Tower campaigns¶
Evaluate earthing measurements of overhead-line towers.
gm-cli towers turns the raw files of an earthing measurement campaign into
an assessment of every tower and a ready-to-sign protocol:
- reads OMICRON COMPANO 100 fall-of-potential exports (XML) and OMICRON HGT1 touch-voltage reports (text),
- determines the earthing impedance with the 62 % method, the footing resistance, the touch voltages at the earth-fault current and the step-voltage profile,
- derives the fault current per tower from a short-circuit line model and the fault clearing time from the position of the tower on the line,
- checks every tower against the permissible touch voltage (EN 50522 / EN 50341) and classifies it,
- writes a JSON file per tower, an Excel summary, HTML/PDF protocols (English or German), a ZIP archive and an optional statistics report over all towers,
- copies the instrument data into the groundmeas database on request
(
gm-cli towers import-db), where the dashboard, the map and all analytics of groundmeas are available.
The tower workflow was developed as the separate package
tower-grounding-measurement and is part of groundmeas since 2026-10; see
Migration if you used the old package.
-
Generate a synthetic demo campaign and evaluate it in two commands.
-
File names, Excel workbooks and the configuration of a real campaign.
-
One location per tower, one measurement per test – for the dashboard and the groundmeas analytics.
-
Fall-of-potential method, touch voltage, permissible limits and the short-circuit model.
At a glance¶
$ pip install "groundmeas[pdf]"
$ gm-cli towers install-browser # once, for PDF protocols
$ gm-cli towers demo demo
$ gm-cli towers run --config demo/config.json
The last command evaluates all towers (--calc), draws the diagrams and
prints one protocol per tower (--print) and packs the PDF files into one
archive (--zip).
flowchart LR
subgraph Inputs
XML["COMPANO 100 XML<br/>ZE_<line>_<tower>.xml"]
TXT["HGT1 report<br/>UT_<line>_<tower>.txt"]
XLS["Excel workbooks<br/>grid data · description · short circuit"]
CFG["config.json"]
end
XML & TXT & XLS & CFG --> CALC["--calc<br/>evaluation"]
CALC --> JSON["JSON per tower"] & SUM["summary.xlsx"]
JSON --> PRINT["--print<br/>diagrams + protocol"] --> PDF["HTML / PDF"]
PDF --> ZIP["--zip<br/>protocols.zip"]
JSON --> STATS["--stats<br/>statistics report"]
XML & TXT --> DB["import-db<br/>groundmeas database"]
Installation¶
The tower workflow is part of every groundmeas installation. Only the PDF protocols need an extra:
$ pip install "groundmeas[pdf]" # adds Playwright
$ gm-cli towers install-browser # downloads Playwright's Chromium (~150 MB)
install-browser runs python -m playwright install chromium with the Python
interpreter of the installation, so it also works for isolated installations
(pipx, uv tool). Behind a restrictive proxy the download may fail; an
installed Google Chrome or Microsoft Edge is then used automatically,
or name a Chromium-based browser in the environment variable
GROUNDMEAS_BROWSER (a Playwright channel such as chrome or msedge, or the
path of an executable). Without any browser, --no-pdf writes the protocols
as HTML.
Linux
Playwright's Chromium needs a few system libraries. On Debian/Ubuntu
install them together with the browser:
python -m playwright install --with-deps chromium (as root).
Scope and limitations¶
The tool supports the engineer who assesses the measurements; it does not replace the assessment. Check in particular
- the permissible touch-voltage curve in the configuration against the edition of EN 50522 / EN 50341 and the national annex you apply,
- the fault currents, reduction factors and clearing times, which come from your grid data and protection settings,
- the plausibility of every measurement (the protocols show the complete profiles for this purpose).
See Physical background for the model assumptions.