The units, the coordinate system, the phasor convention and the signs that every input and output of groundfield follows. Check this page when you build a world from your own data, or when you compare results with another tool or with a measurement.
Units¶
Every physical input and output is in SI units, without prefixes.
| Quantity | Unit | Examples |
|---|---|---|
| coordinates, lengths, radii, depths | m | position, radius, wire_radius, h_1, segment_length |
| cross section | m² | cross_section=95e-6 for 95 mm² (a value above 10⁻² m² warns with CrossSectionUnitWarning) |
| resistivity of soil, concrete, metal | Ω·m | rho, rho_1, concrete_rho_ohm_m, resistivity=1.68e-8 (copper) |
| concrete-shell coefficient | Ω·m | concrete_shell_coefficient_ohm_m |
| current | A (RMS) | CurrentSource.magnitude |
| potential, voltage | V (RMS) | electrode_potentials, touch_voltage |
| impedance | Ω | input_impedance, cluster_impedance, solve_mutual_matrix |
| frequency | Hz | Engine.frequencies |
| inductance | H; per unit length H/m | coupling.inductance |
| per-unit-length impedance | Ω/m | references.earth_return, references.pollaczek |
| time (fault duration) | s | permissible_touch_voltage_en50522(t_clear_s) |
| angles | degrees | phase_deg, orientation_deg |
Names follow two rules: the physics model uses bare SI values and the
literature symbols (rho, rho_1, h_1, h); the generator specs
carry a lower-case unit suffix (depth_m, concrete_rho_ohm_m,
frequency_hz, source_magnitude_a).
Coordinates¶
- Right-handed Cartesian \((x, y, z)\) in metres. In worlds built from map data, \(x\) points east and \(y\) north (local frame of the projection origin).
- \(z\) is the depth below the soil surface, positive downwards. The
soil surface is \(z = 0\), the soil is \(z > 0\), the air \(z < 0\)
(overhead conductors). A ring "0.8 m deep" has
center=(x, y, 0.8). - A rod's
positionis its upper end; it extends downwards bylength. - ParaView and other viewers assume \(z\) upwards: apply a transform with scale \((1, 1, -1)\) to VTK files.
- Projected coordinates (UTM, Gauss–Krüger) may be used as they are.
When a horizontal coordinate of a world exceeds 10 km, the solvers
(
image,image_2layer,mom,mom_sommerfeld,solve_mutual_*) work in a local frame: the world shifted exactly by the centre of its horizontal bounding box, rounded to whole metres. Point sources are reported in the user's coordinates, andFieldResult.potentialevaluates in a local frame of the sources in the same way (since 2026.11). A world at UTM coordinates gives the impedance of the same world at the origin to within about 5 · 10⁻¹¹; worlds within 10 km of the origin are not shifted. - Mixed coordinates. A world that mixes projected and local
coordinates — points within 10 km of the origin and beyond 1 000 km
from it, typically a return electrode, a cabinet or a cable end entered
in a local system in a UTM world — is solved as given: its two groups
lie some 33 000 km apart, and a conductor between them is that long. The
local frame cannot help such a world: its geometry is wrong. Since
2026.11 (user decision D5) the solve of such a world warns once with
MixedCoordinatesWarning(image family,mom,mom_sommerfeld,solve_mutual_*), before anything is discretised, anddiagnose()reports it undercoordinates. A world wholly in projected or wholly in local coordinates is never warned about at the solve;diagnose()reports worlds wider than 100 km as information (audit W2R2-06).
Projected and mixed coordinates: measurements and audit trail
Round-off of projected coordinates. Segment counts and straight
runs allow the round-off of the coordinates' own magnitude,
64 \(\varepsilon |x|\) (0.46 µm at an easting of 32.6 · 10⁶ m). A world
moved from (0, 0) to the UTM origin (32 604 321.123 m, 5 812 345.678 m)
then changes its impedance by 3 · 10⁻¹¹ with the point kernel (mom,
mom_sommerfeld, image with kernel="point"), the effect of the
rounding of its vertices; up to 2026.11 an edge of a whole number of
segments got one more there (a generated 10 m mesh foundation 508
instead of 440 segments, +2.6 · 10⁻⁴ in mom). With the default line
kernel the results agree to the same level: the kernel blends its exact
integral into its far form between six and 7.5 segment lengths (user
decision D2), so no pair switches its form with the round-off of the
coordinates. Over 12 local shifts of 0.1 m … 8.8 km the impedance
spreads by at most 8 · 10⁻¹⁴ (touch voltages 2 · 10⁻¹³), and the solve at
the UTM origin lies within 5 · 10⁻¹¹ of the local one (touch voltages
9.2 · 10⁻¹⁰), for strips, a mesh, a star and a ring in homogeneous and
two-layer soil and for two cross-layer worlds (audits W2B-01 and W3A;
with the one-step switch before, up to 5.4 · 10⁻⁷ for direct pairs and
2.6 · 10⁻⁵ in two-layer soil, where an image distance equalled six
segment lengths)
(known limitations).
Worlds within 10 km of the origin are not shifted, and their electrodes
are discretised as before.
Whole numbers of pieces. A distributed conductor whose length
exceeds a whole number of pieces only by round-off gets that whole
number at any position since 2026.11, near the origin too: a galvanic
counterpoise of 60 m in 10 m pieces from (3, 0, 0.5) m had 7 pieces in
about a quarter of all directions (829 … 876 of 3 600 in 0.1° steps,
depending on how the angles are formed; computed length
60.00000000000001 m) and has 6 in every one, its impedance −0.30 % with
image and −2.54 % with mom (audits W2B-03, W2R2-08).
Mixed coordinates. The round-off of a mixed world is that of the
projected world (1.5 · 10⁻¹¹ against 1.0 · 10⁻¹¹ with the point kernel),
but its geometry is wrong. Measured with a 12 m × 7 m outline and a 3 m
rod at UTM coordinates (audit W2B-04): a return rod given at local
(80, 15) m raises \(Z_{in}\) by 0.43 % with image and 0.44 % with mom
(the potential next to the outline by 5.8 %); a PEN cable to a cabinet
at local coordinates is 33 118 km long, \(Z_{in}\) = 7494 + j25 396 Ω
instead of 5.39 + j0.19 Ω at 50 Hz with carson_series, and the
default sommerfeld earth return does not finish.
Phasors and frequency¶
- Time convention \(e^{+j\omega t}\), \(\omega = 2\pi f\): a quantity \(x(t) = \sqrt{2}\,\operatorname{Re}\{\underline{X}\,e^{j\omega t}\}\) is represented by its RMS phasor \(\underline{X}\). An inductive impedance has a positive imaginary part, \(Z = R + j\omega L\).
- The Laplace variable of the vector fits is \(s = j\omega = j\,2\pi f\).
- Every result is a list with one value per frequency, in the order of
Engine.frequencies(the order is never changed; a non-monotonic list warns withEngineFrequencyOrderWarning). - Frequencies must be finite and non-negative; \(f = 0\) (DC) is a valid operating point. The models are quasi-static and validated for \(f < 1\,\mathrm{kHz}\): displacement currents in the soil and wave propagation along the conductors are neglected. Higher frequencies are accepted but outside the validated range.
- A fault-current spectrum is combined as a true RMS value,
\(U_\text{rms} = \sqrt{\sum_k \lvert\underline{U}_k\rvert^2}\)
(
touch_voltage_spectrum).
Potentials, currents and signs¶
- Potential reference. Every potential is measured against remote earth, \(\varphi \to 0\) far from all electrodes. The soil surface is insulating (no current into the air).
- Source current. A
CurrentSourcewithmagnitude\(I > 0\) andphase_deg\(= 0\) drives \(+I\) into the nodeattached_toand takes it back atreturn_to(or at remote earth). - Electrode currents.
FieldResult.electrode_currents[name]is the current an electrode leaks into the soil: positive at the feeding earth, negative at the electrode that collects the current of a two-terminal source. With one source of \(+1\) A the potentials of the fed earthing system are positive (earth potential rise). - Impedances. Input, cluster and electrode impedance are defined in the quickstart; for a passive earthing system their real parts are positive.
- Touch and step voltage. \(U_T = U_E - \varphi(\text{feet})\) and \(U_S = \varphi(\mathbf{r}_1) - \varphi(\mathbf{r}_1 + 1\,\mathrm{m}\cdot\hat{\mathbf{e}})\), complex phasors in V for the given source current; compare magnitudes with the permissible values.
- When comparing with another tool or a measurement, check its sign convention for injected currents and node potentials.
Material defaults¶
| Parameter | Default | Note |
|---|---|---|
| wire radius of electrodes and conductors | 5 mm | wire_radius=0.005 |
| conductor resistivity | \(1.68\cdot10^{-8}\,\Omega\,\mathrm{m}\) | copper |
| relative permittivity of the soil | stored, not used | quasi-static model (InertConfigurationWarning when changed) |
| magnetic permeability | \(\mu_0 = 4\pi\cdot10^{-7}\,\mathrm{H/m}\) | soil and conductors non-magnetic |