Configuration¶
A campaign is described by one JSON file, usually config.json next to the
data. Start from the demo (gm-cli towers demo DIR) or write an annotated
example with
Which file is used¶
- the path given with
--config PATH, - otherwise the file named in the environment variable
GROUNDMEAS_TOWER_CONFIG(the former nameTOWER_GROUNDING_CONFIGis still read), - otherwise
config.jsonin the current working directory.
Paths¶
Every path may be
- relative to the folder of the configuration file (recommended – the campaign folder can then be moved, synchronised or opened on another operating system without changes),
- absolute (
/home/me/data,C:/DataorC:\\Datain JSON), - written with
~for the home folder or with environment variables ($HOME,${DATA},%USERPROFILE%).
Files are read as UTF-8; a byte-order mark written by Windows editors is accepted.
Complete example¶
{
"language": "en",
"logo": "logo.png",
"nominal_frequency_Hz": 50,
"touch_voltages": {
"t_s": [0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1.0, 10.0],
"U_TP_V": [633, 528, 410, 300, 204, 170, 140, 130, 120, 107, 80],
"U_TP_ext_V": [1878, 1561, 1270, 831, 538, 397, 327, 287, 260, 244, 80]
},
"directory": {
"path_measurements": "measurements",
"path_grid_data": "grid_data.xlsx",
"sc_current_data_path": "short_circuit_data.xlsx",
"measurement_description_path": "measurement_description.xlsx",
"json_export_path": "results",
"path_summary": "results/summary.xlsx",
"export_path_pdf": "results/protocols.zip",
"grounding_impedance_structure": "PREFIX_LINENUMBER_TOWER"
},
"contacts": {
"evaluation_first_name": "Alex",
"evaluation_last_name": "Example",
"evaluation_company": "Example Grid Operator"
},
"default_grid_data": {
"r": 0.66,
"tripping_time": 0.4,
"fault_current_kA": 12
},
"touch_voltage_evaluation": "with_resistor",
"line_protection": {
"enabled": true,
"sheet_name": "Leitungsschutz"
}
}
Keys starting with _ (for example _comment) are ignored and can hold notes.
The unit of a value is given by the suffix of its key: _V volt, _s
seconds, _kA kiloampere, _Hz hertz, _m metre.
Reference¶
General¶
| Key | Type | Default | Meaning |
|---|---|---|---|
language |
"en" | "de" |
"en" |
language of protocols, diagrams, verdicts and hints |
logo |
path | "" |
image shown in the protocol header (PNG, JPG or SVG); empty for none |
nominal_frequency_Hz |
number | 50 |
power frequency the HGT1 readings are interpolated to (50 or 60 Hz) |
touch_voltage_evaluation |
string | "with_resistor" |
which HGT1 readings are assessed, see below |
touch_voltage_evaluation
| Value | Readings used for the assessment |
|---|---|
with_resistor |
termination 2x1k (body resistance + 1 kΩ for footwear/standing surface) |
without_resistor |
termination 1k (body resistance only) – the stricter choice |
all |
all readings |
If the selected subset is empty (or the report has no termination column), all readings are used.
touch_voltages – permissible touch voltage¶
| Key | Type | Meaning |
|---|---|---|
t_s |
list of numbers | fault durations in s |
U_TP_V |
list of numbers | permissible touch voltage \(U_{TP}\) in V for each duration (curve UD1, without additional resistances) |
U_TP_ext_V |
list of numbers | curve with additional resistances (UD2); validated and stored, not used for the assessment |
The three lists must have the same length. Between two entries the value is interpolated linearly; a clearing time outside the table uses the nearest end value and logs a warning.
Check the curve
The example values are the ones used by the original project (curve names UD1/UD2 follow EN 50341); the last point (10 s → 80 V) covers long clearing times in compensated networks. They are not a normative reference: take the values from the edition of EN 50522 / EN 50341 and the national annex you apply – the assessment depends directly on this table.
directory – data and results¶
| Key | Required | Meaning |
|---|---|---|
path_measurements |
yes | flat folder with all instrument files |
path_grid_data |
yes | grid-data workbook (rewritten by --calc) |
measurement_description_path |
yes | measurement-description workbook |
sc_current_data_path |
no | short-circuit workbook (one sheet per line, sheet Leitungsschutz) |
json_export_path |
yes | output folder for JSON files, protocols (html_files/) and statistics (Statistik/); created if missing |
path_summary |
no | Excel summary; default <json_export_path>/summary.xlsx |
export_path_pdf |
no | ZIP archive of the PDF protocols; default <json_export_path>/protocols.zip |
grounding_impedance_structure |
no | layout of the COMPANO file names: PREFIX_LINENUMBER_TOWER (default), LINENUMBER_TOWER or TOWER_LINENUMBER |
The input paths must exist; otherwise the run stops with exit code 2 and names the missing path.
contacts – who evaluated the measurement¶
| Key | Meaning |
|---|---|
evaluation_first_name, evaluation_last_name, evaluation_company |
shown in the signature block of the protocol and in the JSON (Auswertung_*) |
The measuring engineer is taken from the measurement description (Name,
Vorname, Firma).
default_grid_data – fallback values¶
Used for towers without values in the grid-data workbook and without short-circuit data.
| Key | Unit | Default | Meaning |
|---|---|---|---|
r |
– | 1.0 |
reduction factor of the earth wire |
tripping_time |
s | 0.4 |
fault clearing time |
fault_current_kA |
kA | 12 |
single-phase short-circuit current |
Note
The defaults are deliberately conservative but generic. Set them to the
values of your network; a reduction factor of 1.0 assumes that the whole
fault current flows into the earth at the tower.
line_protection – position-dependent clearing time¶
| Key | Default | Meaning |
|---|---|---|
enabled |
false |
read the protection sheet of the short-circuit workbook |
sheet_name |
"Leitungsschutz" |
name of that sheet |
See Preparing a campaign for the sheet layout and Assessment procedure for the background.
Validation¶
The configuration is validated before anything is evaluated. Typical messages:
| Message | Cause |
|---|---|
Configuration file not found: … |
wrong --config path or no config.json in the working directory |
… is not valid JSON: … |
syntax error, e.g. a trailing comma or a single backslash in a Windows path |
directory.path_measurements: directory does not exist: … |
path wrong or relative to the wrong folder |
touch_voltages: the length of t_s (11) does not match … |
the lists of the curve differ in length |
Unsupported language 'fr'; supported: en, de |
only en and de are available |
logo: file does not exist: … |
the logo path is wrong |