Import from OMICRON instruments

groundmeas reads the export files of the OMICRON COMPANO 100 (XML) and the OMICRON HGT1 (StepTouch text report) directly – no OCR and no typing of values. Each test becomes one measurement with all its items.

To try it without own files, create the synthetic demo campaign of the tower workflow; it contains COMPANO and HGT1 files of four towers:

$ gm-cli towers demo demo

Command line

$ gm-cli --db tower8.db import-omicron \
      --location "LX-01 tower 8" --asset-type overhead_line_tower \
      --ze demo/measurements/ZE_LX-01_8.xml \
      --ut demo/measurements/UT_LX-01_8.txt \
      --transferred demo/measurements/UT_LX-01_8-9.txt \
      --soil "demo/measurements/ZE_LX-01_8_spez.Erdw..xml" \
      -D 100 --timezone Europe/Berlin
Connected to tower8.db
Imported fall of potential: measurement id=1
Imported touch voltages: measurement id=2
Imported transferred potential (UT_LX-01_8-9.txt): measurement id=3
Imported soil resistivity: measurement id=4
Option Meaning
--location, -l location name; an existing location with this name is reused
--asset-type, -a asset type of the measurements, e.g. overhead_line_tower or substation
--fall-of-potential, --ze COMPANO export with the fall-of-potential test
--step-touch, --ut HGT1 report with touch voltages (needs --ze for the reference current)
--transferred HGT1 report measured elsewhere, e.g. at a neighbouring tower (repeatable)
--soil COMPANO export with a soil-resistivity measurement
--current-electrode-distance, -D distance of the current electrode in m – needed for the 62 % method
--per-frequency/--no-per-frequency also store the values at both test frequencies (default on)
--voltage-level-kv, --operator measurement metadata
--timezone IANA time zone of the instrument clock; the time stamps are converted to UTC

For a whole campaign of overhead-line towers (one location per tower, metadata from the measurement description) use gm-cli towers import-db.

What is stored

Measurement (method) Items
fall of potential (injection_earth_electrode) earthing_impedance per probe distance (measurement_distance_m, distance_to_current_injection_m = -D) at the power frequency – the instrument result, the mean of both test frequencies – and at both test frequencies; earthing_resistance (footing resistance: probe voltage / current into the footing) if the reduction factor was applied; earthing_current (injected current); earth_fault_current and shield_current from the clamp readings of the reduction factor
touch voltages (injection_earth_electrode) touch_voltage per reading with input_impedance_ohm = 1000 Ω and additional_resistance_ohm = 0 (1k) or 1000 Ω (2x1k), the measuring point in the description; high-impedance readings (HIGH Z) as prospective_touch_voltage, other terminations without input impedance (with a warning); values at the power frequency (interpolated) and at both test frequencies; earthing_current = output current of the step/touch test from the COMPANO export
transferred potential (injection_earth_electrode) transferred_potential per reading, reference current as above
soil resistivity (wenner or schlumberger) soil_resistivity per reading; Wenner (c = a): spacing a in measurement_distance_m; Schlumberger: AB/2 = c + a/2 in measurement_distance_m and MN/2 = a/2 in distance_to_current_injection_m (COMPANO: a = MN spacing, b = electrode depth, c = distance current – potential electrode)

Units are converted to SI: every SI prefix that occurs (µA/μA/uA, mA, mV, kV, mΩ, µΩ, kΩ, kΩm, Ωcm, …), the ohm as Ω, Ω or Ohm, and the lengths cm, km, ft (see Units). An export that contains only the instrument results (no values at the test frequencies) is stored at the power frequency. A file that lacks required elements raises MeasurementFileError with the file name. Each test is stored in one transaction: if an item cannot be stored, no empty measurement is left behind.

Python API

import groundmeas as gm

gm.connect_db("tower8.db")
fop = gm.import_fall_of_potential(
    "demo/measurements/ZE_LX-01_8.xml",
    location="LX-01 tower 8",
    asset_type="overhead_line_tower",
    current_electrode_distance_m=100,
    timezone="Europe/Berlin",
)
touch = gm.import_step_touch(
    "demo/measurements/UT_LX-01_8.txt",
    location="LX-01 tower 8",
    asset_type="overhead_line_tower",
    compano_xml_path="demo/measurements/ZE_LX-01_8.xml",
)
soil = gm.import_soil_resistivity(
    "demo/measurements/ZE_LX-01_8_spez.Erdw..xml",
    location="LX-01 tower 8",
    asset_type="overhead_line_tower",
)

location can also be a dict with name, latitude, longitude and altitude. The readers alone (no database) are in groundmeas.instruments:

from groundmeas.instruments import CompanoXMLReader, Hgt1TXTReader

reader = CompanoXMLReader("demo/measurements/ZE_LX-01_8.xml")
data = reader.read_fall_of_potential()      # distances, complex U and I per test frequency
data.impedance()                            # complex Z at the power frequency (instrument result)
data.impedance(30.0)                        # complex Z at one test frequency
reader.read_reduction_factor()              # clamp readings or None
reader.get_step_touch_currents()            # (frequencies, output currents) of the step/touch test
reader.read_soil_resistivity()              # readings with a, b, c, AB/2, MN/2 or None
Hgt1TXTReader("demo/measurements/UT_LX-01_8.txt", nominal_frequency=50).get_touchvoltage_dataframe()

Evaluating the imported data

# earthing impedance of the profile (62 % method, see Analytics)
gm.distance_profile_value(fop, algorithm="62_percent", frequency_hz=50.0)["result_value"]
# 0.1208...

# the procedure of the tower evaluation (extrapolation + conservative corrections)
gm.distance_profile_value(
    fop, algorithm="62_percent", conservative=True, frequency_hz=50.0
)["result_value"]

# one value per frequency (power frequency and both test frequencies)
gm.impedance_over_frequency(fop)
# {50.0: 0.1208..., 30.0: 0.1208..., 70.0: 0.1208...}
  • distance_profile_value(..., frequency_hz=...) evaluates one frequency of a profile stored at several frequencies; without it, a warning reminds you that the profile mixes frequencies.
  • impedance_over_frequency reduces the profile at every frequency with the chosen profile_algorithm (62 % by default) – input for the ρ–f model.
  • calculate_split_factor(earth_fault_current_id, shield_current_ids) with the earth_fault_current and shield_current items of the fall-of-potential measurement returns the share of the current that flows into the tower footing (the COMPANO reduction factor).
  • The soil-resistivity measurement can be inverted into a layered soil model, e.g. invert_soil_resistivity_layers(soil, method="wenner", layers=2) (pass the method of the measurement).
  • Touch voltages per ampere follow from the touch_voltage items and the earthing_current item of the touch-voltage measurement (the output current of the step/touch test, not the injected current of the fall-of-potential test). Multiplied by the earth-fault current \(I_E\) they give the touch voltages of the tower evaluation, see Campaigns in the database.