A campaign is described by one JSON file, usually config.json next to the data. Start from the demo (gm-cli towers demo DIR) or write an annotated example with

$ gm-cli towers example-config campaign-2026/config.json

Which file is used

  1. the path given with --config PATH,
  2. otherwise the file named in the environment variable GROUNDMEAS_TOWER_CONFIG (the former name TOWER_GROUNDING_CONFIG is still read),
  3. otherwise config.json in the current working directory.

Paths

Every path may be

  • relative to the folder of the configuration file (recommended – the campaign folder can then be moved, synchronised or opened on another operating system without changes),
  • absolute (/home/me/data, C:/Data or C:\\Data in JSON),
  • written with ~ for the home folder or with environment variables ($HOME, ${DATA}, %USERPROFILE%).

Files are read as UTF-8; a byte-order mark written by Windows editors is accepted.

Complete example

{
    "language": "en",
    "logo": "logo.png",
    "nominal_frequency_Hz": 50,
    "touch_voltages": {
        "t_s":        [0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0, 10.0],
        "U_TP_V":     [633, 528, 410, 300, 204, 170, 140, 130, 120, 107, 80],
        "U_TP_ext_V": [1878, 1561, 1270, 831, 538, 397, 327, 287, 260, 244, 80]
    },
    "directory": {
        "path_measurements": "measurements",
        "path_grid_data": "grid_data.xlsx",
        "sc_current_data_path": "short_circuit_data.xlsx",
        "measurement_description_path": "measurement_description.xlsx",
        "json_export_path": "results",
        "path_summary": "results/summary.xlsx",
        "export_path_pdf": "results/protocols.zip",
        "grounding_impedance_structure": "PREFIX_LINENUMBER_TOWER"
    },
    "contacts": {
        "evaluation_first_name": "Alex",
        "evaluation_last_name": "Example",
        "evaluation_company": "Example Grid Operator"
    },
    "default_grid_data": {
        "r": 0.66,
        "tripping_time": 0.4,
        "fault_current_kA": 12
    },
    "touch_voltage_evaluation": "with_resistor",
    "line_protection": {
        "enabled": true,
        "sheet_name": "Leitungsschutz"
    }
}

Keys starting with _ (for example _comment) are ignored and can hold notes. The unit of a value is given by the suffix of its key: _V volt, _s seconds, _kA kiloampere, _Hz hertz, _m metre.

Reference

General

Key Type Default Meaning
language "en" | "de" "en" language of protocols, diagrams, verdicts and hints
logo path "" image shown in the protocol header (PNG, JPG or SVG); empty for none
nominal_frequency_Hz number 50 power frequency the HGT1 readings are interpolated to (50 or 60 Hz)
touch_voltage_evaluation string "with_resistor" which HGT1 readings are assessed, see below

touch_voltage_evaluation

Value Readings used for the assessment
with_resistor termination 2x1k (body resistance + 1 kΩ for footwear/standing surface)
without_resistor termination 1k (body resistance only) – the stricter choice
all all readings

If the selected subset is empty (or the report has no termination column), all readings are used.

touch_voltages – permissible touch voltage

Key Type Meaning
t_s list of numbers fault durations in s
U_TP_V list of numbers permissible touch voltage \(U_{TP}\) in V for each duration (curve UD1, without additional resistances)
U_TP_ext_V list of numbers curve with additional resistances (UD2); validated and stored, not used for the assessment

The three lists must have the same length. Between two entries the value is interpolated linearly; a clearing time outside the table uses the nearest end value and logs a warning.

Check the curve

The example values are the ones used by the original project (curve names UD1/UD2 follow EN 50341); the last point (10 s → 80 V) covers long clearing times in compensated networks. They are not a normative reference: take the values from the edition of EN 50522 / EN 50341 and the national annex you apply – the assessment depends directly on this table.

directory – data and results

Key Required Meaning
path_measurements yes flat folder with all instrument files
path_grid_data yes grid-data workbook (rewritten by --calc)
measurement_description_path yes measurement-description workbook
sc_current_data_path no short-circuit workbook (one sheet per line, sheet Leitungsschutz)
json_export_path yes output folder for JSON files, protocols (html_files/) and statistics (Statistik/); created if missing
path_summary no Excel summary; default <json_export_path>/summary.xlsx
export_path_pdf no ZIP archive of the PDF protocols; default <json_export_path>/protocols.zip
grounding_impedance_structure no layout of the COMPANO file names: PREFIX_LINENUMBER_TOWER (default), LINENUMBER_TOWER or TOWER_LINENUMBER

The input paths must exist; otherwise the run stops with exit code 2 and names the missing path.

contacts – who evaluated the measurement

Key Meaning
evaluation_first_name, evaluation_last_name, evaluation_company shown in the signature block of the protocol and in the JSON (Auswertung_*)

The measuring engineer is taken from the measurement description (Name, Vorname, Firma).

default_grid_data – fallback values

Used for towers without values in the grid-data workbook and without short-circuit data.

Key Unit Default Meaning
r – 1.0 reduction factor of the earth wire
tripping_time s 0.4 fault clearing time
fault_current_kA kA 12 single-phase short-circuit current

Note

The defaults are deliberately conservative but generic. Set them to the values of your network; a reduction factor of 1.0 assumes that the whole fault current flows into the earth at the tower.

line_protection – position-dependent clearing time

Key Default Meaning
enabled false read the protection sheet of the short-circuit workbook
sheet_name "Leitungsschutz" name of that sheet

See Preparing a campaign for the sheet layout and Assessment procedure for the background.

Validation

The configuration is validated before anything is evaluated. Typical messages:

Message Cause
Configuration file not found: … wrong --config path or no config.json in the working directory
… is not valid JSON: … syntax error, e.g. a trailing comma or a single backslash in a Windows path
directory.path_measurements: directory does not exist: … path wrong or relative to the wrong folder
touch_voltages: the length of t_s (11) does not match … the lists of the curve differ in length
Unsupported language 'fr'; supported: en, de only en and de are available
logo: file does not exist: … the logo path is wrong