Skip to content

ADR-0008: groundinsight bridge — BusType export from a rho-f fit

Status Accepted — amended 2026.11 (review pass 10: safe formula parser, input impedance, passivity, the effective resistivity as the rho of layered soil, with weight presets per electrode class); see the amendment at the end of this document
Date 2026-05-08
Deciders Project maintainers
Scope groundfield.io.groundinsight; bridge to the sister project groundinsight

Context

groundfield is the field-grade reference. groundinsight is the reduced equivalent network model that runs the actual planning and fault-current studies. The reduction pipeline

PDE / field model  →  reduced rho-f model  →  measurement-anchored
                                              network model

requires a precise, regression-tested handover between groundfield and groundinsight. The rho-f fit is now in place in two flavours:

  • groundfield.postprocess.vector_fitting — a Gustavsen/Semlyen rational fit \(Z(s)\) in the Laplace variable \(s = j\,2\pi f\) at fixed soil (output of one parametric run).
  • groundfield.postprocess.rho_f_standard — the physically-motivated 5-coefficient form \(Z(\rho, f) = k_1\rho + (k_2 + j k_3)f + (k_4 + j k_5)f\rho\) fitted across a soil-resistivity sweep.

Both produce a SymPy expression. groundinsight.BusType consumes exactly such an expression as its impedance_formula. What is missing is the actual transport: a documented file format, a Python helper that builds a BusType and (optionally) writes it to the groundinsight SQLite store, and a regression test that proves the formula round-trips through groundinsight's own parser and produces the same numbers.

Decision

Symbol convention

groundinsight.BusType.impedance_formula is parsed with two free symbols that the compute_impedance evaluator binds at run time:

  • f — frequency in Hz
  • rho — Bus.specific_earth_resistance, in \(\Omega\,\mathrm{m}\) (for layered soil the effective resistivity, see item 5 of the amendment)

and the imaginary unit j (mapped to sympy.I by the validator).

Therefore:

  • A RhoFStandardFit exports natively: its expression is already in (rho, f).
  • A VectorFitResult exports via the substitution \(s \to j\,2\pi f\) inside fit_to_sympy(...). The exported formula then depends on f only and is independent of rho. This is correct: a vector fit is bound to one specific soil configuration, and its BusType is meant to be paired with a Bus whose specific_earth_resistance matches that soil. Discrepancies are flagged at export time but not enforced.

Transport: JSON + Python API, both first-class

The user has two equally supported paths:

  1. to_bustype_dict(fit, ...) returns a JSON-ready Python dict; save_bustype_json(fit, path, ...) writes the neutral schema below to disk. This is the canonical, persistent exchange. The schema is versioned (schema_version), and groundfield will honour older versions through dedicated loaders. The JSON file is independent of the groundinsight Python package — anyone can produce or consume it.

  2. to_bustype(fit, ...) returns a live groundinsight.BusType Pydantic instance via a lazy import (no top-level dependency on groundinsight). For users running in a notebook with both packages installed this is the one-liner that closes the family pipeline. If groundinsight is not installed the function raises a clear ImportError pointing at the JSON path or at the optional install pip install groundfield[groundinsight].

JSON schema (v1)

Single document, parseable in seconds, no MIME-type tricks. Layout is intentionally close to the groundinsight.BusType Pydantic schema so a programme that only knows the groundinsight shape can still read the file by ignoring the metadata block.

{
  "schema": "groundfield.bustype",
  "schema_version": 1,
  "name": "TN_house_connection_5EFH",
  "description": "...",
  "system_type": "LV",
  "voltage_level": 0.4,
  "impedance_formula": "0.123*rho + 0.000456*f + 0.0*j*f + 1.2e-7*f*rho + 3.4e-8*j*f*rho",
  "samples": {
    "frequency_Hz": [0.1, 1.0, 10.0, 50.0, 100.0, 1000.0],
    "rho_Ohm_m":   [100.0, 100.0, 100.0, 100.0, 100.0, 100.0],
    "Z_real_Ohm":  [...],
    "Z_imag_Ohm":  [...]
  },
  "metadata": {
    "fit_method":      "rho_f_standard",
    "fit_quality":     {"rms_error_Ohm": 0.012, "rms_relative": 0.004},
    "coefficients":    {"k1": 0.123, "k2": 4.56e-4, "k3": 0.0,
                        "k4": 1.2e-7, "k5": 3.4e-8},
    "source":          "groundfield 0.1.0",
    "created_at_utc":  "2026-05-08T14:32:11Z",
    "electrode_name":  "trafo_ring",
    "soil_summary":    "TwoLayerSoil(rho_1 sweep [50, 100, 300, 1000], rho_2=20, h_1=2.0)",
    "rho_definition":  "effective_resistivity"      // amendment 2026.11, item 5
  }
}

A number that is not finite (an unknown rms_error_Ohm of a hand-built fit, a non-finite sample) is written as null; the file is strict JSON (allow_nan=False, amendment 2026.11, finding 10.19).

For vector_fit the metadata block carries n_poles, the pole list and the residue list; coefficients is replaced by {"R_inf": ..., "L_inf": ...}. For rho_f_standard the samples.rho_Ohm_m array spans all sampled rhos; for vector_fit it is constant at the soil under which the fit was done.

Coupling

groundinsight becomes an optional dependency declared as the extras group [groundinsight] in pyproject.toml. The library imports groundinsight lazily inside the few functions that return BusType instances or talk to the database, so

  • pip install groundfield works as before;
  • pip install groundfield[groundinsight] enables the Python-API path;
  • the JSON path needs neither extra.

Validation programme

  1. Symbol round-trip — every formula produced by to_bustype_* is fed back through groundinsight.utils.validations.validate_impedance_formula_value and through groundinsight.utils.impedance_calculator.compute_impedance, and the resulting per-frequency complex values must match fit.evaluate(...) to \(10^{-9}\) relative.
  2. JSON round-trip — save_bustype_json followed by load_bustype_json reproduces every numerical field bit-exact and the formula string verbatim.
  3. End-to-end — a transformer-station notebook (the internal groundinsight-export harness) sweeps \(\rho_1 \in \{50, 100, 300, 1000\}\,\Omega\,\mathrm{m}\) on a 2-layer soil, fits the standard form, exports a BusType, loads it back into a groundinsight.Network, and reproduces the per-frequency \(|Z|\) and \(\arg Z\) within the fit RMS.
  4. Optional-dependency hygiene — a test that monkey-patches groundinsight to be unimportable and verifies the to_bustype / save_bustype_to_db functions raise a clear ImportError, while to_bustype_dict / save_bustype_json keep working.

Consequences

  • The rho-f family is now closed-loop: groundfield produces a fit, exports it, and groundinsight consumes it without any manual stringification.
  • The neutral JSON makes both packages forward-compatible: tabular ingestion on the groundinsight side will read the samples block; the formula stays the canonical artifact in v1.
  • BranchType is out of scope for this ADR. The mutual coupling between two grounding clusters is not yet a rho-f product of groundfield; it is a follow-up once compute_mutual_impedance produces a calibrated formula in the same (f, rho, l) symbol set that BranchType expects.

References

  • ADR-0001, ADR-0007 — engine family and cross-layer support that produced the underlying physics.
  • Vector fitting: Gustavsen & Semlyen, IEEE T-PWRD 14(3), 1052–1061 (1999).
  • Standard rho-f form: defined in groundfield.postprocess.rho_f_standard.
  • groundinsight.models.core_models.BusType — consumer of the exported formula.

Amendment 2026.11 — formulas are parsed, exports are checked (review pass 10)

Findings 10.01, 10.19, 10.27, 10.40, 10.73 and 10.84.

  1. No code execution. A BusType formula is data. evaluate_spec, BusTypeSpec.from_dict and load_bustype_json parse it with an allow-list parser (groundfield.io._formula): ast.parse (which executes nothing), then the SymPy expression is built node by node from numbers, f, rho, j / I, pi, E, + - * /, ** with a bounded literal exponent and sqrt / exp / log, within size, depth, magnitude and work budgets. sympy.sympify — which evaluates its input as Python — is no longer called on formula text (10.01). A rejected formula raises EvaluateSpecError naming the element. The same corpus of accepted and rejected formulas (tests/data/formula_corpus.json) is shared with groundinsight's own guard.
  2. Which impedance is exported. The rho-f exporters fit the input impedance of the feeding source by default (quantity="input"); the BusType metadata records the fitted quantity, all coefficients k0 … k5, weights and fit_quality.max_relative (10.19, 10.27). The standard form of this ADR gains the constant k0.
  3. Readable formulas. Coefficients are rounded once to decimals significant digits; nsimplify (rationals with up to 254 digits) and the merging of partial fractions are gone (10.73).
  4. Passivity. Every export evaluates the formula it writes from 0 Hz to twice the highest fitted frequency (over the fitted ρ range for the standard form) with the shared check_passivity; Re Z < 0 warns (NonPassiveFitWarning) or, with require_passive=True, raises NonPassiveFitError before anything is written (10.40). metadata["passivity"] records the verdict.
  5. rho_at_fit and the rho of layered soil. A vector fit belongs to one soil; its export requires rho_at_fit, and the error message says what to pass (10.84). For layered soil the rho of every BusType — rho_at_fit of a vector fit, the rho samples a standard form is fitted over — is the effective resistivity of the soil it was fitted in, \(\rho_\text{eff} = \rho_1^{\,1-w}\rho_2^{\,w}\) with \(w = w_0 (h_1/10\ \mathrm{m})^{-\beta}\) limited to \([0, 1]\) (groundfield.effective_resistivity; weights \((w_0, \beta)\) of the electrode class, by default the AP1 calibration \(w_0 = 0.13\), \(\beta = 0.8\); \(\rho\) itself for homogeneous soil). This is the value the AP2 network model gives a Bus as specific_earth_resistance (the author's decision for the 2026.11 release), so a BusType pairs with the bus of its soil. It replaces the upper-layer resistivity \(\rho_1\) of an earlier draft of this amendment, which describes a soil only together with a fixed lower layer and thickness. Every document records the convention as metadata["rho_definition"] = "effective_resistivity"; documents of 0.15.0 have no such entry. The exporter cannot check the number it is given. \(\rho_\text{eff}\) is an empirical calibration on the LV networks of the AP1 catalogue (\(h_1\) = 5 … 30 m, \(\rho_1\) = 30 … 1000 Ω·m, \(\rho_2\) = 30 … 200 Ω·m); check the fit quality (max_relative) of a BusType fitted over it.

Weight presets (user decision Q36). The weights depend on the extent of the earthing system: a compact electrode in the upper layer sees less of the lower layer than an LV network. effective_resistivity(soil, preset=...) takes \((w_0, \beta)\) from the read-only mapping groundfield.soil.EFFECTIVE_RESISTIVITY_PRESETS: "lv_network" (0.13, 0.8, the default and the global calibration), "station" (0.06, 1.3, the station electrode alone) and "lv_group_<g>_p<pp>" for the four LV network groups (perimeter equivalent \(n_U\), thresholds 20 / 100 / 250) and the penetrations 5, 10, 20, 40 % of foundation electrodes. The values are those of the author's AP2 hand-over (generated 2026-10-20 from the AP1 catalogue computed with groundfield 0.14.0; per group the median network, q50); they belong to that catalogue and are re-derived when it is recomputed. An explicit w0 or beta replaces that weight only, so every call made before the presets keeps its value. A BusType and its bus must use the same weights. rho_definition stays the token "effective_resistivity"; the preset is recorded next to it (item 7). For the AP1 station in the 39 AP1 soils, \(R = c\,\rho_\text{eff}\) (\(c\) from homogeneous soil) misses the field solution by at most 15.7 % with "station" (median over the 39 soils 1.8 %; the hand-over: 1.7 %, 15.7 %) against 35.9 % with "lv_network" and 41.9 % over \(\rho_1\). 6. Validation programme. The round trip through groundinsight is checked at \(10^{-9}\), as this ADR specified (the test had used \(10^{-3}\)), and evaluate_spec against groundinsight's compute_impedance at \(10^{-9}\). 7. The preset in the document (user decision Q39). The exporters take rho_preset=..., a key of EFFECTIVE_RESISTIVITY_PRESETS (any other value raises, naming the closest presets), and record it as metadata["rho_preset"] next to rho_definition; None when no preset is named (homogeneous soil, explicit weights, or not stated). BusTypeSpec.rho_preset reads it; documents of earlier versions have no entry and load with None, a malformed entry is refused on load. The number rho_at_fit is still not checked against the preset. The paths that serve a bus know its preset: evaluate_spec(spec, f, rho, rho_preset=...) and bustype_from_spec(spec, rho_preset=...) (the live groundinsight.BusType of a loaded document) emit RhoPresetMismatchWarning when the document records another preset; a preset holds for its electrode class only (the AP1 station with "lv_group_4_p40": 39.9 % rms). The live BusType carries no metadata, so the check stays on the groundfield side. Round trip through groundinsight 0.3.0 (PyPI) at \(10^{-9}\). Since audit W3B-06 the live BusType of to_bustype, save_bustype_to_db and bustype_from_spec names the preset in the last line of its description, groundfield rho_preset: <name> (before, it was validated and dropped, so a BusType read back from the database could not be checked); groundinsight's BusType and its database keep the description (bus_types.description of groundinsight 0.3.0), and bustype_rho_preset reads the line back (database round trip tested). On load the preset must be a name of EFFECTIVE_RESISTIVITY_PRESETS or null (audit W3R2B-06), and only the exact preset line is removed or replaced in a description.