Skip to content

Units and conventions

The units, the coordinate system, the phasor convention and the signs that every input and output of groundfield follows. Check this page when you build a world from your own data, or when you compare results with another tool or with a measurement.

Units

Every physical input and output is in SI units, without prefixes.

Quantity Unit Examples
coordinates, lengths, radii, depths m position, radius, wire_radius, h_1, segment_length
cross section m² cross_section=95e-6 for 95 mm² (a value above 10⁻² m² warns with CrossSectionUnitWarning)
resistivity of soil, concrete, metal Ω·m rho, rho_1, concrete_rho_ohm_m, resistivity=1.68e-8 (copper)
concrete-shell coefficient Ω·m concrete_shell_coefficient_ohm_m
current A (RMS) CurrentSource.magnitude
potential, voltage V (RMS) electrode_potentials, touch_voltage
impedance Ω input_impedance, cluster_impedance, solve_mutual_matrix
frequency Hz Engine.frequencies
inductance H; per unit length H/m coupling.inductance
per-unit-length impedance Ω/m references.earth_return, references.pollaczek
time (fault duration) s permissible_touch_voltage_en50522(t_clear_s)
angles degrees phase_deg, orientation_deg

Names follow two rules: the physics model uses bare SI values and the literature symbols (rho, rho_1, h_1, h); the generator specs carry a lower-case unit suffix (depth_m, concrete_rho_ohm_m, frequency_hz, source_magnitude_a).

Coordinates

  • Right-handed Cartesian \((x, y, z)\) in metres. In worlds built from map data, \(x\) points east and \(y\) north (local frame of the projection origin).
  • \(z\) is the depth below the soil surface, positive downwards. The soil surface is \(z = 0\), the soil is \(z > 0\), the air \(z < 0\) (overhead conductors). A ring "0.8 m deep" has center=(x, y, 0.8).
  • A rod's position is its upper end; it extends downwards by length.
  • ParaView and other viewers assume \(z\) upwards: apply a transform with scale \((1, 1, -1)\) to VTK files.
  • Projected coordinates (UTM, Gauss–Krüger) may be used as they are. When a horizontal coordinate of a world exceeds 10 km, the solvers (image, image_2layer, mom, mom_sommerfeld, solve_mutual_*) work in a local frame: the world shifted exactly by the centre of its horizontal bounding box, rounded to whole metres. Point sources are reported in the user's coordinates, and FieldResult.potential evaluates in a local frame of the sources in the same way (since 2026.11). A world at UTM coordinates gives the impedance of the same world at the origin to within about 5 · 10⁻¹¹; worlds within 10 km of the origin are not shifted.
  • Mixed coordinates. A world that mixes projected and local coordinates — points within 10 km of the origin and beyond 1 000 km from it, typically a return electrode, a cabinet or a cable end entered in a local system in a UTM world — is solved as given: its two groups lie some 33 000 km apart, and a conductor between them is that long. The local frame cannot help such a world: its geometry is wrong. Since 2026.11 (user decision D5) the solve of such a world warns once with MixedCoordinatesWarning (image family, mom, mom_sommerfeld, solve_mutual_*), before anything is discretised, and diagnose() reports it under coordinates. A world wholly in projected or wholly in local coordinates is never warned about at the solve; diagnose() reports worlds wider than 100 km as information (audit W2R2-06).
Projected and mixed coordinates: measurements and audit trail

Round-off of projected coordinates. Segment counts and straight runs allow the round-off of the coordinates' own magnitude, 64 \(\varepsilon |x|\) (0.46 µm at an easting of 32.6 · 10⁶ m). A world moved from (0, 0) to the UTM origin (32 604 321.123 m, 5 812 345.678 m) then changes its impedance by 3 · 10⁻¹¹ with the point kernel (mom, mom_sommerfeld, image with kernel="point"), the effect of the rounding of its vertices; up to 2026.11 an edge of a whole number of segments got one more there (a generated 10 m mesh foundation 508 instead of 440 segments, +2.6 · 10⁻⁴ in mom). With the default line kernel the results agree to the same level: the kernel blends its exact integral into its far form between six and 7.5 segment lengths (user decision D2), so no pair switches its form with the round-off of the coordinates. Over 12 local shifts of 0.1 m … 8.8 km the impedance spreads by at most 8 · 10⁻¹⁴ (touch voltages 2 · 10⁻¹³), and the solve at the UTM origin lies within 5 · 10⁻¹¹ of the local one (touch voltages 9.2 · 10⁻¹⁰), for strips, a mesh, a star and a ring in homogeneous and two-layer soil and for two cross-layer worlds (audits W2B-01 and W3A; with the one-step switch before, up to 5.4 · 10⁻⁷ for direct pairs and 2.6 · 10⁻⁵ in two-layer soil, where an image distance equalled six segment lengths) (known limitations). Worlds within 10 km of the origin are not shifted, and their electrodes are discretised as before.

Whole numbers of pieces. A distributed conductor whose length exceeds a whole number of pieces only by round-off gets that whole number at any position since 2026.11, near the origin too: a galvanic counterpoise of 60 m in 10 m pieces from (3, 0, 0.5) m had 7 pieces in about a quarter of all directions (829 … 876 of 3 600 in 0.1° steps, depending on how the angles are formed; computed length 60.00000000000001 m) and has 6 in every one, its impedance −0.30 % with image and −2.54 % with mom (audits W2B-03, W2R2-08).

Mixed coordinates. The round-off of a mixed world is that of the projected world (1.5 · 10⁻¹¹ against 1.0 · 10⁻¹¹ with the point kernel), but its geometry is wrong. Measured with a 12 m × 7 m outline and a 3 m rod at UTM coordinates (audit W2B-04): a return rod given at local (80, 15) m raises \(Z_{in}\) by 0.43 % with image and 0.44 % with mom (the potential next to the outline by 5.8 %); a PEN cable to a cabinet at local coordinates is 33 118 km long, \(Z_{in}\) = 7494 + j25 396 Ω instead of 5.39 + j0.19 Ω at 50 Hz with carson_series, and the default sommerfeld earth return does not finish.

Phasors and frequency

  • Time convention \(e^{+j\omega t}\), \(\omega = 2\pi f\): a quantity \(x(t) = \sqrt{2}\,\operatorname{Re}\{\underline{X}\,e^{j\omega t}\}\) is represented by its RMS phasor \(\underline{X}\). An inductive impedance has a positive imaginary part, \(Z = R + j\omega L\).
  • The Laplace variable of the vector fits is \(s = j\omega = j\,2\pi f\).
  • Every result is a list with one value per frequency, in the order of Engine.frequencies (the order is never changed; a non-monotonic list warns with EngineFrequencyOrderWarning).
  • Frequencies must be finite and non-negative; \(f = 0\) (DC) is a valid operating point. The models are quasi-static and validated for \(f < 1\,\mathrm{kHz}\): displacement currents in the soil and wave propagation along the conductors are neglected. Higher frequencies are accepted but outside the validated range.
  • A fault-current spectrum is combined as a true RMS value, \(U_\text{rms} = \sqrt{\sum_k \lvert\underline{U}_k\rvert^2}\) (touch_voltage_spectrum).

Potentials, currents and signs

  • Potential reference. Every potential is measured against remote earth, \(\varphi \to 0\) far from all electrodes. The soil surface is insulating (no current into the air).
  • Source current. A CurrentSource with magnitude \(I > 0\) and phase_deg \(= 0\) drives \(+I\) into the node attached_to and takes it back at return_to (or at remote earth).
  • Electrode currents. FieldResult.electrode_currents[name] is the current an electrode leaks into the soil: positive at the feeding earth, negative at the electrode that collects the current of a two-terminal source. With one source of \(+1\) A the potentials of the fed earthing system are positive (earth potential rise).
  • Impedances. Input, cluster and electrode impedance are defined in the quickstart; for a passive earthing system their real parts are positive.
  • Touch and step voltage. \(U_T = U_E - \varphi(\text{feet})\) and \(U_S = \varphi(\mathbf{r}_1) - \varphi(\mathbf{r}_1 + 1\,\mathrm{m}\cdot\hat{\mathbf{e}})\), complex phasors in V for the given source current; compare magnitudes with the permissible values.
  • When comparing with another tool or a measurement, check its sign convention for injected currents and node potentials.

Material defaults

Parameter Default Note
wire radius of electrodes and conductors 5 mm wire_radius=0.005
conductor resistivity \(1.68\cdot10^{-8}\,\Omega\,\mathrm{m}\) copper
relative permittivity of the soil stored, not used quasi-static model (InertConfigurationWarning when changed)
magnetic permeability \(\mu_0 = 4\pi\cdot10^{-7}\,\mathrm{H/m}\) soil and conductors non-magnetic