Everything gm-cli towers does is available as functions and classes, for example to evaluate single towers in a notebook, to run parameter studies or to integrate the evaluation into another tool. The most important names can be imported from groundmeas.towers (imported lazily, so the import is fast) and the instrument readers from groundmeas.instruments:

from groundmeas.instruments import (
    CompanoXMLReader,         # COMPANO 100 XML export
    Hgt1TXTReader,            # HGT1 StepTouch report
)
from groundmeas.towers import (
    GroundingSystemAnalysis,  # assessment of one tower
    LineModel,                # short-circuit current along a line
    LineProtectionTable,      # position-dependent clearing time
    calculate_summary,        # run --calc
    print_protocol,           # run --print
    zip_protocols,            # run --zip
    generate_asset_report,    # run --stats
    import_campaign,          # import-db
    write_demo_campaign,      # demo
    read_config,
)

Run the pipeline from Python

from groundmeas.towers import calculate_summary, print_protocol, zip_protocols

config = "demo/config.json"
summary = calculate_summary(config_path=config)                      # returns a DataFrame
print(summary[["Leitung", "Mast", "ZE_62", "UT", "UT_zulaessig_V", "UT_zu_hoch"]])
print_protocol(config_path=config, worker_count=2, print_pdf=False)  # HTML only
zip_protocols(config_path=config)
  Leitung Mast     ZE_62          UT  UT_zulaessig_V  UT_zu_hoch
0   LX-01    3  0.552489  419.879955           300.0        True
1   LX-01    8  0.120835   94.987200           633.0       False
2   LX-01   21  0.601578  309.824592           633.0       False
3   LX-01   37  0.351584  260.134875           300.0       False

With worker_count > 1 the protocols are printed in separate processes; in a script, put the calls under if __name__ == "__main__": (required by Python's spawn/forkserver start methods, the default on Windows, macOS and – since Python 3.14 – Linux).

Log messages go to the logger groundmeas (its sub-logger groundmeas.towers); enable them with logging.basicConfig(level=logging.INFO).

Evaluate a single tower

GroundingSystemAnalysis needs no configuration file when the touch-voltage curve and the evaluation mode are passed explicitly:

from groundmeas.instruments import CompanoXMLReader, Hgt1TXTReader
from groundmeas.towers import GroundingSystemAnalysis

impedance, footing = CompanoXMLReader(
    "demo/measurements/ZE_LX-01_8.xml"
).get_impedance_to_ground_dataframe()
touch = Hgt1TXTReader(
    "demo/measurements/UT_LX-01_8.txt", nominal_frequency=50
).get_touchvoltage_dataframe()

tower = GroundingSystemAnalysis(
    impedance_to_ground=impedance,
    touch_voltage=touch,
    fault_current=11_200,          # I_k in A
    fault_duration=0.1,            # t_F in s
    reduction_factor=0.66,         # r
    extended_resistance=False,
    residual_resistance=footing,
    current_probe_dist=100,        # D in m
    touch_voltage_curve={0.1: 633, 0.2: 528, 0.3: 410, 0.4: 300, 0.5: 204, 1.0: 107, 10.0: 80},
    touch_voltage_evaluation="with_resistor",
)
print(f"I_E     = {tower.earth_current:.0f} A")
print(f"U_TP    = {tower.permitted_touch_voltage:.0f} V")
print(f"Z_E,62  = {tower.grounding_impedance_62:.3f} Ohm (limit {tower.permitted_ground_impedance:.3f} Ohm)")
print(f"U_E     = {tower.earth_current * tower.grounding_impedance_62:.0f} V")
print(f"U_T,max = {tower.touch_voltage_max:.0f} V")
I_E     = 7392 A
U_TP    = 633 V
Z_E,62  = 0.121 Ohm (limit 0.171 Ohm)
U_E     = 893 V
U_T,max = 95 V

Useful attributes after the evaluation:

Attribute Meaning
earth_current \(I_E = r \cdot I_k\) in A
permitted_touch_voltage \(U_{TP}(t_F)\) in V
permitted_ground_impedance \(2\,U_{TP} / I_E\) in Ω
grounding_impedance_62, dist_62 assessed impedance and the 62 % distance
residual_resistance_62 footing resistance scaled to the 62 % point
touch_voltage data frame of the readings with CalculatedTouchVoltage (V at \(I_E\))
touch_voltage_max highest assessed touch voltage
impedance_to_high, touch_voltage_to_high results of the limit checks
step_voltage step voltage per metre along the profile

The category of the assessment follows from the two flags:

from groundmeas.towers.campaign import assessment_category

assessment_category(tower)  # 'ZE'

The 62 % value itself is computed by groundmeas.value_at_62_percent(..., conservative=True), the same function that distance_profile_value(..., algorithm="62_percent", conservative=True) uses for profiles stored in the database.

Short-circuit current along a line

import pandas as pd

from groundmeas.towers import LineModel

training = pd.DataFrame(
    {
        "Ik": [12.9, 11.0, 9.9, 9.6, 10.4],      # kA, from a network calculation
        "l": [0.0, 2.9, 5.85, 8.8, 11.7],       # km from the line start
        "Mast": [1, None, None, None, 40],      # first and last tower number
    }
)
model = LineModel()
model.training_data["LX-01"] = training         # or model.read_training_parameter(path, "LX-01")
model.train_curve_model("LX-01")
model.get_sc_current("LX-01", 21)               # 9.9 (kA)
model.curve_data["LX-01"]["type"]               # 'two_sided'

Position-dependent clearing time

import pandas as pd

from groundmeas.towers import LineProtectionTable

table = LineProtectionTable(
    pd.DataFrame(
        [{"Leitung": "LX-01", "Mast_Anfang": 1, "Mast_Ende": 40,
          "t_Schnellzeit_s": 0.1, "t_Endbereich_s": 0.4}]
    )
)
result = table.lookup("LX-01", "37")
result.tripping_time_s, round(result.position_percent, 1), result.zone   # (0.4, 92.3, 'Endbereich')
table.lookup("LX-01", "8").hint("en")
# 'Position 17.9 % of the line length: instantaneous tripping from both line ends (distance protection)'

Synthetic test data

groundmeas.towers.demo creates instrument files from physical models. They are useful for tests of your own tooling:

import numpy as np

from groundmeas.towers.demo import fall_of_potential_profile, write_compano_xml

distances = np.array([1, 2, 5, 10, 20, 30, 40, 50, 60, 65, 70], dtype=float)
profile = fall_of_potential_profile(distances, earthing_impedance_ohm=0.4, electrode_radius_m=3.0)
write_compano_xml("ZE_TEST_1.xml", distances, profile, footing_share=0.5)

Modules

Module Content
groundmeas.towers.analysis GroundingSystemAnalysis, LineModel, permitted_voltage_for_time
groundmeas.towers.line_protection LineProtectionTable
groundmeas.towers.campaign calculate_summary, assessment categories, grid-data handling
groundmeas.towers.config read_config, ConfigError, write_example_config, EXPORT_TEMPLATE
groundmeas.towers.files file discovery in the flat measurement folder (read_from_device)
groundmeas.towers.flatten plan_flatten, apply_flatten
groundmeas.towers.database import_campaign, find_tower_files, location_name
groundmeas.towers.protocol, .plots, .results, .pdf diagrams, HTML/PDF protocols, ZIP
groundmeas.towers.stats statistics report
groundmeas.towers.i18n, .naming, .paths texts (en/de), identifiers, paths
groundmeas.towers.demo synthetic demo campaign
groundmeas.instruments COMPANO 100 / HGT1 readers