Skip to content

Campaigns in the database

The tower evaluation works on files: the JSON results and protocols are its output. The measured data of a campaign can additionally be copied into the groundmeas database, where the dashboard, the map, the profile algorithms, the ρ–f model, the split factor and the soil inversion of groundmeas are available:

$ gm-cli --db towers.db towers import-db --config campaign-2026/config.json --dry-run
$ gm-cli --db towers.db towers import-db --config campaign-2026/config.json \
      --voltage-level-kv 110 --timezone Europe/Berlin
LX-01 tower 3                  fall_of_potential      ZE_LX-01_3.xml: measurement 1
LX-01 tower 3                  touch_voltage          UT_LX-01_3.txt: measurement 2
LX-01 tower 8                  fall_of_potential      ZE_LX-01_8.xml: measurement 3
...
10 measurements imported, 0 skipped, 0 failed (4 towers)

The database is chosen like for every gm-cli command (--db, GROUNDMEAS_DB, the stored default, ./groundmeas.db). --dry-run lists the files and the problems (see below) without opening the database.

What is stored

Every tower becomes a location named "<line> tower <tower>" (tower number without leading zeros, letters upper-case: LX-01 tower 8N). If the measurement description has the columns latitude/longitude/altitude (or Breitengrad/Längengrad), the location gets coordinates and appears on the map.

Each test becomes a measurement with asset_type = "overhead_line_tower":

File Measurement (method) Items
ZE_<line>_<tower>.xml fall-of-potential test (injection_earth_electrode) earthing_impedance per probe distance at the power frequency and at both test frequencies, with distance_to_current_injection_m = Entfernung_Hilfserder_m of the measurement description; earthing_resistance (footing resistance) if the reduction factor was applied; earthing_current (injected current); earth_fault_current and shield_current from the clamp readings of the reduction factor
UT_<line>_<tower>.txt touch voltages (injection_earth_electrode) touch_voltage per HGT1 reading (input_impedance_ohm 1000 Ω, additional_resistance_ohm 0 for 1k and 1000 Ω for 2x1k, measuring point in the description; high-impedance readings as prospective_touch_voltage) at the power frequency and both test frequencies; earthing_current = output current of the step/touch test from the COMPANO export
UT_<line>_<tower>-<neighbour>.txt (each) transferred potential (injection_earth_electrode) transferred_potential per reading, reference current as above
ZE_<line>_<tower>_spez….xml (each) soil resistivity (wenner or schlumberger) soil_resistivity per reading; Wenner: spacing a; Schlumberger: AB/2 = c + a/2 and MN/2 = a/2

The measurement description provides the operator (Vorname Name, Firma) and notes in the measurement description (file name, weather, instruments, current-electrode distance and angle). The time stamps come from the instruments; --timezone Europe/Berlin converts the instrument clock to UTC as stored by groundmeas (without the option the local time is kept). --no-per-frequency stores the values at the power frequency only.

The evaluation results (grid values, permissible touch voltage, category, protocols) are not stored in the database; they stay in the JSON and Excel output of gm-cli towers run.

Problems and repeated imports

The measurement description is required: if it cannot be read or lacks the columns Leitung, Mast or Entfernung_Hilfserder_m, nothing is imported (exit code 1). A file is reported with FAILED and the reason – and not imported – if

  • its tower has no row in the measurement description,
  • it is a fall-of-potential export and the row has no current-electrode distance (the 62 % method needs it),
  • it cannot be read or stored.

The other files are imported and the command exits with code 1. Every file is stored in its own transaction, so a failure leaves nothing behind. Files that are already in the database – same location, file name in the measurement description – are skipped; after fixing the cause, simply run the command again:

0 measurements imported, 10 skipped, 0 failed (4 towers)

--reimport imports all files again (as additional measurements).

Evaluating the imported data

The imported data reproduce the tower evaluation. For the demo campaign:

import numpy as np
import groundmeas as gm

gm.connect_db("towers.db")
measurements, _ = gm.read_measurements_by(asset_type="overhead_line_tower")
tower8 = [m for m in measurements if m["location"]["name"] == "LX-01 tower 8"]
fop = next(m for m in tower8 if m["description"].startswith("Fall-of-potential"))
touch = next(m for m in tower8 if m["description"].startswith("Touch voltages"))

# earthing impedance with the 62 % method of the tower evaluation
z62 = gm.distance_profile_value(
    fop["id"], algorithm="62_percent", conservative=True, frequency_hz=50.0
)
print(round(z62["result_value"], 3))            # 0.121 = ZE_62_Ohm of the JSON result

# touch voltages scaled to the earth-fault current I_E = r * I_k
earth_current = 0.66 * 11_200                    # from grid_data.xlsx
items = [i for i in touch["items"] if i["frequency_hz"] == 50.0]
reference = next(i["value"] for i in items if i["measurement_type"] == "earthing_current")
print([int(np.ceil(i["value"] * earth_current / reference))
       for i in items if i["measurement_type"] == "touch_voltage"])
# [133, 95, 127, 91, 43, 31] = UT_V of the JSON result

conservative=True applies the procedure of the tower evaluation (see The 62 % method) and gives the same value as ZE_62_Ohm; without it the plain 62 % interpolation of groundmeas is used. Other profile algorithms (maximum, minimum_gradient, minimum_stddev, inverse) are useful for a comparison, see Analytics.

Python API

import groundmeas as gm
from groundmeas.towers import import_campaign

gm.connect_db("towers.db")
records = import_campaign(
    "campaign-2026/config.json",
    voltage_level_kv=110,
    timezone="Europe/Berlin",
)
# one dict per file: line, tower, location, test, file, status, measurement_id, message

import_campaign(..., dry_run=True) needs no database connection. find_tower_files(folder) lists the files that belong to each tower.