|
bool
|
|
True
|
Returns:
| Name | Type | Description |
|---|---|---|
L_per_length |
float
|
Loop self-inductance per unit length in H/m. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/oeding.py
two_wire_loop_radius ¶
Effective wire radius \(r' = r \cdot e^{-1/4}\) used in the Oeding loop-inductance formulas.
The factor \(e^{-1/4}\) is the mean geometric distance of a circular cross section from itself (Anhang A.7, case 1) and folds the internal-field contribution \(\mu_0 / (8\pi)\) into a purely geometric expression. With \(r' = r \cdot e^{-1/4}\) the loop self-inductance becomes \(L'_S = (\mu_0 / \pi) \ln(d/r')\), which equals \((\mu_0 / \pi)(\ln(d/r) + 1/4)\) — Eq. (9.13c).
Pass include_internal=False to suppress the substitution and
obtain the pure external-field expression.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
wire_radius
|
float
|
Wire radius \(r\) in m. |
required |
include_internal
|
bool
|
|
True
|
Returns:
| Type | Description |
|---|---|
float
|
Effective wire radius in m. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/oeding.py
carson ¶
Closed-form Carson 1926 reference values for the test suite.
This module collects the worked examples and tabulated values from
Carson's original paper (Bell Syst. Tech. J. 5(4), 1926, pp.
539–554) plus a small set of textbook reference cases from
Tleis 2008 and Oeding/Oswald 2016. They are the ground truth that
the implementation in groundfield.coupling.carson must
reproduce.
All values are returned in the dimensionless form
\(J(p, q) = P(a, \theta) + j Q(a, \theta)\) — the bare Carson
integral, without the \((\omega \mu_0 / \pi)\) pre-factor. The
production code applies that pre-factor in
carson_self_correction() and
carson_mutual_correction().
References
- Carson, J. R. (1926). Wave propagation in overhead wires with ground return. Bell Syst. Tech. J. 5(4), 539–554. Section V worked examples are reproduced verbatim.
- Tleis, N. D. (2008). Power Systems Modelling and Fault Analysis, Newnes, Tab. 3.2 (P, Q values for the intermediate-\(a\) regime).
- Oeding, D. & Oswald, B. R. (2016). Elektrische Kraftwerke und Netze, 8. Aufl., Springer, §9.4.
RAILWAY_25HZ
module-attribute
¶
RAILWAY_25HZ = CarsonExample(name='Railway induction (Carson 1926 p. 553)', a=0.2, theta=math.radians(63.5), P_expected=0.369, Q_expected=1.135, abs_tolerance=0.005, rel_tolerance=0.01, source='Carson 1926, Bell STJ 5(4), §V, p. 553')
Carson's railway-induction example (1926, §V, p. 553) at 25 Hz.
Trolley wire and telephone line at 10 m height, 40 m apart:
a = 0.2, theta = 63.5°; reference value J = 0.369 + j 1.135.
TLEIS_TAB_3_2
module-attribute
¶
Four regression anchors of the Carson integral (tuple of CarsonExample).
The values come from a direct numerical evaluation of Carson's Eq. 29
(Gauss-Legendre quadrature) across the small-a, intermediate and
asymptotic regimes, not from Tleis (2008), Tab. 3.2. The name is a
backwards-compatible alias retained from an early draft.
WAVE_ANTENNA_HIGH_RHO
module-attribute
¶
WAVE_ANTENNA_HIGH_RHO = CarsonExample(name='Wave antenna, high rho (Carson 1926 p. 552)', a=4.0, theta=0.0, P_expected=0.126, Q_expected=0.168, abs_tolerance=0.005, rel_tolerance=0.05, source='Carson 1926, Bell STJ 5(4), §V, p. 552')
Carson's wave-antenna example (1926, §V, p. 552) at a = 4.0, theta = 0.
The asymptotic regime of the Carson series; reference value J = 0.126 + j 0.168.
WAVE_ANTENNA_LOW_RHO
module-attribute
¶
WAVE_ANTENNA_LOW_RHO = CarsonExample(name='Wave antenna, low rho (Carson 1926 p. 552)', a=0.4, theta=0.0, P_expected=0.323, Q_expected=0.871, abs_tolerance=0.02, rel_tolerance=0.03, source='Carson 1926, Bell STJ 5(4), §V, p. 552')
Carson's wave-antenna example (1926, §V, p. 552) at a = 0.4, theta = 0.
The intermediate regime of the Carson series; reference value J = 0.323 + j 0.871 as printed by Carson (a modern evaluation gives Q ≈ 0.853, hence the 3 % relative tolerance).
CarsonExample
dataclass
¶
CarsonExample(name: str, a: float, theta: float, P_expected: float, Q_expected: float, abs_tolerance: float = 0.0, rel_tolerance: float = 0.05, source: str = '')
One worked example for the Carson series test suite.
Attributes:
| Name | Type | Description |
|---|---|---|
name |
str
|
Human-readable label. |
a |
float
|
Carson parameter \(a = D \sqrt{\omega\mu_0\sigma}\). |
theta |
float
|
Carson angle \(\theta\) in radians (\(\theta = 0\) for the self-impedance case, \(\arctan(d/(h_i+h_j))\) for mutual). |
P_expected |
float
|
Reference value for the real part \(P\) of the Carson integral \(J = P + jQ\). |
Q_expected |
float
|
Reference value for the imaginary part \(Q\) of \(J\). |
abs_tolerance |
float
|
Absolute tolerance on \(P\) and \(Q\) against which the implementation is compared (default 0.0). |
rel_tolerance |
float
|
Relative tolerance on \(P\) and \(Q\) (default 0.05). The test passes if either bound is met. |
source |
str
|
Bibliographic source. |
all_examples ¶
Return all Carson reference examples used by the test suite.
Returns:
| Type | Description |
|---|---|
tuple of CarsonExample
|
The three Carson 1926 worked examples followed by the four
regression anchors of |
Source code in src/groundfield/references/carson.py
earth_return ¶
Carson earth-return line-impedance reference (per unit length).
Closed-form series impedance of a conductor with earth return, as
derived by Carson (1926) and reproduced in every power-system textbook.
It is the engineering-level (Ω/km) companion to the dimensionless Carson
integral tabulated in groundfield.references.carson, and the
reference against which the assembled Sommerfeld/Pollaczek earth-return
stack (earth_inductive_model="sommerfeld") is benchmarked in
tests/test_earth_return_benchmark.py and
notebooks/45_earth_return_line_impedance.ipynb.
Mathematical background
For a thin conductor of geometric mean radius \(\mathrm{GMR}\) above or below a homogeneous earth of resistivity \(\rho\), carrying a current that returns through the earth, Carson's series impedance per unit length at angular frequency \(\omega = 2\pi f\) is
where \(d_{ij}\) is the conductor–conductor separation and
is Carson's equivalent earth-return depth — the depth of the fictitious return conductor that reproduces the earth's inductive effect. Two features carry the physics:
- the earth-return resistance \(R'_\text{earth} = \omega\mu_0/8\) (\(\approx 0.0493\) Ω/km at 50 Hz) is independent of the soil resistivity — it is the loss of the return current spreading through the earth;
- the equivalent depth \(D_e \propto \sqrt{\rho/f}\) shrinks with frequency and grows with soil resistivity — a more resistive or lower-frequency earth lets the return current spread deeper and wider. The earth-return reactance \(X' = (\omega\mu_0/2\pi)\ln(D_e/\mathrm{GMR})\) therefore increases with soil resistivity and also increases with frequency: the \(\omega\) prefactor dominates the shrinking logarithm, so \(X'\) rises almost linearly with \(f\) (1000 Ω·m, GMR = 7 mm: 0.814 mΩ/m at 50 Hz → 14.39 mΩ/m at 1 kHz, a 17.7× rise over a 20× frequency step).
Internal-inductance convention (review pass 10, finding 10.46). The
formulas here are external to the conductor for a given
\(\mathrm{GMR}\). The assembled inductive stack of groundfield adds
the DC internal inductance \(\mu_0/(8\pi)\) per metre of a solid round
conductor to every self term by default
(groundfield.coupling.inductance.thin_wire_self_inductance(),
include_internal=True), so a like-for-like comparison uses
\(\mathrm{GMR} = a\,e^{-1/4} = 0.7788\,a\); with GMR = a the
stack sits 2.0–2.5 % above Carson's reactance (100 Ω·m at 50 Hz to
30 Ω·m at 1 kHz, 4 mm wire) for that reason alone. Use GMR = a
together with include_internal=False. The frequency dependence of the
internal impedance (skin effect) is
groundfield.conductors.Conductor.internal_impedance_per_length().
References
- Carson, J. R. (1926). Wave propagation in overhead wires with ground return. Bell Syst. Tech. J. 5(4), 539–554.
- Tleis, N. D. (2008). Power Systems Modelling and Fault Analysis, Newnes, §3.2 (earth-return impedance, equivalent depth \(D_e\)).
- Oeding, D. & Oswald, B. R. (2016). Elektrische Kraftwerke und Netze,
- Aufl., Springer, §9.4.
MU_0
module-attribute
¶
Vacuum permeability μ0 = 4π · 10⁻⁷ H/m (the conventional value).
carson_earth_return_resistance ¶
Carson earth-return resistance per unit length \(\omega\mu_0/8\).
Independent of the soil resistivity. Returns Ω/m.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
frequency
|
float
|
Frequency in Hz. Must be positive. |
required |
Returns:
| Type | Description |
|---|---|
float
|
Earth-return resistance in Ω/m (\(\approx 4.93\times10^{-5}\) at 50 Hz, i.e. 0.0493 Ω/km). |
Source code in src/groundfield/references/earth_return.py
carson_equivalent_depth ¶
Carson equivalent earth-return depth \(D_e = 658.87\sqrt{\rho/f}\).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Soil resistivity in Ω·m. Must be positive. |
required |
frequency
|
float
|
Frequency in Hz. Must be positive. |
required |
Returns:
| Type | Description |
|---|---|
float
|
Equivalent depth in metres. |
Source code in src/groundfield/references/earth_return.py
carson_mutual_impedance ¶
Carson earth-return mutual impedance per unit length (Ω/m).
\(Z' = \omega\mu_0/8 + j\,(\omega\mu_0/2\pi)\ln(D_e/d)\), the
per-unit-length coupling between two parallel conductors a horizontal
distance separation apart, both closing through the earth. This is
the impedance behind an induced voltage on a parallel measurement /
pilot line — Carson's original railway-induction problem.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Soil resistivity in Ω·m. Must be positive. |
required |
frequency
|
float
|
Frequency in Hz. Must be positive. |
required |
separation
|
float
|
Conductor–conductor distance in m. Must be positive. |
required |
Returns:
| Type | Description |
|---|---|
complex
|
Mutual impedance \(R' + jX'\) in Ω/m. |
Source code in src/groundfield/references/earth_return.py
carson_self_impedance ¶
Carson earth-return self impedance per unit length (Ω/m).
\(Z' = \omega\mu_0/8 + j\,(\omega\mu_0/2\pi)\ln(D_e/\mathrm{GMR})\), the external earth-return series impedance of a single conductor (no internal-conductor resistance or inductance).
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho
|
float
|
Soil resistivity in Ω·m. Must be positive. |
required |
frequency
|
float
|
Frequency in Hz. Must be positive. |
required |
gmr
|
float
|
Geometric mean radius of the conductor in m: the physical wire
radius \(a\) for an external-inductance model, |
required |
Returns:
| Type | Description |
|---|---|
complex
|
Series impedance \(R' + jX'\) in Ω/m. |
Source code in src/groundfield/references/earth_return.py
pollaczek ¶
Layered (Pollaczek/Sunde) earth-return line impedance reference.
The per-unit-length self and mutual impedances of conductors
buried in a two-layer earth, as exact quasi-static spectral integrals.
This is the layered, buried-conductor companion to
groundfield.references.earth_return.carson_self_impedance(): where
Carson gives the homogeneous equivalent-depth closed form, this gives the
spectral integral over a stratified earth, and reduces to Pollaczek's
homogeneous form for rho_1 == rho_2.
It is the analytic per-unit-length quantity that the assembled
Sommerfeld/Pollaczek stack (earth_inductive_model="sommerfeld") does
not expose directly — the assembled stack builds a PEEC segment
inductance matrix, from which a single per-unit-length line impedance
cannot be read back without an ill-defined return-path assumption. This
closed integral form therefore both (a) serves callers that need a
frequency- and layer-dependent series impedance belag z'(f) (e.g. a
reduced nodal network of a distribution earthing system) and (b) gives
groundfield an independent per-unit-length reference against which the
assembled stack's earth-return reactance can be benchmarked.
Mathematical background
A line current at depth \(h\) in a two-layer earth (layer 1 of thickness \(h_1\) and resistivity \(\rho_1\) over a half-space \(\rho_2\), air above) has the quasi-static vector potential
with \(\gamma_k^2 = j\omega\mu_0/\rho_k\) of the conductor's layer and \(u_k = \sqrt{\lambda^2 + \gamma_k^2}\). The spectral amplitude \(F\) follows exactly from the continuity of \(A\) and \(\partial A/\partial z\) at the soil surface and at the layer interface (Tsiamitros et al. 2005, Eq. 8). For a conductor in layer 1, with \(r_0 = (u_1-\lambda)/(u_1+\lambda)\) and \(K = (u_1-u_2)/(u_1+u_2)\),
and the per-unit-length self impedance is
Conductors in layer 2 and pairs in different layers use the
corresponding generalised-reflection and transmission amplitudes (see
_two_layer_amplitude()). For \(\rho_1 = \rho_2\) the form
reduces to the homogeneous Pollaczek integral
\(K_0(\gamma\,\mathrm{GMR}) - K_0(2\gamma h) + 2\int_0^\infty e^{-2hu}/(\lambda+u)\,d\lambda\).
Review pass 10 (finding 10.45) replaced two approximations of earlier releases:
- the two-layer kernel used the surface wavenumber
\(u_\text{eff}\) of the layered earth (Tagg/Sunde/Wait recursion,
layered_effective_wavenumber()) in the buried exponent, \(e^{-2h u_\text{eff}}/(\lambda + u_\text{eff})\) — exact only for \(h \to 0\) or \(\rho_1 = \rho_2\); it missed the lower-interface term \(K e^{-2u_1(h_1-h)}\): \(R'\) −0.13…−0.5 % in band near an interface, −28.5 % at 1 MHz; - the head term was the small-argument form \(\ln(2h/\mathrm{GMR})\) of \(K_0(\gamma\,\mathrm{GMR}) - K_0(2\gamma h)\): \(R'\) −0.15 % (1 m) and −0.99 % (3 m) at 30 Ω·m, 1 kHz — more than the documented "< 0.05 %".
Both are now exact at every frequency (quasi-static) for the same cost.
Note the exponent: for a conductor buried in the earth the vertical decay of the reflected field is governed by \(u_1\), not by \(\lambda\). The Laplace kernel \(e^{-2h\lambda}\) is Carson's air kernel, valid only for a conductor above the interface; using it below the interface under-counts \(R'\) and inverts the sign of its depth dependence (fixed in 0.15.0, pass-9 F09).
Internal-inductance convention. Like
groundfield.references.earth_return, this returns the
earth-return series impedance, external to the conductor, for the
geometric mean radius gmr: pass gmr equal to the physical wire
radius \(a\) for a pure external model, or
\(a\,e^{-1/4} = 0.7788\,a\) to include the DC internal inductance
\(\mu_0/(8\pi)\) of a solid round conductor — the convention of the
assembled inductive stack (include_internal=True, the default of
groundfield.coupling.inductance.thin_wire_self_inductance()).
Limiting cases (all covered by the regression tests):
rho_1 == rho_2— homogeneous Pollaczek, which matchescarson_self_impedance()to well under 1 % in the reactance across 50 Hz – 1 kHz; the earth-return resistance sits slightly above \(\omega\mu_0/8\) (Carson's low-frequency, surface-return limit) and rises with burial depth and with frequency.h_1 → ∞— upper layer only;h_1 → 0(conductor in layer 2) — lower layer only.- two-layer — the reactance lies within the
[carson(rho_1), carson(rho_2)]bracket, weighted toward the deeper, more conductive layer at low frequency.
References
- Pollaczek, F. (1926). Über das Feld einer unendlich langen wechselstromdurchflossenen Einfachleitung. Elektr. Nachr.-Techn. 3, 339–359.
- Sunde, E. D. (1949). Earth Conduction Effects in Transmission Systems, Van Nostrand, §§ 3–4 (buried-conductor earth-return, layered surface impedance).
- Wait, J. R. (1970). Electromagnetic Waves in Stratified Media, §2.
- Tsiamitros, D. A. et al. (2005). Earth return path impedances of underground cables for the two-layer earth case. IEEE Trans. Power Delivery 20(3), 2174–2181 (Eq. 8).
layered_effective_wavenumber ¶
layered_effective_wavenumber(lam: float, rho_1: float, rho_2: float, h_1: float, omega: float) -> complex
Effective vertical wavenumber \(u_\text{eff}(\lambda)\) of a two-layer earth.
The Tagg/Sunde/Wait tanh-recursion surface term: the input
wavenumber of the layered earth seen from the surface (it sets the
surface reflection coefficient \((u_\text{eff}-\lambda)/ (u_\text{eff}+\lambda)\) of an overhead conductor). It is not the
exponent of a buried conductor's kernel — the self and mutual
impedances of this module use the exact buried amplitude since review
pass 10 (finding 10.45). Reduces to the homogeneous half-space value \(u_1\) when
rho_1 == rho_2, to \(u_1\) as h_1 → ∞ and to \(u_2\)
as h_1 → 0. Units: 1/m.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
lam
|
float
|
Spectral (Hankel) variable, 1/m. |
required |
rho_1
|
float
|
Upper / lower layer resistivity in Ω·m. |
required |
rho_2
|
float
|
Upper / lower layer resistivity in Ω·m. |
required |
h_1
|
float
|
Upper-layer thickness in m. |
required |
omega
|
float
|
Angular frequency in rad/s. |
required |
Returns:
| Type | Description |
|---|---|
complex
|
Effective wavenumber \(u_\text{eff}\) in 1/m. |
Source code in src/groundfield/references/pollaczek.py
loop_impedance_conductor_earth ¶
loop_impedance_conductor_earth(rho_1: float, rho_2: float, h_1: float, frequency: float, *, depth: float, gmr: float, r_internal: float) -> complex
Conductor–earth loop impedance per unit length (Ω/m), ideal termination.
The series impedance seen by a current that flows out along a buried earthing conductor — a cable PEN, a cable screen — and returns through the earth, with the earthing electrodes at both ends idealised as \(\approx 0\,\Omega\):
This is the "go along the conductor, return through the soil" loop that
governs earth-fault current sharing and the reach of an earthing system
connected through cable PENs / screens — the quantity a bare
earth-return impedance (pollaczek_self_impedance()) does not give
on its own, because it omits the conductor's own series resistance.
Convention. The earth-return term carries the external inductance and,
through gmr, the conductor's internal inductance: for a solid
round conductor pass gmr = 0.7788·a = a·e^{-1/4} (a the physical
radius), which already includes the internal inductance
\(\mu_0/(8\pi)\); for a thin tubular / wire screen pass gmr equal
to the screen radius (negligible internal inductance). r_internal is
the conductor's series resistance per unit length — its DC / IEC 60228
value, or a skin-corrected AC value near the top of the band. With the
ideal (\(\approx 0\,\Omega\)) earthing at both ends the loop
impedance of a line of length \(\ell\) is simply
\(z'_\text{loop}\,\ell\); a real earthing resistance \(R_E\) at
the terminations adds in series on top of that.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho_1
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), exactly as in |
required |
rho_2
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), exactly as in |
required |
h_1
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), exactly as in |
required |
frequency
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), exactly as in |
required |
depth
|
float
|
Burial depth of the conductor in m. Must be positive. |
required |
gmr
|
float
|
Geometric mean radius in m — |
required |
r_internal
|
float
|
Conductor series resistance per unit length in Ω/m. Must be non-negative. |
required |
Returns:
| Type | Description |
|---|---|
complex
|
Loop series impedance \(R'_\text{loop} + jX'_\text{loop}\) in Ω/m. Multiply by the line length for the terminated loop impedance. |
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Notes
Earth-return path only: no mutual coupling to a parallel conductor, and
no internal skin-effect model (pass a skin-corrected r_internal if
that matters at the top of the band). A conductor–conductor loop (e.g.
line–PEN at a fixed spacing) has its return-path reactance set by that
spacing, not by the earth-return depth, and is much smaller — this
function is specifically the conductor–earth loop.
Examples:
>>> import math
>>> a = math.sqrt(150e-6 / math.pi) # 150 mm^2 solid-round radius
>>> z = loop_impedance_conductor_earth( # NAYY PEN, 100 Ohm.m, 50 Hz
... 100.0, 100.0, 10.0, 50.0,
... depth=0.7, gmr=0.7788 * a, r_internal=0.206e-3)
>>> round(z.real * 1e3, 3), round(z.imag * 1e3, 3) # mOhm/m -> Ohm/km
(0.255, 0.758)
Source code in src/groundfield/references/pollaczek.py
483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 | |
pollaczek_mutual_impedance ¶
pollaczek_mutual_impedance(rho_1: float, rho_2: float, h_1: float, frequency: float, *, depth_i: float, depth_j: float, separation: float) -> complex
Layered Pollaczek earth-return mutual impedance per unit length (Ω/m).
The per-unit-length coupling impedance between two parallel buried
conductors — each closing its current through the earth — over a
two-layer earth, in the same exact spectral form as
pollaczek_self_impedance():
with the horizontal separation \(x\), the direct distance \(d = \sqrt{x^2 + (h_i - h_j)^2}\), \(\gamma_k\) of the common layer and the exact two-layer amplitude \(F\) (module docstring). For two conductors in different layers there is no direct \(K_0\) term and \(F\) is the transmitted amplitude. In the homogeneous case the bracket is \(K_0(\gamma d) - K_0(\gamma D) + 2\int_0^\infty e^{-(h_i+h_j)u}/(\lambda + u)\cos(\lambda x)\,d\lambda\) with \(D = \sqrt{x^2 + (h_i + h_j)^2}\).
This is the mutual (off-diagonal) counterpart of
pollaczek_self_impedance(): the coupling that induces a voltage on
a parallel earthing conductor / cable through the shared earth-return
path — the term a self impedance alone omits. It carries no
internal-conductor term (the two conductors are galvanically separate;
the coupling is purely inductive through the soil), so with ideal
(\(\approx 0\,\Omega\)) earthing at both ends the coupling impedance
of a parallel run of length \(\ell\) is \(Z'_\text{M}\,\ell\).
Together with two self impedances it forms the \(2\times2\) loop
impedance matrix of the coupled pair.
Limiting behaviour (covered by the tests): it reduces to the homogeneous
Carson mutual impedance
(carson_mutual_impedance())
when \(\rho_1 = \rho_2\) (reactance to well under 1 % at low
frequency), its magnitude is below the self impedance and decays
monotonically with the separation \(x\), and its two-layer reactance
lies within the two homogeneous Carson bounds, deep-layer dominated at
low frequency.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho_1
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), as in |
required |
rho_2
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), as in |
required |
h_1
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), as in |
required |
frequency
|
float
|
Two-layer earth resistivities (Ω·m), upper-layer thickness (m) and
frequency (Hz), as in |
required |
depth_i
|
float
|
Burial depths of the two conductors in m. Must be positive. |
required |
depth_j
|
float
|
Burial depths of the two conductors in m. Must be positive. |
required |
separation
|
float
|
Horizontal centre-to-centre distance \(x\) between the
conductors in m. Must be non-negative; |
required |
Returns:
| Type | Description |
|---|---|
complex
|
Mutual series impedance \(R'_\text{M} + jX'_\text{M}\) in Ω/m. |
Notes
Earth-return coupling only: quasi-static, no displacement current. The
vertical decay in the soil is governed by \(u_1\), not by Carson's
air kernel \(e^{-(h_i+h_j)\lambda}\). As \(x \to \mathrm{GMR}\)
with \(depth_i = depth_j\) it recovers
pollaczek_self_impedance().
Raises:
| Type | Description |
|---|---|
ValueError
|
If |
Source code in src/groundfield/references/pollaczek.py
362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 | |
pollaczek_self_impedance ¶
pollaczek_self_impedance(rho_1: float, rho_2: float, h_1: float, frequency: float, *, depth: float, gmr: float) -> complex
Layered Pollaczek earth-return self impedance per unit length (Ω/m).
Exact two-layer, buried-conductor series impedance
\(Z' = R' + jX'\) (quasi-static), earth-return only — no internal
conductor resistance; the internal inductance is included only through
gmr (see the module docstring). Reduces to Pollaczek's homogeneous
form for rho_1 == rho_2 and agrees with
carson_self_impedance() in the reactance.
Parameters:
| Name | Type | Description | Default |
|---|---|---|---|
rho_1
|
float
|
Upper / lower layer resistivity in Ω·m. Must be positive. Set equal for a homogeneous earth. |
required |
rho_2
|
float
|
Upper / lower layer resistivity in Ω·m. Must be positive. Set equal for a homogeneous earth. |
required |
h_1
|
float
|
Upper-layer thickness in m. Must be positive (ignored when
|
required |
frequency
|
float
|
Frequency in Hz. Must be positive. |
required |
depth
|
float
|
Burial depth of the conductor in m. Must be positive; a depth
|
required |
gmr
|
float
|
Geometric mean radius of the conductor in m: the physical wire
radius for an external-inductance model, |
required |
Returns:
| Type | Description |
|---|---|
complex
|
Earth-return series impedance \(R' + jX'\) in Ω/m. |