Skip to content

Quickstart

This page takes you from an empty Python session to the numbers of a typical earthing study: the earthing impedance of a rod, a ring and a grid in homogeneous and in two-layer soil, the earth potential rise and the touch voltage of a fault, a potential profile with a plot, and the impedances of two earthing systems joined by a PEN conductor. Every code block runs as it stands, in the order of the page (later blocks reuse earlier objects); the comments show what it prints. Install the package first (installation).

1. A rod in homogeneous soil

A driven rod of 3 m in soil of 100 Ω·m, fed with 1 A:

import groundfield as gf

world = gf.create_world(soil=gf.HomogeneousSoil(rho=100.0))                       # 100 Ω·m
gf.create_electrode(world, "rod", name="rod", position=(0.0, 0.0, 0.0), length=3.0)
gf.create_source(world, attached_to="rod", magnitude=1.0)                         # 1 A

result = world.solve(gf.create_engine(frequencies=[50.0]))
print(f"{result.input_impedance()[0].real:.2f} Ω")    # 35.99 Ω

What each line does:

  • Soil. HomogeneousSoil(rho=100.0) is a half-space of resistivity \(\rho = 100\,\Omega\,\mathrm{m}\) below an insulating air space. All inputs are SI units (m, Ω·m, A, Hz).
  • World. The World holds the physical model: soil, electrodes, conductors and sources.
  • Electrode. Coordinates are \((x, y, z)\) in metres with \(z\) the depth, positive downwards. A rod's position is its upper end; this one runs from the surface to 3 m. The wire radius defaults to 5 mm.
  • Source. 1 A RMS injected at the rod. Without return_to the current returns through remote earth, the potential reference (\(\varphi \to 0\) far away).
  • Engine and solve. The Engine holds the numerics. The default backend image solves the problem in closed form; the result holds one value per frequency, here one. With 1 A the impedance in ohms is also the earth potential rise in volts.

Dwight's formula for a rod, \(R = \frac{\rho}{2\pi L}\bigl(\ln\frac{4L}{a} - 1\bigr)\) with length \(L\) and wire radius \(a\), is a quick plausibility check:

from groundfield.references import dwight1936

print(f"{dwight1936.rod(rho=100.0, length=3.0, radius=0.005):.2f} Ω")   # 35.99 Ω

The two agree to about 0.01 %: both assume a uniform current along the rod. A real rod leaks more current near its ends, and its resistance lies about 1 % lower; choosing an engine explains when that matters.

2. A rod, a ring and a grid in two soils

A small helper builds one earthing system per call, so that the same electrode can be solved in different soils:

def earthing_system(kind, soil, current=1.0):
    """A world with one earth electrode named "earth", fed with `current` in A."""
    world = gf.create_world(soil=soil)
    if kind == "rod":
        gf.create_electrode(world, "rod", name="earth", position=(0.0, 0.0, 0.0), length=3.0)
    elif kind == "ring":
        gf.create_electrode(world, "ring", name="earth", center=(0.0, 0.0, 0.8), radius=3.0)
    else:  # a grid of 20 m × 20 m with 4 × 4 meshes, 0.5 m deep
        gf.create_electrode(
            world, "grid_mesh", name="earth", corner=(-10.0, -10.0, 0.5), size=(20.0, 20.0), n_x=4, n_y=4
        )
    gf.create_source(world, attached_to="earth", magnitude=current)
    return world


soils = {
    "homogeneous": gf.HomogeneousSoil(rho=100.0),
    "two-layer": gf.TwoLayerSoil(rho_1=100.0, rho_2=300.0, h_1=2.0),
}
engine = gf.create_engine(frequencies=[50.0])
impedances = {}
for kind in ("rod", "ring", "grid"):
    impedances[kind] = [earthing_system(kind, soil).solve(engine).input_impedance()[0].real for soil in soils.values()]
    print(f"{kind:5s} {impedances[kind][0]:6.2f} Ω {impedances[kind][1]:6.2f} Ω")
# rod    35.99 Ω  51.41 Ω
# ring    9.41 Ω  13.81 Ω
# grid    2.37 Ω   4.80 Ω

TwoLayerSoil is a top layer of resistivity \(\rho_1 = 100\,\Omega\,\mathrm{m}\) and thickness \(h_1 = 2\,\mathrm{m}\) over a half-space of \(\rho_2 = 300\,\Omega\,\mathrm{m}\). The more resistive lower layer raises every impedance, and the more so the larger the electrode: the current of a large electrode spreads deeper into the soil. The rod gains 43 %, the ring 47 %, the 20 m grid more than doubles. The engine needs no change: image forwards a two-layer soil to image_2layer, the Tagg/Sunde image series.

3. A fault: earth potential rise and touch voltage

Feed the grid in the two-layer soil with an earth-fault current of 100 A. The touch voltage next to a grid depends on how the current crowds to its edges and corners, so solve it with mom, which computes one current per wire segment (the default image assumes one uniform current per straight wire and warns near grids):

grid = earthing_system("grid", soils["two-layer"], current=100.0)   # 100 A
fault = grid.solve(gf.create_engine(backend="mom", frequencies=[50.0]))

epr = abs(fault.electrode_potentials["earth"][0])
_, u_touch = gf.touch_voltage_envelope(fault, grid, electrode="earth", distance=1.0)
u_step = abs(gf.step_voltage(fault, position=(10.0, 10.0, 0.0), direction=(1.0, 1.0, 0.0), world=grid))
u_tp = gf.permissible_touch_voltage_en50522(0.5)   # fault cleared after 0.5 s
print(f"EPR {epr:.0f} V, touch voltage up to {abs(u_touch).max():.0f} V, step voltage {u_step:.0f} V")
print(f"permissible touch voltage {u_tp:.0f} V")
# EPR 476 V, touch voltage up to 129 V, step voltage 54 V
# permissible touch voltage 225 V
  • The earth potential rise (EPR) is the potential of the grid against remote earth: here \(4.76\,\Omega \times 100\,\mathrm{A}\) (mom reads the impedance 0.9 % below image).
  • The touch voltage \(U_T = U_E - \varphi(\text{feet})\) is the EPR \(U_E\) of the touched metal minus the surface potential where a person stands, 1 m away. touch_voltage_envelope puts the feet 1 m outside the grid's footprint, on 24 directions and on the arc around each corner; the largest value lies off the corners.
  • The step voltage is the difference of the surface potential over 1 m; here from the point above a corner outwards.
  • The comparison with the permissible touch voltage of EN 50522 (Figure 8, Table B.4; 225 V for 0.5 s) leaves out body, footwear and surface-layer resistances, which is conservative; permissible_prospective_touch_voltage_en50522 adds them.

With the default image engine the same envelope reads 9 % higher and the call warns with UniformCurrentFieldWarning. For impedances the two engines agree within 1 %; for field quantities near extended electrodes mom is the reference (choosing an engine). Every result scales linearly with the source current.

4. A potential profile and a plot

FieldResult.potential evaluates the potential at any point of the soil or its surface. Along a line at \(y\) = 2.5 m, through the middle of a row of meshes:

import numpy as np

x = np.array([0.0, 11.0, 20.0, 50.0])                       # m from the centre
points = np.column_stack([x, np.full_like(x, 2.5), np.zeros_like(x)])
for xi, phi in zip(x, fault.potential(points).real):
    print(f"x = {xi:4.0f} m: {phi:4.0f} V ({phi / epr:.0%} of the EPR)")
# x =    0 m:  460 V (97% of the EPR)
# x =   11 m:  400 V (84% of the EPR)
# x =   20 m:  233 V (49% of the EPR)
# x =   50 m:   95 V (20% of the EPR)

Inside the grid the surface stays close to the EPR, which keeps touch voltages there small; outside it the potential falls off towards remote earth, and the touch voltage grows with it. Two plotting functions show the same as figures:

import matplotlib.pyplot as plt

gf.plot_potential_profile(fault, start=(0.0, 2.5, 0.0), direction=(1.0, 0.0, 0.0), distance=50.0)
gf.plot_surface_potential(fault, grid)
plt.show()

The first draws the curve of the table above, the second a colour map of the surface potential over the grid and its surroundings with the electrode drawn on top. The plotting guide shows the other plots (geometry, cross-sections, current sharing, sweeps).

5. Two earthing systems joined by a PEN conductor

A substation ring earth and the rod earth of a house 40 m away, joined by a PEN conductor, in the two-layer soil; a current of 1 A is injected at the substation and returns through remote earth.

world = gf.create_world(soil=gf.TwoLayerSoil(rho_1=100.0, rho_2=300.0, h_1=2.0))
gf.create_electrode(world, "ring", name="substation", center=(0.0, 0.0, 0.8), radius=3.0)
gf.create_electrode(world, "rod", name="house", position=(40.0, 0.0, 0.0), length=3.0)
gf.create_conductor(world, name="pen", start="substation", end="house", cross_section=95e-6)
gf.create_source(world, attached_to="substation", magnitude=1.0)

result = world.solve(gf.create_engine(frequencies=[50.0]))
print(result.input_impedance()[0])                # (11.2695+0j) Ω
print(result.cluster_impedance("substation")[0])  # (14.1034+0j) Ω

The conductor is a 95 mm² copper PEN (cross_section in m²): a branch with resistance \(R = \rho_\text{Cu}\,\ell/A\) between the two electrodes, with the copper resistivity \(\rho_\text{Cu}\), the length \(\ell\) and the cross-section \(A\). Without cross_section it would be an ideal connection and both electrodes would form one galvanic cluster.

Three impedances of one solve

Z_in = result.input_impedance()[0]
Z_substation = result.cluster_impedance("substation")[0]
Z_house = result.cluster_impedance("house")[0]
share = result.electrode_currents["substation"][0]   # leakage current, A
print(f"{Z_in.real:.2f} Ω, {Z_substation.real:.2f} Ω, {share.real:.0%} at the substation")
# 11.27 Ω, 14.10 Ω, 80% at the substation
Method Definition What it describes
input_impedance(source) \((\varphi_a - \varphi_r)/I_s\) what an earth tester or a fault sees at the feeding point: the whole connected system
cluster_impedance(electrode) \(\varphi_c / \sum_{e \in c} I_e\) the local earthing system: one galvanic cluster and only the current it leaks itself
grounding_impedance(electrode) \(\varphi_c / I_e\) the share of one electrode; equal to the cluster impedance for a cluster of one electrode

\(\varphi_a\), \(\varphi_r\) are the potentials of the feeding and the return node (zero for a return through remote earth), \(I_s\) the source current, \(\varphi_c\) the length-weighted potential of a cluster and \(I_e\) the current an electrode leaks into the soil. Here 20 % of the test current flows through the PEN to the house earth, so the substation ring alone (14.10 Ω) is seen as 11.27 Ω at the feeding point. Because the PEN resistance is only a few milliohms, the input impedance is the parallel connection of the two cluster impedances:

print(abs(1 / (1 / Z_substation + 1 / Z_house) - Z_in))   # 0.0003 Ω

Which one you need depends on the question: the input impedance for a measurement or a fault loop (it is the default of sweep, convergence_study and the rho-f fits), the cluster impedance to characterise one earthing system on its own. The sources and measurement page explains the definitions in detail.

6. Check the result with a second method

Every number from a field model should be checked against an independent computation. Two quick checks: solve the same world with a second backend, and refine the discretisation.

report = gf.compare_engines(
    world,
    engines={"image": gf.create_engine(), "mom": gf.create_engine(backend="mom")},
    rel_tolerance=0.05,
)
print(report.summary())     # largest deviation 1.1 % (house cluster): consistent

fine = world.solve(gf.create_engine(segment_length=0.25))
print(fine.input_impedance()[0])   # (11.2758+0j) Ω, +0.06 % at half the segment length

The two methods differ in the current model: mom solves for one current per segment by point matching with midpoint point sources, image_2layer assumes a uniform current per unit length on each straight wire and integrates it with the exact line-source kernel. Agreement within about 1 % is expected (the point kernel reads 1–2 % low, see source kernels).

Values asserted by the test suite

The code blocks on this page are executed by the documentation tests; these assertions keep the numbers quoted in sections 5 and 6 in step with the code.

assert abs(Z_in - 11.2695) < 5e-4 and abs(Z_substation - 14.1034) < 5e-4
assert abs(share.real - 0.799) < 1e-3
assert abs(1 / (1 / Z_substation + 1 / Z_house) - Z_in) < 1e-3
assert report.is_consistent and max(report.deviations.values()) < 0.012
assert abs(fine.input_impedance()[0] - 11.2758) < 5e-4

Where next

  • Tutorials: from the first impedance to layered soil, connected systems, frequency response, the rho-f export, TN networks, measurements and touch voltages, step by step.
  • Examples: three complete case studies — a secondary substation with its low-voltage network, a single-family house, and the mesh grid of a high-voltage substation in two-layer soil.
  • Choosing an engine: which backend for which question, and where each one must not be used.
  • How-to guides: recipes for sweeps, plots, touch voltages, export and large studies.
  • Factories: every create_* function and its parameters; units and conventions: coordinates, phasors, signs.