Preparing a campaign¶
A campaign is a set of towers measured with the same procedure, usually one or more overhead lines. Everything the tool needs is described by one configuration file; the data live in a folder of your choice, for example:
campaign-2026/
├── config.json
├── grid_data.xlsx grid data per tower (updated by --calc)
├── measurement_description.xlsx one row per measured tower
├── short_circuit_data.xlsx short-circuit currents + line protection (optional)
├── measurements/ all instrument files in ONE flat folder
│ ├── ZE_<line>_<tower>.xml
│ ├── UT_<line>_<tower>.txt
│ └── Map_<line>_<tower>.png
└── results/ created by the tool
The quickest way to get a valid starting point is the demo campaign
(gm-cli towers demo DIR): replace its files with yours and adjust
config.json. gm-cli towers example-config config.json writes only the
configuration.
Keep campaign data out of source repositories
Configuration and data contain names, locations and grid data. Keep them
next to the measurements, not in a clone of a code repository (the
groundmeas .gitignore excludes *.json, *.xml and *.csv for this
reason).
Measurement files¶
All instrument files of a campaign are stored in one flat folder
(directory.path_measurements). The file name tells the tool which line and
tower a file belongs to.
| File | Instrument | Required | Content |
|---|---|---|---|
ZE_<line>_<tower>.xml |
OMICRON COMPANO 100 | yes | fall-of-potential measurement and the measuring currents of the step/touch test |
UT_<line>_<tower>.txt |
OMICRON HGT1 | yes1 | touch-voltage readings (StepTouch report) |
ZE_<line>_<tower>_spez….xml |
COMPANO 100 | no | soil-resistivity measurement (any name that contains spez) |
UT_<line>_<tower>-<neighbour>.txt |
HGT1 | no | voltage measured at the neighbouring tower during the injection at <tower> |
Map_<line>_<tower>.<png\|jpg\|jpeg\|gif\|svg\|webp> |
– | no | map or sketch of the measurement layout for the protocol |
Naming rules¶
- Line identifiers must not contain
_– the underscore separates the parts of the file name. Hyphens, dots and digits are fine (L-110.07). - Tower identifiers may contain letters (
28N,2M). Leading zeros and letter case are ignored when files are matched:UT_L1_008n.txtbelongs toZE_L1_8N.xml. - Extensions are case-insensitive (
.XML,.Txt). - Unicode spellings are normalised (macOS stores
üdecomposed), so names with umlauts match on every operating system. - The layout of the COMPANO file names is configurable with
directory.grounding_impedance_structure:
| Value | File name | Example |
|---|---|---|
PREFIX_LINENUMBER_TOWER (default) |
<prefix>_<line>_<tower>.xml |
ZE_LX-01_8.xml |
LINENUMBER_TOWER |
<line>_<tower>.xml |
LX-01_8.xml |
TOWER_LINENUMBER |
<tower>_<line>.xml |
8_LX-01.xml |
HGT1 reports are always named UT_<line>_<tower>.txt.
Delivery with one folder per tower¶
Contractors often deliver one folder per line and tower
(<line>/Mast <tower>/…). gm-cli towers flatten copies such a delivery into
the flat layout. Line and tower are taken from the folder names, so typos
in delivered file names are corrected (UT_LH_01-0815_5.txt, a touch-voltage
report saved as ZE_….txt); photos, PDFs and spreadsheets are not copied and
the originals stay untouched.
$ gm-cli towers flatten delivery/ campaign-2026/measurements/
$ gm-cli towers flatten delivery/ campaign-2026/measurements/ --apply --report mapping.csv
Without --apply the command only prints the plan (N files, M renamed,
K conflicts). If two files would get the same name it stops with exit code 1
and copies nothing. Folder names are matched with regular expressions
(--line-pattern, default (LH[-_]\d+[-_][0-9A-Z]+), and --tower-pattern,
default ^Mast\s+(\S+)); --only FOLDER (repeatable) restricts the run to
some tower folders and --map-strip sets the prefix removed from the line in
map file names (default LH-).
COMPANO 100 export (XML)¶
Export the measurement on the COMPANO 100 (or with its PC software) as XML. The tool reads
- the potential-probe distances, the input voltages, the raw output
currents and the corrected output currents of the fall-of-potential
measurement (
FallOfPotentialReport), - the output currents of the step/touch test (the current that was injected while the HGT1 readings were taken),
- the nominal frequency configured on the instrument (available through
the Python API; the evaluation uses
nominal_frequency_Hzof the configuration), - for soil-resistivity exports the apparent specific resistances and the
electrode distances a, b, c (
SoilResistanceReport).
Units are converted to A, V and m (mA, µA/μA/uA, mV, µV, kV,
cm, km and ft are accepted, see Units). A file that lacks one of the required elements is reported with
its name and skipped. The readers are available as
groundmeas.instruments.CompanoXMLReader and Hgt1TXTReader, see
Import from OMICRON instruments.
HGT1 report (text)¶
The HGT1 StepTouch report is a tab-separated text file with a header row
Location Meas. ID Date Time f1 Level1 f2 Level2 Termination followed
by a unit row (levels in [V], [mV], [µV] or [kV], frequencies in [Hz])
and one row per reading. Each reading contains the voltage at two
frequencies next to the power frequency (for example 30 Hz and 70 Hz); the
value at the nominal frequency is interpolated linearly (see
Physical background).
The Termination column tells how the voltage was measured:
| Termination | Meaning | Used for the assessment with touch_voltage_evaluation |
|---|---|---|
1k |
1 kΩ measuring resistance (body impedance) only | without_resistor |
2x1k |
additional 1 kΩ in series (footwear/standing surface) | with_resistor (default) |
UTF-8 and Windows-1252 encoded files are both accepted.
Measurement description (measurement_description.xlsx)¶
One row per measured tower, describing how it was measured. The first worksheet is read.
| Column | Required | Meaning |
|---|---|---|
Leitung |
yes | line identifier (as in the file names) |
Mast |
yes | tower identifier |
Messung_RA_Profil_bool |
yes | 1 if the footing-resistance profile of the COMPANO export is valid, 0 to ignore it2 |
Messung_RA_Einzelwert_Ohm |
yes (may be empty) | footing resistance measured with a high-frequency earth tester in Ω |
Entfernung_Hilfserder_m |
yes | distance between tower and current electrode in m (needed for the 62 % method) |
Messpunkte_UT |
yes | measuring points of the touch voltage, comma-separated, e.g. Tower, Tower, Fence |
Name, Vorname, Firma |
no | measuring engineer and company (shown in the protocol) |
Datum |
no | date of the measurement |
Winkel_Sonde_Hilfserder_grad |
no | angle between potential probe and current electrode in degrees |
Winkel_Leitung_Hilfserder_grad |
no | angle between line and current electrode in degrees |
Witterung |
no | weather |
Messtechnik_Name |
no | instruments used |
Messfehler_Z_pu, Messfehler_U_pu |
no | measurement uncertainty of impedance and voltage (per unit) |
Sichtbefund |
no | visual inspection findings |
latitude, longitude, altitude (or Breitengrad, Längengrad) |
no | tower coordinates; used only by import-db for the location |
Every column whose name equals a key of the JSON result
is copied into the JSON file. Do not add columns named like computed results
(for example UT_V), they would overwrite them.
Measuring points. Messpunkte_UT lists one entry per HGT1 reading, or one
entry per measuring point if every point was measured twice (1k and 2x1k).
If the HGT1 itself recorded real location names, those are used and a
warning is logged when they differ from the description. If the number of
entries fits neither, the list is repeated cyclically and a warning asks you
to check the labels.
Grid data (grid_data.xlsx)¶
The grid values per tower. Only Leitung and Mast are needed initially; the
--calc step fills in the rest and writes the workbook back (rows sorted,
duplicates merged, further columns kept).
| Column | Unit | Meaning |
|---|---|---|
Mast, Leitung |
– | tower and line identifier |
Reduktionsfaktor |
– | reduction factor \(r\) of the earth wire |
Abschaltzeit |
s | fault clearing time |
Fehlerstrom |
A | single-phase short-circuit current \(I_k\) at the tower |
Lage_Prozent |
% | position of the tower on the line (written by --calc) |
Hinweis_Abschaltzeit |
– | how the clearing time was determined (written by --calc) |
The values are chosen per tower in this order (highest priority first):
| Value | 1. | 2. | 3. | 4. |
|---|---|---|---|---|
| fault current | flat value of the Leitungsschutz sheet |
short-circuit line model | value in the workbook | default_grid_data.fault_current_kA |
| reduction factor | flat value of the Leitungsschutz sheet |
value in the workbook | default_grid_data.r |
|
| clearing time | Leitungsschutz sheet (position on the line) |
value in the workbook | default_grid_data.tripping_time |
Close the workbook and keep a backup
Excel locks open files; --calc then stops with a message. Because the
workbook is rewritten, keep a copy of the original.
Short-circuit data (short_circuit_data.xlsx, optional)¶
One sheet per line¶
A worksheet named exactly like the line provides calculated single-phase
short-circuit currents along the line, for example from a network
calculation for faults at 0 %, 10 %, …, 100 % of the line length. Columns
B to D are read; column A is free (e.g. the fault location in percent).
| Column | Header | Meaning |
|---|---|---|
| B | Ik |
short-circuit current in kA |
| C | l |
distance of the fault location from the line start in km |
| D | Mast |
tower number; only the first and the last row are needed (first and last tower of the line) |
The tool fits the two-sided infeed model to these points and evaluates it at every measured tower. If the fit fails, a straight line is used and a warning is logged.
Sheet Leitungsschutz¶
Enables the position-dependent fault clearing time (and optional flat
values per line). It is read only if line_protection.enabled is true in the
configuration.
| Column | Required | Meaning |
|---|---|---|
Leitung |
yes | line identifier |
t_Schnellzeit_s |
yes | clearing time in the middle section (both relays in zone 1), e.g. 0.1 |
t_Endbereich_s |
yes | clearing time near the line ends (remote relay in zone 2), e.g. 0.4 |
Mast_Anfang, Mast_Ende |
for positions | first and last tower number (0 % and 100 %) |
Schnellzeit_von_Prozent, Schnellzeit_bis_Prozent |
no | limits of the middle section, default 16 and 84 |
Fehlerstrom_pauschal_kA |
no | flat fault current for the whole line |
Reduktionsfaktor_pauschal |
no | flat reduction factor for the whole line |
Netzform, Schutzkonzept, Bemerkung |
no | free text (network earthing, protection concept, remark) |
Equal times in both columns give one flat clearing time for the line, e.g. a
compensated network with t_Schnellzeit_s = t_Endbereich_s = 10. The
background is explained in
Assessment procedure.
Map images and logo¶
Map_<line>_<tower>.<ext> is searched next to the JSON results first and then
in the measurement folder; it appears on the first page of the protocol. A
company logo for the protocol header is configured with the key logo.
Checklist¶
- All files in one flat measurement folder, names follow the rules above
- One row per tower in the measurement description, required columns present
- Current-electrode distance filled in for every tower
- Grid-data workbook closed in Excel, backup made
- Short-circuit sheets named like the lines (if used)
- Permissible touch-voltage curve checked against the applicable standard
-
gm-cli towers run --config … --calcruns without warnings