Skip to content

Warnings and errors

This page explains every warning and error that groundfield emits: when it appears, what it means for your result, and what to do. Look a message up here when a solve or a post-processing call warns; the how-to guide Read and act on warnings shows the workflow, and Known limitations gives the size of each limit behind a warning.

groundfield warns when a result is valid but limited, and raises when it cannot produce a meaningful result. Every warning class below is a subclass of UserWarning (except DeprecationWarning), so it can be filtered by category:

import warnings

import groundfield as gf

with warnings.catch_warnings():
    warnings.simplefilter("error", gf.UniformCurrentFieldWarning)   # make it fatal
    warnings.simplefilter("ignore", gf.ExperimentalBackendWarning)  # or silence it
    ...  # solve and post-process here

Warnings are attributed to the line of your code that caused them, not to the inside of the package; warnings that the package's own internal calls would trigger (for example a generator using an old keyword) are not shown, because you cannot act on them. Python shows a DeprecationWarning by default only for code in __main__ and in notebooks; run tests with -W error::DeprecationWarning to find deprecated names early. The page lists every warning and exception class defined in src/groundfield, then the plain UserWarnings, then the built-in exceptions with a fixed meaning.

Class Kind Typical cause
BackendCapabilityError error the engine cannot represent the world
BackendCapabilityWarning warning a documented simplification of a custom backend
ExperimentalBackendWarning warning first solve with fem
BackendOptionsWarning warning options for a backend that does not run
ProbePointsIgnoredWarning warning probe_points of 0.15.0 code
EngineFrequencyOrderWarning warning frequencies not increasing
ShallowSegmentWarning warning point kernel, segment long against its depth
PointKernelInterfaceWarning warning point kernel, wire next to the layer interface
InterfaceContactWarning warning rod end or wire at a layer interface
SeriesTruncationWarning warning image series cut at its cap
SommerfeldConvergenceWarning warning layered quadrature not converged
FemReductionWarning warning never emitted since 2026.11
ComplexImageFitWarning warning direct call of the old complex-image fit
SommerfeldResolutionWarning warning Hankel quadrature out of nodes
SommerfeldTailTruncationWarning warning tail of the reflected kernel not bounded
DeprecationWarning warning deprecated name, keyword or alias
InertConfigurationWarning warning a setting no backend reads
CrossSectionUnitWarning warning cross section given in mm²
DiagnosticsWarning warning the findings of diagnose(...).warn()
MixedCoordinatesWarning warning projected and local coordinates mixed
ResourceLimitError error too many segments, nodes or ports
UniformCurrentFieldWarning warning image-family field values near grids and stars
VectorFitQualityWarning warning vector fit misses its rms tolerance
VectorFitConvergenceWarning warning poles still moving
VectorFitUnderdeterminedWarning warning more poles than samples
RhoFStandardQualityWarning warning standard form misses a sample
NonPassiveFitWarning / NonPassiveFitError warning / error exported formula not passive
RhoPresetMismatchWarning warning BusType fitted over another preset
EvaluateSpecError error BusType document or formula rejected
ResultFormatError error not a readable result file
OverpassError error failed Overpass query

Solver and backends

BackendCapabilityError

gf.BackendCapabilityError, subclass of ValueError and NotImplementedError.

When: raised by Engine.solve before any numerics when the backend cannot represent the world: a number of soil layers it does not support (three or more distinct layers for every engine but mom_sommerfeld and fem), an explicitly requested kernel the backend does not implement (kernel="line" for the mom family), a world outside the axisymmetric model of fem with FemOptions.model="axisymmetric", a world the 3-D model of fem refuses before meshing (see the fem engine page), or a horizontal wire so close to the layer interface, on either side of it, that the point form cannot evaluate it (see PointKernelInterfaceWarning). solve_mutual_matrix and solve_mutual_field raise it for a backend outside the image family and for three or more layers. A backend registered by the user that declares no support for concrete shells, junctions or voltage sources raises it for such worlds; every built-in backend supports them.

What it means: nothing was computed. The message names the backends that can solve the world.

What to do: choose one of them (see the backend registry); three or more distinct layers need mom_sommerfeld.

BackendCapabilityWarning

groundfield.solver.BackendCapabilityWarning.

When: emitted when the backend solves the world with a documented simplification: a backend without two-terminal sources returns the current of a source with return_to through remote earth.

What it means: the conductor network or the return terminal is simplified. No built-in backend emits it since 2026.11.

What to do: use an image or MoM backend when the conductor network or the return terminal matters.

Audit trail

Up to 2026.11 fem also treated distributed and inductive conductors as lumped resistive branches, with this warning.

ExperimentalBackendWarning

gf.ExperimentalBackendWarning.

When: emitted once per process on the first solve with an experimental backend (fem).

What it means: fem is a reference backend whose model, options and results may still change between releases; its measured accuracy is on the fem engine page.

What to do: nothing; filter the category once you have read the limits of fem.

BackendOptionsWarning

groundfield.solver.BackendOptionsWarning.

When: emitted when Engine.options configures a backend that will not run (for example options={"fem": ...} with backend="mom").

What it means: the options are ignored.

What to do: remove them or select that backend.

ProbePointsIgnoredWarning

gf.ProbePointsIgnoredWarning (also groundfield.solver).

When: emitted by solve_mutual_matrix when it is given probe_points but computes the galerkin off-diagonal, the default of every call since 2026.11.

What it means: a call written for 0.15.0 (the AP1 pipeline, for example) keeps running and now returns the reciprocal galerkin matrix, which reproduces the solve of the clusters joined by branches; the probe matrix missed it by −0.15 … −0.88 % on an AP1-like site.

What to do: drop probe_points, or pass offdiag="probe" to keep the 0.15.0 definition.

Audit trail

Up to 0.15.0 probe points selected the potential at those points as the off-diagonal.

EngineFrequencyOrderWarning

groundfield.solver.engine.EngineFrequencyOrderWarning.

When: emitted when Engine.frequencies is not strictly increasing.

What it means: the order is kept, and every result list follows it.

What to do: sort the list, or state the intent with engine.with_frequencies(..., preserve_order=True).

ShallowSegmentWarning

groundfield.solver.ShallowSegmentWarning.

When: emitted for the point kernel only (kernel="point" and the mom family) when a leakage segment is longer than about four times its depth.

What it means: the self term uses the point image at distance \(2z\) instead of the image line, which overestimates it by more than 13 % and biases the impedance high. The message quantifies the worst case.

What to do: shorter segments, or the exact line kernel of the image family (the default), which has no such bias.

PointKernelInterfaceWarning

groundfield.solver.PointKernelInterfaceWarning.

When: emitted for the point form (kernel="point" of the image family and of solve_mutual_*, the mom family) when a horizontal wire lies within 0.6 segment lengths of the layer interface \(h_1\), on either side of it. Closer than 0.387 segment lengths, or where the rule would reach above the surface, the solve raises BackendCapabilityError instead.

What it means: the impedance is biased low. With an electrode that reaches the interface (the cross-layer path) the three-point rule of the diagonal samples the layered correction where it varies quickly; with every wire above \(h_1\) the diagonal takes the image of a segment in the interface as a point source \(2\lvert z - h_1\rvert\) away, while its image line runs much closer to the wire. Measured: 3–17 % low on the cross-layer path, −2.5 % and −0.4 % for a ring 0.2 m above \(h_1\) (1000/30 and 30/1000 Ω·m, ds = 0.5 m).

What to do: the exact line kernel of the image family (the default), or segments shorter than the distance of the wire to the interface.

Audit trail

The refusal below 0.387 segment lengths follows audit A3S-02: a ring 1 µm above \(h_1\) read −1931 Ω where the line kernel gives 4.18 Ω.

InterfaceContactWarning

groundfield.solver.InterfaceContactWarning.

When: emitted by every segment backend (the image family, mom, mom_sommerfeld), by solve_mutual_* and by the three-dimensional fem (both rules, once per rule and solve) where the thin-wire model, which carries the current on the wire axis, deviates from the solid wire next to a layer interface:

  • Rod ends: a rod head or tip within one wire radius of a layer interface. An end that meets the end of another rod — a rod split at the interface into two pieces, the usual way to give each layer its own piece — has no free end face and is not reported.
  • Horizontal wires: every electrode but a rod, and the leaking pieces of a galvanic distributed conductor, whose axis lies within the reach of a contrasting interface (table below). A piece of a galvanic distributed conductor counts as horizontal while its slope \(\lvert e_z\rvert\) is at most 0.1 (5.7°).

What it means: the result carries the thin-wire error next to the interface. The thin-wire model has no end face: a rod that ends exactly at the interface is a wire entirely on one side of it, and one that reaches past it by a fraction of its radius touches the other layer through a short part only, while the solid rod with a flat end is continuous in between. Against an axisymmetric model of the solid rod (4.5 m, \(a\) = 8 mm, 1000/30 Ω·m) the thin wire reads +21 % with its tip at the interface, +7 % 1 mm above it, −4.6 % 1 mm below it, and within a few per cent beyond two radii, as anywhere else. Next to a more conductive layer the current of a horizontal wire crowds to its near side, which a current on the axis cannot follow: against the solid torus a ring of \(a\) = 5 mm over a layer 33 times more conductive reads +0.59 % at 4 radii, +1.2 % at 3, +3.6 % at 2, +8.6 % at 1.5 and +32 % at 1.1 radii, and +89 % when the interface cuts the wire; under a more resistive layer up to +2.6 %.

Reach of the interface, wire axis to interface plane, in wire radii \(a\):

contrast of the layers more conductive beyond more resistive beyond
1.4 1.0 \(a\) 1.0 \(a\)
2 1.3 \(a\) (1.14 \(a\))
3 1.9 \(a\) 1.3 \(a\)
5.5 2.7 \(a\) (1.60 \(a\))
10 3.3 \(a\) 1.9 \(a\)
18 3.7 \(a\) (2.05 \(a\))
33 3.9 \(a\) 2.2 \(a\)
100 4.1 \(a\) 2.2 \(a\)
1000 4.3 \(a\) 2.3 \(a\)

Log-linear in between, values in brackets interpolated; held beyond 1000, and at 1.0 \(a\) down to a contrast of 1.3; 1.0 \(a\): only a wire that the interface cuts. Below a contrast of 1.3 nothing is reported. The table is measured on rings with \(r_0/a \ge 18\); a thicker wire on a smaller ring is not covered. No generated network and no world of the AP1 soils (\(h_1\) = 5 or 30 m) comes within reach.

diagnose() reports both under interface_contact; with an fem engine it reports neither for a world that the axisymmetric model takes, which resolves rod end faces and ring wires.

What to do: keep rod ends and horizontal wires a few wire radii from a contrasting interface; bracket a rod end by moving it by ±2 wire radii; check a ring with fem's axisymmetric model (FemOptions.model="axisymmetric"), which solves the wire as the solid torus and does not warn.

How the reach was measured, and audit trail

The three-dimensional fem is a thin wire without end faces too: a rod tip on 1000/30 Ω·m reads +43 % there against the solid rod, with an error estimate of 6e-3 (audit W4R2A-03, since which it warns for rod ends). It shares the horizontal-wire limit as well (its smoothed line source lies between the thin wire and the torus). The horizontal-wire rule dates from 2026.11 (audits W4A-07, W4B-02, W4R2A-04 and W4R3A-02).

The solid torus is the axisymmetric fem; a Hankel thin ring plus the exact 2-D proximity correction agrees with it to 5e-4. The +2.6 % under a more resistive layer is a 55 mm wire on a 1 m ring at 1.01 radii, contrast 1000.

The reach is the distance of the wire axis from the interface inside which the thin wire (converged in its segment length) is 1 % or more off: the largest of five ring geometries (\(r_0/a\) = 18 … 400: rings of 0.5 … 5 m at 0.3 … 2 m depth, \(a\) = 5 … 55 mm; the more conductive layer below the wire, for the 2 m ring also above it; the more resistive layer below and above every one; a 55 mm wire on a 1 m ring is the widest at every contrast), rounded up to 0.1 \(a\), plus 0.1 \(a\) for the contrasts between the nodes — the resistive side from the converged thin wire, the conductive side from the thin wire at one segment length, its node at 1000 raised to 4.3 \(a\) so that the converged distances lie inside.

Checked at the nodes and between them (conductive 1.3 … 1.9, 2.5, 4, 7, 14, 25, 50, 300; resistive 2, 5.5, 18, 300): of 2348 conductive distances (the thin wire at one segment length) and 2470 resistive ones (converged in it) none with the thin wire 1 % or more off lies outside the reach, the largest errors outside it are +0.94 % and +0.93 %; converged, the thick wire's conductive 1 % distances lie 0.004 … 0.17 \(a\) inside the reach (the node at 1000 is 4.3 \(a\) for the 4.15 \(a\) at 300). Below a contrast of 1.3 a cut wire is at most +0.96 % off at 1.3 and +1.06 % at 1.35 (the thick wire cut 0.5 \(a\) below its axis by a more resistive layer above it).

Up to audit W4R2A-04 the table came from four geometries (0.2 … 0.4 \(a\) short of the thick wire on the 1 m ring) and started at a contrast of 2, below which a cut wire read up to −1.46 %; up to audit W4R3A-02 its resistive side was measured above the wire for the thin ring only (the thick wire 1 % off up to 0.74 \(a\) beyond it: +1.75 % at 1.3 \(a\) under a 33 times more resistive layer, unreported) and it started at 1.4 (+1.16 % there).

A steeper piece of a galvanic distributed conductor passes the reach of an interface over at most \(2\,\mathrm{reach}/\lvert e_z\rvert\) wire radii of its length, like a rod through an interface, and is not reported (a step at the cutoff, kept). That diagnose() reports nothing for a world of the axisymmetric fem is audit W4R2A-05.

SeriesTruncationWarning

groundfield.solver.image_2layer.SeriesTruncationWarning (also in groundfield.solver.mom and groundfield.solver.mom_sommerfeld).

When: emitted when the Tagg/Sunde image series reaches Engine.image_max_terms before its tail bound \(\lvert K\rvert^{n+1}/(1-\lvert K\rvert)\) falls below image_series_tol, typically at very high layer contrast (\(\lvert K\rvert \to 1\)).

What it means: the image series is cut before its tolerance; the result is not converged in the series.

What to do: raise image_max_terms (the default 300 covers \(\lvert K\rvert = 0.94\)).

SommerfeldConvergenceWarning

groundfield.solver.mom_sommerfeld.SommerfeldConvergenceWarning.

When: emitted when the quadrature of the reflected part of the layered Green's function does not converge to epsrel. The message names the worst pair and the cause.

What it means: the value may even have the wrong sign.

What to do: raise max_osc_panels in Engine(options={"mom_sommerfeld": {...}}) for kilometre separations with thin layers; at a layer contrast \(\lvert K\rvert \to 1\) in two-layer soil use image_2layer.

FemReductionWarning

gf.FemReductionWarning.

When: never emitted since 2026.11: fem solves a conforming finite-element model (user decision Q37) instead of the equivalent-hemisphere reduction.

What it means: the class is kept importable for filters of older code.

What to do: none needed; remove filters for this category when convenient. The conforming model and its guards are on the fem engine page.

Audit trail: the reduction up to 2026.11

Up to 2026.11 it was emitted once per fem solve, listing the reasons, when the reduction did not represent the world: several electrodes in a cluster (mutual resistance neglected; −35 % for a ring with three rods, −55 … −75 % for two bonded rods of which one reaches into a conductive top layer), several clusters (no coupling between them), or a layer interface within the hemisphere radius or the electrode's horizontal extent over a layer that the electrodes touch or that conducts no better than theirs (−3 … +48 % measured for a spanned layer, −17 … +16 % for one within the extent; −44 … −78 % for a rod that reaches 1 µm … 8 cm into a conductive top layer, −21 … +30 % for a ring lying exactly on the interface; −10 … +46 % for a more conductive layer within the extent behind one that conducts no better than the electrodes', audit R2A-09). A layer that no electrode touches, that conducts better than the electrodes' layer and whose top lies above the hemisphere radius or the horizontal half-extent (below the hemisphere: with no such shielding layer in between) was no warning but a BackendCapabilityError (user decision Q23 and audit D2A-03: fem misplaced the current, mostly far too low), as were electrodes touching a layer the hemisphere does not reach, a strip deeper than half its length, a ring deeper than its diameter and a driven MeshElectrode (the closed forms outside their range).

ComplexImageFitWarning

groundfield.solver.cim.ComplexImageFitWarning.

When: emitted only by a direct call of groundfield.solver.cim.fit_complex_images when the complex-image fit misses its tolerance. The cim backend no longer fits (it is a deprecated alias of image).

What it means: the fitted images do not reproduce the layered kernel to the requested tolerance.

What to do: do not use the fit as a Green's function.

Coupling (earth return, layered Green's function)

SommerfeldResolutionWarning

groundfield.coupling.layered_green.SommerfeldResolutionWarning (also raised by coupling.sommerfeld_inductance).

When: emitted when the Hankel quadrature cannot place enough nodes per oscillation of \(J_0(\lambda s)\) within its node budget — for example a conductor longer than the spectral range of the earth-return quadrature (see Known limitations).

What it means: the result would not be converged.

What to do: lower lambda_max_factor (no accuracy is lost: the truncated tail is added in closed form) or reduce the distance range of the group.

SommerfeldTailTruncationWarning

groundfield.coupling.layered_green.SommerfeldTailTruncationWarning.

When: emitted when the reflected kernel needs more closed-form image terms than its budget to bound the truncated tail of the quadrature (a very wide range of horizontal distances in one group, typically pairs near the surface or the layer interface).

What it means: the value is then not bounded by the documented tolerance.

What to do: lower lambda_max_factor (fewer image terms are then needed) or reduce the horizontal distance range of the group.

Model and input

DeprecationWarning

When: emitted for every deprecated name, keyword, JSON key or backend alias.

What it means: the name still works; the message names the replacement and the earliest removal (2027.5).

What to do: see Deprecations.

InertConfigurationWarning

groundfield.utils.InertConfigurationWarning.

When: emitted when a public setting is stored but read by no backend: a non-default BoundaryConditions field or a soil relative_permittivity (also in the generator soil specs).

What it means: the setting has no effect. Every backend uses the quasi-static conduction-current model with remote earth as reference.

What to do: remove the setting.

CrossSectionUnitWarning

groundfield.conductors.CrossSectionUnitWarning.

When: emitted for a conductor cross_section above 10⁻² m².

What it means: almost always a value in mm² (50 instead of 50e-6), which would make the conductor a near-ideal short.

What to do: give the cross section in m².

Diagnostics

DiagnosticsWarning

gf.DiagnosticsWarning.

When: emitted by diagnose(...).warn(): one aggregated warning with all findings, one line per cause (mixed coordinates, thin-wire ratio, resolution, problem size, close or interpenetrating wires, overlapping inductive conductors, rod ends and horizontal wires next to a layer interface, inert settings, series truncation).

What it means: the solve emits the discretisation findings as individual warnings; this class collects them before a solve.

What to do: follow the advice in each line; see Diagnostics.

MixedCoordinatesWarning

groundfield.diagnostics.MixedCoordinatesWarning.

When: emitted once per solve by the image family, mom, mom_sommerfeld, fem and solve_mutual_*, before anything is discretised, when points of the world lie both within 10 km of the origin and beyond 1000 km from it (horizontal distance): electrodes at projected (UTM, Gauss–Krüger) coordinates and a node or electrode near (0, 0), almost always given in the wrong system by mistake.

What it means: the world is solved as given, its two groups some 33 000 km apart; the message names both groups and the conductors between them. Measured with a 12 m × 7 m outline and a 3 m rod at UTM coordinates: a return rod given at local (80, 15) m raises \(Z_{in}\) by 0.43 %; a PEN cable to a cabinet at local coordinates is 33 118 km long, \(Z_{in}\) = 7494 + j25 396 Ω instead of 5.39 + j0.19 Ω at 50 Hz with carson_series, and the default sommerfeld earth return does not finish.

What to do: give every point in one coordinate system; to stop such a solve at once, warnings.simplefilter("error", MixedCoordinatesWarning). diagnose() reports the same world under coordinates (a warning), and a world wider than 100 km that does not mix as information. A world wholly in projected or wholly in local coordinates never warns.

Audit trail

The warning and the check of fem at the solve date from 2026.11 (user decision D5); the measurements are those of audit W2B-04.

ResourceLimitError

gf.ResourceLimitError, subclass of ValueError.

When: raised before any allocation when the predicted number of segments, or of unknowns of the dense nodal system, exceeds the engine's limit Engine.max_segments (default groundfield.diagnostics.HARD_LIMIT, 20 000), by every segment backend and by solve_mutual_matrix / solve_mutual_field. fem checks the display segments that carry the point sources of its result against Engine.max_segments too, and limits its mesh by FemOptions.max_nodes (axisymmetric, about 4 GB per million nodes) and max_nodes_3d (3-D; the solve adds about 2.9 GB per million nodes, 3.0 … 3.1 GB with the process), estimated before anything is assembled, and the ports of its 3-D model by max_ports_3d (100), checked before meshing.

What it means: nothing was allocated. The usual cause is a geometry given in millimetres, a very small segment_length or a conductor discretize_segment_length in millimetres.

What to do: check units and segment lengths; to solve a large world on purpose, raise the limit of the engine, Engine(max_segments=...) (or the FemOptions limit). Below that limit, a world at or above the engine's notice size (Engine(warn_segments=...), default SOFT_LIMIT = 5 000) only emits the UserWarning "budget: ..." that the solve may take minutes; the notice comes from Engine.solve (with any backend), not from solve_mutual_matrix / solve_mutual_field. Both sizes count the segments of the integral engines.

Post-processing

UniformCurrentFieldWarning

gf.UniformCurrentFieldWarning.

When: emitted once per call by touch_voltage, step_voltage, touch_voltage_envelope, touch_voltage_at_part and touch_voltage_spectrum when a result of the image family (one uniform current per straight wire of an electrode) is evaluated within 5 m (NEAR_FIELD_DISTANCE_M) of a grid, mesh, star, strip, open polyline or bonded multi-electrode cluster. Without the world the point sources of the result stand in for the wires.

What it means: the real current crowds to edges and tips, so the field values there are impedance-grade, not field-grade (against mom: a 20 m grid corner +6 % in the touch voltage 1 m outside and −8 % in the step from 1 m to 2 m outside; see Known limitations).

What to do: re-solve with backend="mom" for those quantities.

VectorFitQualityWarning

gf.VectorFitQualityWarning.

When: emitted when the relative rms error of a vector fit exceeds rms_tol (1 %), or when the imaginary part of a 0 Hz sample had to be discarded.

What it means: the fitted model misses the samples by more than the tolerance.

What to do: inspect rms_relative; try another n_poles, more samples or weighting="inverse_magnitude".

VectorFitConvergenceWarning

groundfield.fit.VectorFitConvergenceWarning.

When: emitted when the poles still move by more than 1 % after n_iter relocation steps.

What it means: the poles are not converged.

What to do: more iterations, another n_poles, or a different weighting.

VectorFitUnderdeterminedWarning

groundfield.fit.VectorFitUnderdeterminedWarning.

When: emitted when n_poles is not smaller than the number of samples.

What it means: the fit only interpolates.

What to do: fewer poles or more frequencies.

RhoFStandardQualityWarning

gf.RhoFStandardQualityWarning.

When: emitted when the standard-form fit misses a sample by more than max_relative_tol (5 %).

What it means: the fixed ansatz cannot represent the sampled \(Z(\rho, f)\).

What to do: check max_relative, restrict the \(\rho\) range, or fit per \(\rho\) with vector fitting.

IO and export

NonPassiveFitWarning / NonPassiveFitError

gf.NonPassiveFitWarning, gf.NonPassiveFitError (subclass of ValueError).

When: emitted (or raised, with require_passive=True) when the exported impedance formula has \(\operatorname{Re}Z < 0\) somewhere between 0 Hz and twice the highest fitted frequency.

What it means: the formula is not passive there; the message names the frequency (and \(\rho\)) of the most negative value.

What to do: refit (fewer poles, different weighting) before exporting.

RhoPresetMismatchWarning

gf.RhoPresetMismatchWarning (also groundfield.io).

When: emitted by evaluate_spec and bustype_from_spec when the caller names the preset of its bus (rho_preset=...) and the document records a different one in metadata["rho_preset"].

What it means: the rho of the bus then means another resistivity than the rho of the formula (see the effective resistivity in Known limitations).

What to do: evaluate the BusType with the preset it was fitted over, or refit it over the preset of your bus.

Audit trail

The preset record is user decision Q39.

EvaluateSpecError

gf.EvaluateSpecError, subclass of ValueError.

When: raised by evaluate_spec, load_bustype_json and BusTypeSpec.from_dict when a BusType document or its formula is rejected: not a BusTypeSpec, empty formula, unknown symbol, or a formula outside the allowed grammar or its size bounds.

What it means: the parser never evaluates the text; its own groundfield.io._formula.FormulaError arrives wrapped in this class.

What to do: regenerate the document with save_bustype_json, or fix the formula by hand.

ResultFormatError

gf.ResultFormatError, subclass of ValueError.

When: raised by load_result for a file that is not a readable result file: wrong format, a newer schema_version, invalid JSON or UTF-8, or metadata outside what the writer produces.

What it means: the file is not loaded.

What to do: load it with the groundfield version that wrote it (written_by), or regenerate it.

OverpassError

gf.OverpassError, subclass of RuntimeError.

When: raised by the OSM queries on a non-success Overpass answer or a malformed payload (after the retries); status_code and the start of the body are attached.

What it means: the answer is not cached.

What to do: retry later, reduce the radius, or work from a cached / stored answer.

Other warnings (plain UserWarning)

Where When What to do
coupling (Carson) earth_inductive_model="carson_series" with layered soil: the upper-layer \(\rho_1\) is used use "sommerfeld", which supports layered soil
solver (inductive assembly) earth_inductive_model="perfect_mirror" with inductive segments on both sides of the soil surface (an overhead lead and a buried PEN); once per solve, naming the pairs and conductors use "sommerfeld" (the default) for numbers
solver (image_2layer, kernel="point") the deepest segment ends less than two segment lengths above the layer interface refine segment_length near the interface, or use the default line kernel
solver (kernels) two segments of different wires closer than the 1 mm singularity clamp merge the wires or move them apart
solver (pipeline) a source looks like the hand-made counter-source of another one use one source with return_to
solver (pipeline) conductors could not be matched to the branch network; their inductance is not applied check the conductor end points
World.set_boundary_conditions a boundary field set to (or back from) a non-default value none needed; the fields are not read
geometry (PolylineElectrode) closed=True with only two vertices (treated as open) give at least three vertices
generators buildings that cannot be connected to a PEN cable or a feeder, exhausted feeder slots, a cabinet without electrodes, a footprint widened to 1 m, source_return_to overriding the measurement return check the layout parameters named in the message
geo an unreadable Overpass cache file (re-fetched) none
fit / io a fit or exported formula that does not depend on frequency expected for frequency-independent data; otherwise check the samples

The warning of perfect_mirror across the soil surface is user decision Q27: its additive image has no physical basis for such a pair, and its result is a diagnostic baseline.

Built-in exceptions with a fixed meaning

Exception Raised when
KeyError an electrode, junction, conductor or source name is unknown (the message suggests the closest names)
ValueError an invalid value: non-finite or non-positive physical input, a current source of 0 A, a short-circuited two-terminal source, a loop of voltage sources, a junction without soil contact, an empty world
TypeError an unknown keyword of a factory, or a soil that is not a soil model
NotImplementedError FieldResult.potential for three or more soil layers (BackendCapabilityError, a subclass, for a world a backend cannot represent, such as a strip with FemOptions.model="axisymmetric")
ImportError a function of groundfield.geo without the geo extra, fem's 3-D model without the fem3d extra, or to_bustype without groundinsight (the message gives the install command)
pydantic.ValidationError a model field fails validation (subclass of ValueError)