Skip to content

Glossary (English / German)

The terms of the documentation and the code, with their German counterparts and their meaning in groundfield. Use it to look up a term of the package or of the numerics, or to find the English word for a German one (German → English at the end). The documentation and the code use English terms; the German terms are those of DIN EN 50522 (VDE 0101-2), DIN 18014 and the German network practice. Names of releases up to 0.15.0 that were German (kvs, OrtsnetzLayout, …) are listed under Deprecations.

Network and installation

English German Meaning in groundfield
LV network Ortsnetz low-voltage distribution network supplied by one MV/LV substation; generated by TnNetworkGenerator / LvNetworkLayout
MV/LV substation, substation Ortsnetzstation (ONS) transformer station feeding an LV network; substation in the generators
cable distribution cabinet Kabelverteilerschrank (KVS) street cabinet that branches the LV cables; cabinet in the generators (kvs up to 0.15.0)
service connection Hausanschluss (HA), Hausanschlusskasten (HAK) connection of a building to the LV network
service drop Hausanschlussleitung the cable from the PEN main to a building; generated by the network generators
single-family house Einfamilienhaus (EFH) the residential building type
multi-family house Mehrfamilienhaus (MFH)
small / medium commercial building Gewerbe (klein / mittel) the small_industry / medium_industry building types
TN system TN-System LV system whose neutral is earthed at the substation and connected to the exposed parts through the PEN / PE conductor
PEN conductor PEN-Leiter combined protective and neutral conductor; joins the earthing systems of an LV network (conductor_type="pen")
cable screen Kabelschirm metallic screen of a power cable; an earth-return path in parallel to the soil
overhead line, earth wire Freileitung, Erdseil conductor_type="overhead"; \(z < 0\)
MV network Mittelspannungsnetz the network of work package AP2
neutral earthing Sternpunktbehandlung decides the earth-fault current in the MV network
single-line-to-earth fault einpoliger Erdfehler, Erdschluss / Erdkurzschluss fault that drives the current into the earthing systems
harmonics Oberschwingungen frequency components of a fault current up to 1 kHz (touch_voltage_spectrum)
work packages AP1, AP2 Arbeitspakete AP1: model of the TN LV network (catalogue of real networks); AP2: earthing system of the MV network

Earthing system

English German Meaning in groundfield
earthing system Erdungsanlage all electrodes and earthing conductors of an installation
interconnected (global) earthing system vernetztes / globales Erdungssystem earthing systems joined by PEN conductors and cable screens so that no dangerous touch voltage arises (EN 50522)
earth electrode Erder conductor in contact with the soil (Electrode)
foundation earth electrode Fundamenterder closed conductor in the foundation of a building (DIN 18014); FoundationElectrodeSpec, usually encased in concrete
ring earth electrode Ringerder RingElectrode, or a closed PolylineElectrode around a building
driven rod, rod electrode Tiefenerder, Staberder RodElectrode
strip electrode Banderder, Oberflächenerder StripElectrode
star earth electrode Strahlenerder, Sternerder StarElectrode
mesh earth electrode, grid Maschenerder, Erdungsnetz MeshElectrode, GridMeshElectrode
earthing conductor, bonding conductor Erdungsleiter, Verbindungsleitung Conductor between electrodes
concrete encasement Betonummantelung shell of concrete around a foundation earth; per-length coefficient concrete_shell_coefficient_ohm_m
penetration Durchdringung share of buildings that have a foundation earth electrode
perimeter equivalent Umfangsäquivalent \(n_U = \sum_i U_i / 40\ \mathrm{m}\) of an LV network (\(U_i\) building perimeters); forms the four LV network groups of the AP2 hand-over (thresholds 20 / 100 / 250; presets lv_group_<g>_p<pp> of effective_resistivity)
galvanic cluster galvanisch verbundener Erderverbund electrodes joined by ideal conductors; one potential
junction Knoten (ohne Erdkontakt), Muffe node of the conductor network without soil contact (Junction): cable joint, instrument terminal

Soil and fields

English German Symbol Meaning
soil resistivity spezifischer Erdwiderstand \(\rho\), \(\rho_E\) Ω·m; rho, rho_1, rho_2
two-layer soil Zweischichtboden upper layer \(\rho_1\), thickness \(h_1\), half-space \(\rho_2\)
layer thickness Schichtdicke \(h_1\) m
reflection coefficient Reflexionsfaktor \(K\) \((\rho_2 - \rho_1)/(\rho_2 + \rho_1)\)
effective resistivity effektiver spezifischer Erdwiderstand \(\rho_\text{eff}\) Ω·m; one resistivity that stands for a two-layer soil: the rho of a groundinsight bus and of a BusType in layered soil (effective_resistivity, see below)
remote earth Bezugserde potential reference, \(\varphi \to 0\) far away
soil surface Erdoberfläche \(z = 0\) depth \(z\) positive downwards
skin depth (in the soil) Eindringtiefe \(\delta\) \(\sqrt{2\rho/(\omega\mu_0)}\)
earth return Erdrückleitung path of a current through the soil back to its source; enters the inductive coupling
mutual inductance Gegeninduktivität \(M\) Neumann integral between two conductor segments

The effective resistivity is \(\rho_\text{eff} = \rho_1^{1-w}\rho_2^{w}\), a weighted geometric mean of the two layers, with the weight \(w = w_0 (h_1/10\ \mathrm{m})^{-\beta}\) limited to \([0, 1]\): the thinner the top layer, the more the lower layer counts. The weights are calibrated per electrode class (AP1 calibration \(w_0 = 0.13\), \(\beta = 0.8\) by default; presets "station" and "lv_group_<g>_p<pp>" in EFFECTIVE_RESISTIVITY_PRESETS); for homogeneous soil \(\rho_\text{eff} = \rho\).

Quantities

English German Symbol Meaning in groundfield
earth potential rise (EPR) Erdungsspannung \(U_E\) potential of an earthing system against remote earth
grounding impedance, earthing impedance Erdungsimpedanz \(Z_E\) \(U_E / I\); three variants below
input impedance Eingangsimpedanz \(Z_\text{in}\) \((\varphi_a - \varphi_r)/I_s\) at a source: what an earth tester or a fault sees (input_impedance)
cluster impedance Erdungsimpedanz des Erderverbunds \(Z_c\) cluster potential over the current the cluster leaks itself (cluster_impedance)
electrode impedance Erdungsimpedanz eines Erders cluster potential over one electrode's leakage current (grounding_impedance)
grounding resistance, spreading resistance Erdungswiderstand, Ausbreitungswiderstand \(R_E\), \(R_A\) real part of the grounding impedance at low frequency
mutual grounding impedance Koppelimpedanz \(Z_{ij}\) potential of cluster \(i\) per ampere leaking from cluster \(j\) (solve_mutual_matrix)
touch voltage Berührungsspannung \(U_T\) potential of the touched part minus the surface potential 1 m from it (touch_voltage_at_part; touch_voltage with the electrode as the touched part)
touch point Berührungspunkt an accessible metal part above ground bonded to the earthing system: station housing or door, mast, fence, cable cabinet, service connection box (touch_voltage_at_part)
transferred potential Potentialverschleppung potential of an earthing system carried by a connected conductor (cable screen, PEN, pipe) into an area of low potential rise (EN 50522, 3.6; touch_voltage_at_part(bonded_to=<junction>))
prospective touch voltage Leerlauf-Berührungsspannung (prospektive B.) \(U_{vT}\) open-circuit touch voltage, before body and footwear resistances (EN 50522, Annex B)
permissible touch voltage zulässige Berührungsspannung \(U_{Tp}\) EN 50522 Figure 8 / Table B.4 up to 10 s of fault duration, 80 V beyond
permissible prospective touch voltage zulässige Leerlauf-Berührungsspannung \(U_{vTp}\) \(U_{Tp}\) plus the drop of the body current over hand, footwear and surface-layer resistances (EN 50522, Annex B; permissible_prospective_touch_voltage_en50522)
touch-voltage envelope touch voltages on a ring of directions 1 m outside an electrode's footprint, a proxy where the touched parts are not known (touch_voltage_envelope)
mesh voltage Maschenspannung (IEEE Std 80) \(E_m\) the largest touch voltage inside a mesh of a grid, near the mesh centre (touch_voltage_envelope(interior="meshes"))
step voltage Schrittspannung \(U_S\) surface potential difference over one step of 1 m (step_voltage)
fault duration Fehlerdauer \(t_F\) s
current sharing Stromaufteilung currents of the electrodes and conductors (cluster_current_balance)
split factor Aufteilungsfaktor \(s\) share of a source current that leaves the feeding cluster through the soil (split_factor)
reduction factor Reduktionsfaktor \(r\) share of an earth-fault current that returns through the soil instead of cable screens and earth wires (inductive; not computed)
rho-f model ρ-f-Modell, ρ-f-Funktion \(Z(\rho, f)\) reduced model of an earthing system over resistivity and frequency, exported to groundinsight
characteristic matrix charakteristische Matrix \((\mathbf{Y}_L + \mathbf{Y}_G)\,\mathbf{u} = \mathbf{i}\) nodal description of an LV network: line admittances plus the inverse of the mutual grounding-impedance matrix

Measurement

English German Meaning in groundfield
fall-of-potential measurement Erdungsmessung (Strom-Spannungs-Verfahren) test current between the earthing system and an auxiliary electrode, voltage measured with a probe (MeasurementSetupConfig)
auxiliary (current) electrode Hilfserder return electrode of the test current (terminal H of the instrument)
probe Sonde voltage probe (terminal S)
current lead, probe lead Stromzuleitung, Sondenleitung measurement leads, overhead or buried (overhead_lead, buried_lead); inductively coupled to the PEN network
earth tester Erdungsmessgerät measured_impedance(result): probe voltage over test current

Terms of the package

Term Meaning
World the physical model: soil, electrodes, junctions, conductors, sources
Engine the numerics: backend, frequencies, segment length, kernel, earth-return model
FieldResult the result of a solve: potentials, currents and impedances per frequency, point sources for the field, metadata
backend, engine a registered numerical method (image, image_2layer, mom, mom_sommerfeld, fem); see choosing an engine
effective backend the backend that actually ran: image runs image_2layer for a two-layer soil (metadata["effective_backend"])
deprecated alias an old backend name that runs another backend: cim runs image, bem runs mom; comparing an alias with its target checks nothing
segment straight piece of a discretised wire, at most segment_length long
straight wire a straight run of an electrode: a rod, a strip, a wire line of a grid, an arm of a star, a side of a polyline; carries one unknown current in the image family
owner a straight wire (per soil layer it reaches) that carries one unknown current in the image family (user decisions Q30, Q44)
BusType groundinsight's model of a network node with an impedance formula in f and rho (for layered soil the effective resistivity \(\rho_\text{eff}\))

Methods and numerics

Term Meaning
Green's function the potential of a unit point current in the layered soil; the engines differ in how they evaluate it
image family the engines image and image_2layer: closed-form Green's functions (air image, Tagg/Sunde series) and one uniform current per straight wire
mom family the engines mom and mom_sommerfeld: one current per segment, point matching
image series, Tagg/Sunde series the two-layer Green's function as a sum of mirror images whose strengths are powers of the reflection coefficient \(K\)
Sommerfeld integral the layered Green's function as an integral over the horizontal wavenumber; evaluated by quadrature in mom_sommerfeld and for electrodes through a layer interface
cross-layer path the Sommerfeld kernel that image_2layer and mom use as soon as an electrode reaches the layer interface (ADR-0007)
canonical layer stack the soil after dropping zero-thickness layers and merging equal neighbours; a TwoLayerSoil(ρ, ρ, h) is solved as homogeneous
uniform-current ansatz the current model of the image family: one leakage current per unit length per straight wire; impedance-grade, not field-grade next to grids and stars
point matching the testing of the mom family: one pulse current per segment, the potential matched at every segment midpoint (collocation)
source kernel how a segment's current enters the Green's function: "line" (exact uniform line source, the default of the image family) or "point" (midpoint point source, always in the mom family)
reaction matrix, multiport matrix the matrix that turns the leakage currents of segments or wires into their potentials; reduced per cluster it is the mutual grounding-impedance matrix
transfer impedance the mutual grounding impedance \(Z_{ij}\) of two different clusters: the off-diagonal entries of the multiport matrix
earth-return model how the soil enters the inductance of conductors: sommerfeld (default), carson_series (long parallel lines), perfect_mirror (diagnostic baseline)
Neumann inductance the partial (self and mutual) inductance of conductor segments from the Neumann integral
skin effect the current displacement inside a solid round conductor at higher frequency (resistance_model="skin")
vector fit a rational fit of a frequency response (poles and residues), the alternative to the standard rho-f form (vector_fit)
Richardson extrapolation the extrapolation of fem over two nested mesh levels; the difference of the extrapolated value to the finer level is its error estimate (metadata["fem_error_estimate"])

German → English

Auxiliary index for German search terms: Aufteilungsfaktor → split factor; Ausbreitungswiderstand → spreading resistance; Banderder → strip electrode; Berührungspunkt → touch point; Berührungsspannung → touch voltage; Betonummantelung → concrete encasement; Bezugserde → remote earth; Durchdringung → penetration; effektiver spezifischer Erdwiderstand → effective resistivity; EFH → single-family house; Eindringtiefe → skin depth; Eingangsimpedanz → input impedance; Erder → earth electrode; Erdrückleitung → earth return; Erdseil → earth wire; Erdungsanlage → earthing system; Erdungsimpedanz → grounding impedance; Erdungsleiter → earthing conductor; Erdungsmessung → fall-of-potential measurement; Erdungsspannung → earth potential rise (EPR); Fehlerdauer → fault duration; Freileitung → overhead line; Fundamenterder → foundation earth electrode; Gegeninduktivität → mutual inductance; HAK → service connection box; Hausanschlussleitung → service drop; Hilfserder → auxiliary electrode; Kabelschirm → cable screen; KVS → cable distribution cabinet; Leerlauf-Berührungsspannung → prospective touch voltage; Maschenerder → mesh earth electrode; Maschenspannung → mesh voltage; ONS → MV/LV substation; Ortsnetz → LV network; PEN-Leiter → PEN conductor; Potentialverschleppung → transferred potential; Reduktionsfaktor → reduction factor; Ringerder → ring earth electrode; Schichtdicke → layer thickness; Schrittspannung → step voltage; Sonde → probe; spezifischer Erdwiderstand → soil resistivity; Staberder, Tiefenerder → driven rod; Sternerder, Strahlenerder → star earth electrode; Sternpunktbehandlung → neutral earthing; Stromaufteilung → current sharing; Umfangsäquivalent → perimeter equivalent; Zweischichtboden → two-layer soil.