Physical background¶
This page explains the physics behind the evaluation: why the earthing of an overhead-line tower is measured, how the instruments measure, and how the tool turns the readings into the quantities that are assessed. The decision rules themselves are summarised in Assessment procedure.
Why tower earthing matters¶
During a single-phase earth fault on an overhead line (for example a flashover across an insulator), the fault current flows from the phase conductor into the tower. Part of it returns through the earth wires (shield wires) to the neighbouring towers and substations, the rest – the earth current \(I_E\) – flows through the tower earthing into the soil:
\(I_k\) is the single-phase short-circuit current at the fault location and \(r\) the reduction factor of the earth wire (\(r = 1\) without earth wire; the better the earth wire conducts and couples to the phase conductor, the smaller \(r\)).
The earth current raises the potential of the tower and of the soil around it relative to remote earth. This earth potential rise is
with the earthing impedance \(Z_E\) of the tower. A person touching the tower while standing on the soil a metre away bridges a part of \(U_E\), the touch voltage \(U_T\); a person walking near the tower bridges the step voltage \(U_S\) between the feet. Because the soil potential drops with the distance to the tower, \(U_T\) is always a fraction of \(U_E\).
The permissible touch voltage depends on how long the current flows through the body, i.e. on the fault clearing time \(t_F\) of the protection (see below).
Measuring the earthing impedance¶
The fall-of-potential method¶
The OMICRON COMPANO 100 injects a test current \(I\) between the tower earthing and an auxiliary current electrode placed at a distance \(D\) (typically 100 m or more). A potential probe is moved step by step from the tower towards the current electrode; at every distance \(x\) the instrument records the voltage \(U(x)\) between tower and probe. The ratio
is the fall-of-potential profile. To suppress interference from the power-frequency stray currents in the soil, the measurement is made at frequencies next to the power frequency (for example 30 Hz and 70 Hz).
Close to the tower \(Z(x)\) rises steeply, far from both electrodes it flattens (the probe is "at remote earth" with respect to the tower), and near the current electrode it rises again. The earthing impedance is the value of the flat part – which, for a finite distance \(D\), has to be identified carefully.
The 62 % method¶
For a hemispherical electrode of radius \(a\) in homogeneous soil of resistivity \(\rho\) the potential at a distance \(p\) from its centre is \(\varphi(p) = \rho I / (2 \pi p)\). With the return current \(-I\) at the current electrode (distance \(D\) from the centre) the probe at distance \(p\) measures
where \(R = \rho / (2 \pi a)\) is the true earthing resistance. \(Z(p)\) equals \(R\) when the two "error terms" cancel:
This is the classical 62 % rule (Curdts 1958, Tagg 1964): the true resistance is read with the potential probe at 61.8 % of the distance to the current electrode, measured from the electrical centre of the earthing system.
The tool evaluates every profile as follows
(GroundingSystemAnalysis.get_62_percentage_value):
- \(d_{62} = 0.62 \cdot D\), with \(D\) the distance tower – current electrode
from the measurement description (
Entfernung_Hilfserder_m). - \(Z(d_{62})\) is interpolated linearly between the three measuring points closest to \(d_{62}\) (extrapolated if \(d_{62}\) lies outside the measured range).
- Conservative corrections handle profiles that do not look like the
textbook curve:
- the profile ends before \(d_{62}\) and its maximum is higher → the maximum is used;
- a point closer to the tower than \(d_{62}\) shows a higher impedance → that higher value is used;
- the profile starts after \(d_{62}\) (all probes farther away) and the extrapolated value is lower than the value at the first probe → that value is used (the extrapolation could otherwise even become negative).
Repeated probe distances are merged into their highest reading before the interpolation. 4. The result is \(Z_{E,62}\), the earthing impedance used for the assessment.
The same procedure is available as the pure function
groundmeas.value_at_62_percent(distances, values, D, conservative=True) and
for profiles stored in the database as
distance_profile_value(..., algorithm="62_percent", conservative=True).
Without conservative=True groundmeas interpolates between the three nearest
points without extrapolation (the end value is kept) and without the
corrections of step 3.
Check with the analytical model
The synthetic demo profiles are generated from the formula above, with the probe distances measured from the electrode surface (radius 1.5 m to 2.5 m). The 62 % evaluation reproduces the true values with a small deviation to the safe side, because 62 % of \(D\) from the surface lies slightly beyond the exact 61.8 % point from the centre:
| Tower | true \(R\) | \(Z_{E,62}\) | deviation |
|---|---|---|---|
| 3 | 0.550 Ω | 0.552 Ω | +0.5 % |
| 8 | 0.120 Ω | 0.121 Ω | +0.7 % |
| 21 | 0.600 Ω | 0.602 Ω | +0.3 % |
| 37 | 0.350 Ω | 0.352 Ω | +0.5 % |
The test suite compares the method in addition with a least-squares fit of the hemisphere model and with the exact 61.8 % point.
Earthing impedance and footing resistance¶
With the earth wires connected, the injected current divides: part of it flows into the soil at the tower, the rest flows through the earth wires to the neighbouring towers. The COMPANO export therefore contains two currents:
- the raw output current – the total injected current. \(Z = U / I_{raw}\) is the earthing impedance \(Z_E\) of the tower including the earth-wire chain, i.e. the impedance that determines the earth potential rise during a fault;
- the corrected output current – the share that flows into the tower footing. \(R_A = U / I_{corr}\) is the footing resistance of the tower alone, an indicator of the condition of the tower's own earthing.
The footing resistance at the 62 % point is obtained by scaling the maximum footing resistance with the ratio of the impedances, \(R_{A,62} = R_{A,max} \cdot Z_{E,62} / Z_{E,max}\).
The footing resistance can also be measured with a high-frequency earth tester, whose high test frequency decouples the neighbouring towers through the inductance of the earth wire. If such a single value is given in the measurement description and deviates by more than 20 % from the fall-of-potential value (or if there is no profile), the protocol shows the high-frequency value and says so. The footing resistance is reported, not assessed.
Touch voltage¶
Measurement¶
While the COMPANO injects its test current \(I_{meas}\) into the tower, the OMICRON HGT1 measures the voltage between the tower (or another touchable object: fence, gate, street light) and a test electrode placed 1 m away on the soil. The HGT1 measures frequency-selectively at the two test frequencies \(f_1\) and \(f_2\) and loads the measurement with a defined resistance (termination):
1k– 1 kΩ, representing the body impedance,2x1k– 1 kΩ plus an additional 1 kΩ in series, representing footwear and standing surface.
The value at the nominal frequency \(f_n\) (50 Hz or 60 Hz) is interpolated linearly:
Scaling to the earth-fault current¶
The earthing system is linear: voltages scale with the injected current. The touch voltage expected during an earth fault is therefore
with \(I_{meas}\) the mean measuring current of the step/touch test from the COMPANO export. The tool rounds the result up to whole volts.
The same scaling is applied to voltages measured at a neighbouring tower
(UT_<line>_<tower>-<neighbour>.txt): they show how much of the earth
potential rise is transferred along the earth wire.
Permissible touch voltage¶
The permissible touch voltage \(U_{TP}\) is derived from the current that the human body tolerates for a given duration without ventricular fibrillation (IEC/TS 60479-1) and the body impedance. It decreases steeply with the duration of the current flow, which equals the fault clearing time \(t_F\). The standards for high-voltage installations (EN 50522) and overhead lines (EN 50341-1) give it as a curve over \(t_F\); the tool reads the curve as a table from the configuration and interpolates linearly between its points.
Step voltage¶
The step voltage over one metre is approximated from the slope of the fall-of-potential profile, scaled to the earth current:
with \(x_0 = 0\) and \(Z(0) = 0\) at the tower; the value at the last point is extrapolated linearly from the two preceding slopes. The step voltage is shown for information. It is not assessed, because the permissible step voltages are considerably higher than the touch voltages (the current path from foot to foot does not cross the heart).
Short-circuit current along the line¶
The single-phase short-circuit current depends on the fault location. For a line fed from both ends it is modelled as the sum of the contributions of both sources:
| Symbol | Meaning |
|---|---|
| \(x\) | tower index from the line start (0 … N−1) |
| \(N\) | number of towers |
| \(l\) | mean span length (line length / (N − 1)) |
| \(a\) | driving voltage (fit parameter) |
| \(b\) | line impedance per unit length (fit parameter) |
| \(c\), \(d\) | source impedances at both line ends (fit parameters) |
The four parameters are fitted with scipy.optimize.curve_fit to short-circuit
currents calculated with a network-calculation program for a few fault
locations (sheet per line in the short-circuit workbook). If the fit does not
converge, a straight line is used (one-sided infeed) and a warning is logged.
The model is a smooth interpolation between calculated values; it is only as
good as the network calculation behind it.
Fault clearing time along the line¶
Earth faults on lines in solidly or low-impedance earthed networks are cleared by distance protection at both line ends. Zone 1 of each relay covers about 80–85 % of the line and trips without intentional delay; faults beyond it are cleared by the delayed zone 2. A fault in the middle section is therefore cleared quickly from both ends, a fault near one end only after the remote relay's zone-2 delay. The tool assigns
| Position on the line | Clearing time |
|---|---|
| < 16 % | end-zone time t_Endbereich_s (e.g. 0.4 s) |
| 16 % … 84 % | instantaneous time t_Schnellzeit_s (e.g. 0.1 s) |
| > 84 % | end-zone time |
with configurable limits per line. The position follows from the tower number, assuming uniform spans. Positions between the integer limits are assigned to the end zone (the longer time is the conservative choice).
Soil resistivity¶
Some towers are measured with a Schlumberger array: four electrodes on a line, current injected through the outer pair, voltage measured with the inner pair, for increasing electrode spacings. The COMPANO reports the apparent soil resistivity \(\rho_a\) for every spacing directly; the tool copies the values and the electrode distances into the JSON file. Increasing \(\rho_a\) with increasing spacing indicates that deeper layers have a higher resistivity.
Assumptions and limitations¶
- Linearity. Scaling the measured values to the fault current assumes a linear earthing system (no soil ionisation, no saturation).
- 62 % rule. The rule is exact for a compact electrode in homogeneous
soil with the potential probe on the straight line towards the current
electrode. The angle between probe and current electrode is recorded
(
Winkel_Sonde_Hilfserder_grad) but not used in the calculation. In layered soil, for extended earthing systems or with too short distances the profile may have no plateau; the conservative corrections and the profile diagram in the protocol help to recognise such cases – check them. - Measuring current. The touch voltages are scaled with the mean measuring current of both test frequencies.
- Interpolation to 50/60 Hz is linear between the two test frequencies.
- Short-circuit currents, reduction factors and clearing times are input data. The results are only as good as these values.
- Permissible touch voltage. The curve comes from the configuration; the tool does not check it against a particular edition of a standard.
References¶
- EN 50522:2010, Earthing of power installations exceeding 1 kV a.c.
- EN 50341-1:2012, Overhead electrical lines exceeding AC 1 kV – Part 1: General requirements – Common specifications, and its national normative aspects (EN 50341-2-x).
- IEC/TS 60479-1, Effects of current on human beings and livestock – Part 1: General aspects.
- IEEE Std 81-2012, IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System.
- E. B. Curdts, "Some of the fundamental aspects of ground resistance measurements", AIEE Transactions, Part I, vol. 77, 1958.
- G. F. Tagg, Earth Resistances, George Newnes, London, 1964.
- OMICRON electronics, user manuals of the COMPANO 100 and the HGT1.