Troubleshooting

Run with -v for debug messages and with -q to see only warnings and errors. Every warning names the file or the tower it refers to.

Installation and PDF export

PDF export needs Playwright …

Playwright is an optional dependency of groundmeas. Install the extra with pip install "groundmeas[pdf]" (or pipx inject groundmeas playwright for a pipx installation), then run gm-cli towers install-browser. --no-pdf creates HTML protocols without Playwright.

No Chromium-based browser found for the PDF export

Install Playwright's Chromium with gm-cli towers install-browser. If the download is blocked, install Google Chrome or Microsoft Edge (used automatically) or point GROUNDMEAS_BROWSER to a Chromium-based browser. --no-pdf creates HTML protocols without any browser.

Playwright's Chromium does not start on Linux

The browser needs system libraries: python -m playwright install --with-deps chromium (Debian/Ubuntu, as root).

gm-cli: command not found

The scripts folder of your Python installation is not on the PATH. Use python -m groundmeas.ui.cli … or install with pipx, which takes care of the PATH.

Configuration

… is not valid JSON

Typical causes are a trailing comma after the last entry and single backslashes in Windows paths ("C:\Data" must be written "C:\\Data" or "C:/Data"). Relative paths avoid the problem.

directory.… does not exist

Relative paths are resolved against the folder of the configuration file, not against the current working directory.

Measurement files

Skipping file with unrecognised name: …

The XML file name does not follow the configured grounding_impedance_structure. Most often the line identifier contains an underscore (LX_01 instead of LX-01) or the file has a suffix (ZE_LX-01_8 (2).xml).

No HGT1 report for … / Skipping …: no touch-voltage (HGT1) data

The touch-voltage report must be named UT_<line>_<tower>.txt and lie in the same folder. Leading zeros and letter case are ignored.

… the measuring points of the description … differ from the HGT1 report

The HGT1 recorded location names that do not match Messpunkte_UT of the measurement description. The HGT1 names are used; correct the description if they are wrong.

… measuring points in the description for … readings; the list is repeated cyclically

Messpunkte_UT needs one entry per reading, or one entry per measuring point when every point was measured with and without additional resistor. Check the labels in the protocol.

Skipping …: no row in the measurement description

Line and tower of the file name were not found in the measurement description. Compare the spelling of the line identifier.

Footing-resistance profile of … not usable …

The profile of corrected currents is missing or has a different number of points than the impedance profile. The tower is evaluated without it; a high-frequency single value is shown if available.

Results

Cannot write …. The file is probably open in Excel

Close the summary or the grid-data workbook and run again.

Clearing time … is outside the touch-voltage table

The clearing time is shorter or longer than the table in touch_voltages. The value at the table end is used; extend the table (for example with 10 s → 80 V for compensated networks).

The protocol shows the wrong map

The map is searched as Map_<line>_<tower>.<ext> next to the JSON files first and then in the measurement folder. Remove outdated map images from the result folder.

No JSON files found … Run the calc step first. for --stats

The statistics are created from the JSON results; run --calc before --stats.

import-db: FAILED: no current-electrode distance … / no row in the measurement description

The profile of a tower is imported only with the distance of the current electrode (Entfernung_Hilfserder_m), and the files of a tower only if the measurement description has a row for it. Correct the description and run gm-cli towers import-db again (without --reimport): files that are already in the database are skipped, the failed ones are imported. --dry-run shows these problems without touching the database.

import-db: The measurement description … lacks the columns … / could not be read

The first worksheet must start with the header row and contain the columns Leitung, Mast and Entfernung_Hilfserder_m (a title row above the header is not supported). Nothing is imported in this case.

Reporting a problem

Please open an issue on GitHub with the command, the full output with -v, your operating system and the version (python -c "import groundmeas; print(groundmeas.__version__)"). Do not attach real measurement data; the demo campaign or a reduced, anonymised example is usually enough to reproduce a problem.