Glossary (English / German)¶
The terms of the documentation and the code, with their German
counterparts and their meaning in groundfield. Use it to look up a term of
the package or of the numerics, or to find the English word for a German
one (German → English at the end). The documentation
and the code use English terms; the German terms are those of
DIN EN 50522 (VDE 0101-2), DIN 18014 and the German network practice.
Names of releases up to 0.15.0 that were German (kvs, OrtsnetzLayout,
…) are listed under Deprecations.
Network and installation¶
| English | German | Meaning in groundfield |
|---|---|---|
| LV network | Ortsnetz | low-voltage distribution network supplied by one MV/LV substation; generated by TnNetworkGenerator / LvNetworkLayout |
| MV/LV substation, substation | Ortsnetzstation (ONS) | transformer station feeding an LV network; substation in the generators |
| cable distribution cabinet | Kabelverteilerschrank (KVS) | street cabinet that branches the LV cables; cabinet in the generators (kvs up to 0.15.0) |
| service connection | Hausanschluss (HA), Hausanschlusskasten (HAK) | connection of a building to the LV network |
| service drop | Hausanschlussleitung | the cable from the PEN main to a building; generated by the network generators |
| single-family house | Einfamilienhaus (EFH) | the residential building type |
| multi-family house | Mehrfamilienhaus (MFH) | |
| small / medium commercial building | Gewerbe (klein / mittel) | the small_industry / medium_industry building types |
| TN system | TN-System | LV system whose neutral is earthed at the substation and connected to the exposed parts through the PEN / PE conductor |
| PEN conductor | PEN-Leiter | combined protective and neutral conductor; joins the earthing systems of an LV network (conductor_type="pen") |
| cable screen | Kabelschirm | metallic screen of a power cable; an earth-return path in parallel to the soil |
| overhead line, earth wire | Freileitung, Erdseil | conductor_type="overhead"; \(z < 0\) |
| MV network | Mittelspannungsnetz | the network of work package AP2 |
| neutral earthing | Sternpunktbehandlung | decides the earth-fault current in the MV network |
| single-line-to-earth fault | einpoliger Erdfehler, Erdschluss / Erdkurzschluss | fault that drives the current into the earthing systems |
| harmonics | Oberschwingungen | frequency components of a fault current up to 1 kHz (touch_voltage_spectrum) |
| work packages AP1, AP2 | Arbeitspakete | AP1: model of the TN LV network (catalogue of real networks); AP2: earthing system of the MV network |
Earthing system¶
| English | German | Meaning in groundfield |
|---|---|---|
| earthing system | Erdungsanlage | all electrodes and earthing conductors of an installation |
| interconnected (global) earthing system | vernetztes / globales Erdungssystem | earthing systems joined by PEN conductors and cable screens so that no dangerous touch voltage arises (EN 50522) |
| earth electrode | Erder | conductor in contact with the soil (Electrode) |
| foundation earth electrode | Fundamenterder | closed conductor in the foundation of a building (DIN 18014); FoundationElectrodeSpec, usually encased in concrete |
| ring earth electrode | Ringerder | RingElectrode, or a closed PolylineElectrode around a building |
| driven rod, rod electrode | Tiefenerder, Staberder | RodElectrode |
| strip electrode | Banderder, Oberflächenerder | StripElectrode |
| star earth electrode | Strahlenerder, Sternerder | StarElectrode |
| mesh earth electrode, grid | Maschenerder, Erdungsnetz | MeshElectrode, GridMeshElectrode |
| earthing conductor, bonding conductor | Erdungsleiter, Verbindungsleitung | Conductor between electrodes |
| concrete encasement | Betonummantelung | shell of concrete around a foundation earth; per-length coefficient concrete_shell_coefficient_ohm_m |
| penetration | Durchdringung | share of buildings that have a foundation earth electrode |
| perimeter equivalent | Umfangsäquivalent | \(n_U = \sum_i U_i / 40\ \mathrm{m}\) of an LV network (\(U_i\) building perimeters); forms the four LV network groups of the AP2 hand-over (thresholds 20 / 100 / 250; presets lv_group_<g>_p<pp> of effective_resistivity) |
| galvanic cluster | galvanisch verbundener Erderverbund | electrodes joined by ideal conductors; one potential |
| junction | Knoten (ohne Erdkontakt), Muffe | node of the conductor network without soil contact (Junction): cable joint, instrument terminal |
Soil and fields¶
| English | German | Symbol | Meaning |
|---|---|---|---|
| soil resistivity | spezifischer Erdwiderstand | \(\rho\), \(\rho_E\) | Ω·m; rho, rho_1, rho_2 |
| two-layer soil | Zweischichtboden | upper layer \(\rho_1\), thickness \(h_1\), half-space \(\rho_2\) | |
| layer thickness | Schichtdicke | \(h_1\) | m |
| reflection coefficient | Reflexionsfaktor | \(K\) | \((\rho_2 - \rho_1)/(\rho_2 + \rho_1)\) |
| effective resistivity | effektiver spezifischer Erdwiderstand | \(\rho_\text{eff}\) | Ω·m; one resistivity that stands for a two-layer soil: the rho of a groundinsight bus and of a BusType in layered soil (effective_resistivity, see below) |
| remote earth | Bezugserde | potential reference, \(\varphi \to 0\) far away | |
| soil surface | Erdoberfläche | \(z = 0\) | depth \(z\) positive downwards |
| skin depth (in the soil) | Eindringtiefe | \(\delta\) | \(\sqrt{2\rho/(\omega\mu_0)}\) |
| earth return | Erdrückleitung | path of a current through the soil back to its source; enters the inductive coupling | |
| mutual inductance | Gegeninduktivität | \(M\) | Neumann integral between two conductor segments |
The effective resistivity is \(\rho_\text{eff} = \rho_1^{1-w}\rho_2^{w}\), a
weighted geometric mean of the two layers, with the weight
\(w = w_0 (h_1/10\ \mathrm{m})^{-\beta}\) limited to \([0, 1]\): the thinner the
top layer, the more the lower layer counts. The weights are calibrated per
electrode class (AP1 calibration \(w_0 = 0.13\), \(\beta = 0.8\) by default;
presets "station" and "lv_group_<g>_p<pp>" in
EFFECTIVE_RESISTIVITY_PRESETS); for homogeneous soil
\(\rho_\text{eff} = \rho\).
Quantities¶
| English | German | Symbol | Meaning in groundfield |
|---|---|---|---|
| earth potential rise (EPR) | Erdungsspannung | \(U_E\) | potential of an earthing system against remote earth |
| grounding impedance, earthing impedance | Erdungsimpedanz | \(Z_E\) | \(U_E / I\); three variants below |
| input impedance | Eingangsimpedanz | \(Z_\text{in}\) | \((\varphi_a - \varphi_r)/I_s\) at a source: what an earth tester or a fault sees (input_impedance) |
| cluster impedance | Erdungsimpedanz des Erderverbunds | \(Z_c\) | cluster potential over the current the cluster leaks itself (cluster_impedance) |
| electrode impedance | Erdungsimpedanz eines Erders | cluster potential over one electrode's leakage current (grounding_impedance) |
|
| grounding resistance, spreading resistance | Erdungswiderstand, Ausbreitungswiderstand | \(R_E\), \(R_A\) | real part of the grounding impedance at low frequency |
| mutual grounding impedance | Koppelimpedanz | \(Z_{ij}\) | potential of cluster \(i\) per ampere leaking from cluster \(j\) (solve_mutual_matrix) |
| touch voltage | Berührungsspannung | \(U_T\) | potential of the touched part minus the surface potential 1 m from it (touch_voltage_at_part; touch_voltage with the electrode as the touched part) |
| touch point | Berührungspunkt | an accessible metal part above ground bonded to the earthing system: station housing or door, mast, fence, cable cabinet, service connection box (touch_voltage_at_part) |
|
| transferred potential | Potentialverschleppung | potential of an earthing system carried by a connected conductor (cable screen, PEN, pipe) into an area of low potential rise (EN 50522, 3.6; touch_voltage_at_part(bonded_to=<junction>)) |
|
| prospective touch voltage | Leerlauf-Berührungsspannung (prospektive B.) | \(U_{vT}\) | open-circuit touch voltage, before body and footwear resistances (EN 50522, Annex B) |
| permissible touch voltage | zulässige Berührungsspannung | \(U_{Tp}\) | EN 50522 Figure 8 / Table B.4 up to 10 s of fault duration, 80 V beyond |
| permissible prospective touch voltage | zulässige Leerlauf-Berührungsspannung | \(U_{vTp}\) | \(U_{Tp}\) plus the drop of the body current over hand, footwear and surface-layer resistances (EN 50522, Annex B; permissible_prospective_touch_voltage_en50522) |
| touch-voltage envelope | touch voltages on a ring of directions 1 m outside an electrode's footprint, a proxy where the touched parts are not known (touch_voltage_envelope) |
||
| mesh voltage | Maschenspannung (IEEE Std 80) | \(E_m\) | the largest touch voltage inside a mesh of a grid, near the mesh centre (touch_voltage_envelope(interior="meshes")) |
| step voltage | Schrittspannung | \(U_S\) | surface potential difference over one step of 1 m (step_voltage) |
| fault duration | Fehlerdauer | \(t_F\) | s |
| current sharing | Stromaufteilung | currents of the electrodes and conductors (cluster_current_balance) |
|
| split factor | Aufteilungsfaktor | \(s\) | share of a source current that leaves the feeding cluster through the soil (split_factor) |
| reduction factor | Reduktionsfaktor | \(r\) | share of an earth-fault current that returns through the soil instead of cable screens and earth wires (inductive; not computed) |
| rho-f model | ρ-f-Modell, ρ-f-Funktion | \(Z(\rho, f)\) | reduced model of an earthing system over resistivity and frequency, exported to groundinsight |
| characteristic matrix | charakteristische Matrix | \((\mathbf{Y}_L + \mathbf{Y}_G)\,\mathbf{u} = \mathbf{i}\) | nodal description of an LV network: line admittances plus the inverse of the mutual grounding-impedance matrix |
Measurement¶
| English | German | Meaning in groundfield |
|---|---|---|
| fall-of-potential measurement | Erdungsmessung (Strom-Spannungs-Verfahren) | test current between the earthing system and an auxiliary electrode, voltage measured with a probe (MeasurementSetupConfig) |
| auxiliary (current) electrode | Hilfserder | return electrode of the test current (terminal H of the instrument) |
| probe | Sonde | voltage probe (terminal S) |
| current lead, probe lead | Stromzuleitung, Sondenleitung | measurement leads, overhead or buried (overhead_lead, buried_lead); inductively coupled to the PEN network |
| earth tester | Erdungsmessgerät | measured_impedance(result): probe voltage over test current |
Terms of the package¶
| Term | Meaning |
|---|---|
World |
the physical model: soil, electrodes, junctions, conductors, sources |
Engine |
the numerics: backend, frequencies, segment length, kernel, earth-return model |
FieldResult |
the result of a solve: potentials, currents and impedances per frequency, point sources for the field, metadata |
| backend, engine | a registered numerical method (image, image_2layer, mom, mom_sommerfeld, fem); see choosing an engine |
| effective backend | the backend that actually ran: image runs image_2layer for a two-layer soil (metadata["effective_backend"]) |
| deprecated alias | an old backend name that runs another backend: cim runs image, bem runs mom; comparing an alias with its target checks nothing |
| segment | straight piece of a discretised wire, at most segment_length long |
| straight wire | a straight run of an electrode: a rod, a strip, a wire line of a grid, an arm of a star, a side of a polyline; carries one unknown current in the image family |
| owner | a straight wire (per soil layer it reaches) that carries one unknown current in the image family (user decisions Q30, Q44) |
| BusType | groundinsight's model of a network node with an impedance formula in f and rho (for layered soil the effective resistivity \(\rho_\text{eff}\)) |
Methods and numerics¶
| Term | Meaning |
|---|---|
| Green's function | the potential of a unit point current in the layered soil; the engines differ in how they evaluate it |
| image family | the engines image and image_2layer: closed-form Green's functions (air image, Tagg/Sunde series) and one uniform current per straight wire |
mom family |
the engines mom and mom_sommerfeld: one current per segment, point matching |
| image series, Tagg/Sunde series | the two-layer Green's function as a sum of mirror images whose strengths are powers of the reflection coefficient \(K\) |
| Sommerfeld integral | the layered Green's function as an integral over the horizontal wavenumber; evaluated by quadrature in mom_sommerfeld and for electrodes through a layer interface |
| cross-layer path | the Sommerfeld kernel that image_2layer and mom use as soon as an electrode reaches the layer interface (ADR-0007) |
| canonical layer stack | the soil after dropping zero-thickness layers and merging equal neighbours; a TwoLayerSoil(ρ, ρ, h) is solved as homogeneous |
| uniform-current ansatz | the current model of the image family: one leakage current per unit length per straight wire; impedance-grade, not field-grade next to grids and stars |
| point matching | the testing of the mom family: one pulse current per segment, the potential matched at every segment midpoint (collocation) |
| source kernel | how a segment's current enters the Green's function: "line" (exact uniform line source, the default of the image family) or "point" (midpoint point source, always in the mom family) |
| reaction matrix, multiport matrix | the matrix that turns the leakage currents of segments or wires into their potentials; reduced per cluster it is the mutual grounding-impedance matrix |
| transfer impedance | the mutual grounding impedance \(Z_{ij}\) of two different clusters: the off-diagonal entries of the multiport matrix |
| earth-return model | how the soil enters the inductance of conductors: sommerfeld (default), carson_series (long parallel lines), perfect_mirror (diagnostic baseline) |
| Neumann inductance | the partial (self and mutual) inductance of conductor segments from the Neumann integral |
| skin effect | the current displacement inside a solid round conductor at higher frequency (resistance_model="skin") |
| vector fit | a rational fit of a frequency response (poles and residues), the alternative to the standard rho-f form (vector_fit) |
| Richardson extrapolation | the extrapolation of fem over two nested mesh levels; the difference of the extrapolated value to the finer level is its error estimate (metadata["fem_error_estimate"]) |
German → English¶
Auxiliary index for German search terms: Aufteilungsfaktor → split factor; Ausbreitungswiderstand → spreading resistance; Banderder → strip electrode; Berührungspunkt → touch point; Berührungsspannung → touch voltage; Betonummantelung → concrete encasement; Bezugserde → remote earth; Durchdringung → penetration; effektiver spezifischer Erdwiderstand → effective resistivity; EFH → single-family house; Eindringtiefe → skin depth; Eingangsimpedanz → input impedance; Erder → earth electrode; Erdrückleitung → earth return; Erdseil → earth wire; Erdungsanlage → earthing system; Erdungsimpedanz → grounding impedance; Erdungsleiter → earthing conductor; Erdungsmessung → fall-of-potential measurement; Erdungsspannung → earth potential rise (EPR); Fehlerdauer → fault duration; Freileitung → overhead line; Fundamenterder → foundation earth electrode; Gegeninduktivität → mutual inductance; HAK → service connection box; Hausanschlussleitung → service drop; Hilfserder → auxiliary electrode; Kabelschirm → cable screen; KVS → cable distribution cabinet; Leerlauf-Berührungsspannung → prospective touch voltage; Maschenerder → mesh earth electrode; Maschenspannung → mesh voltage; ONS → MV/LV substation; Ortsnetz → LV network; PEN-Leiter → PEN conductor; Potentialverschleppung → transferred potential; Reduktionsfaktor → reduction factor; Ringerder → ring earth electrode; Schichtdicke → layer thickness; Schrittspannung → step voltage; Sonde → probe; spezifischer Erdwiderstand → soil resistivity; Staberder, Tiefenerder → driven rod; Sternerder, Strahlenerder → star earth electrode; Sternpunktbehandlung → neutral earthing; Stromaufteilung → current sharing; Umfangsäquivalent → perimeter equivalent; Zweischichtboden → two-layer soil.