Thermal limits of earthing conductors (IEC 60949 / IEC 60909-0)¶
Does an earthing conductor survive the fault current thermally? This is the equipment-integrity counterpart to the touch-voltage (person-safety) assessment.
- IEC 60909-0: thermally equivalent short-time current $I_{th} = I_{s,\mathrm{RMS}} \cdot \sqrt{m + n}$, with the heat factor $m$ of the decaying DC component and $n$ of the AC component.
- IEC 60949: admissible adiabatic current $I_{adm} = k \cdot S / \sqrt{t_k}$, with the material constant $k$ from the initial and final temperature.
The linear AC RMS shield currents are superposed by the solve as usual; the non-linear IEC 60909 factor is applied to that aggregate ($I_{th}$ is never superposed directly).
import groundinsight as gi
gi.IEC60949_MATERIALS
{'Cu': {'K': 226.0, 'beta': 234.5, 'theta_final_default_C': 300.0},
'Al': {'K': 148.0, 'beta': 228.0, 'theta_final_default_C': 300.0},
'Steel': {'K': 78.0, 'beta': 202.0, 'theta_final_default_C': 300.0}}
The material constant $k = K\sqrt{\ln\big((\theta_f+\beta)/(\theta_i+\beta)\big)}$ reproduces the tables of the standard:
print("Cu XLPE (90->250 C):", round(gi.iec60949_k("Cu", 90, 250), 1), "(table: 143)")
print("Cu PVC (70->160 C):", round(gi.iec60949_k("Cu", 70, 160), 1), "(table: 115)")
print("Al XLPE (90->250 C):", round(gi.iec60949_k("Al", 90, 250), 1), "(table: 94)")
Cu XLPE (90->250 C): 143.1 (table: 143) Cu PVC (70->160 C): 115.0 (table: 115) Al XLPE (90->250 C): 94.5 (table: 94)
A small network with a copper earthing conductor¶
Two 20 kV buses, a 5000 A earth fault, and a BranchType that carries the
conductor material, its cross-section and the initial and final temperatures
of the thermal check. The impedances are illustrative.
def build(cross_section_mm2):
net = gi.create_network(name="thermal", frequencies=[50.0])
bt = gi.BusType(name="b", system_type="s", voltage_level=20.0, impedance_formula="rho*0 + 0.5")
ct = gi.BranchType(name="c", grounding_conductor=True,
self_impedance_formula="(rho*0 + 0.25 + j*f*0.012)*l",
mutual_impedance_formula="(rho*0 + 0.05 + j*f*0.012)*l",
conductor_material="Cu", cross_section_mm2=cross_section_mm2,
theta_initial_C=20.0, theta_final_C=300.0)
for b in ["b1", "b2"]:
gi.create_bus(name=b, type=bt, network=net)
gi.create_branch(name="c1", type=ct, from_bus="b1", to_bus="b2", length=1.0, network=net)
gi.create_source(name="src", bus="b1", values={50.0: 5000.0}, network=net)
gi.create_fault(name="F", bus="b2", network=net)
gi.run_fault(net, fault="F")
return net
Check a 16 mm² conductor, fault duration 1 s, R/X = 0.1¶
t_k_s is the short-circuit duration in seconds; r_to_x the R/X ratio of
the source, from which the peak factor $\kappa$ and the DC heat factor $m$
follow.
net = build(cross_section_mm2=16.0)
df = gi.check_conductor_limits(net, "F", t_k_s=1.0, r_to_x=0.1)
df.select("branch_name", "I_s_rms_A", "kappa", "m", "n", "I_th_A", "k",
"I_admissible_A", "utilization", "within_limit")
| branch_name | I_s_rms_A | kappa | m | n | I_th_A | k | I_admissible_A | utilization | within_limit |
|---|---|---|---|---|---|---|---|---|---|
| str | f64 | f64 | f64 | f64 | f64 | f64 | f64 | f64 | bool |
| "c1" | 4360.986753 | 1.746002 | 0.034127 | 1.0 | 4434.775163 | 194.679146 | 3114.866339 | 1.423745 | false |
within_limit=False and utilization > 1 mean the conductor is thermally
undersized.
The same two numbers by hand, from the shield current of the solve and the formulas of the two standards:
import math
row = df.to_dicts()[0]
kappa = gi.kappa_from_r_to_x(0.1) # 1.02 + 0.98 exp(-3 R/X)
m = gi.iec60909_m(kappa, 50.0, 1.0) # DC heat factor
i_th = row["I_s_rms_A"] * math.sqrt(m + 1.0) # n = 1, far from generators
k = gi.iec60949_k("Cu", 20.0, 300.0)
i_adm = k * 16.0 / math.sqrt(1.0)
print(f"kappa = {kappa:.6f} (1.02 + 0.98 e^-0.3 = {1.02 + 0.98 * math.exp(-0.3):.6f})")
print(f"I_th = {i_th:.1f} A check_conductor_limits: {row['I_th_A']:.1f} A")
print(f"I_adm = {i_adm:.1f} A check_conductor_limits: {row['I_admissible_A']:.1f} A")
kappa = 1.746002 (1.02 + 0.98 e^-0.3 = 1.746002) I_th = 4434.8 A check_conductor_limits: 4434.8 A I_adm = 3114.9 A check_conductor_limits: 3114.9 A
Increase the cross-section and the utilization drops below 1:
for S in [16.0, 50.0, 95.0, 240.0]:
r = gi.check_conductor_limits(build(S), "F", t_k_s=1.0, r_to_x=0.1).to_dicts()[0]
print(f"S={S:6.1f} mm^2 I_th={r['I_th_A']:7.0f} A I_adm={r['I_admissible_A']:8.0f} A "
f"util={r['utilization']:.2f} ok={r['within_limit']}")
S= 16.0 mm^2 I_th= 4435 A I_adm= 3115 A util=1.42 ok=False S= 50.0 mm^2 I_th= 4435 A I_adm= 9734 A util=0.46 ok=True S= 95.0 mm^2 I_th= 4435 A I_adm= 18495 A util=0.24 ok=True S= 240.0 mm^2 I_th= 4435 A I_adm= 46723 A util=0.09 ok=True
Fault duration matters (adiabatic ∝ 1/√t_k)¶
A longer clearing time lowers the admissible current, so the same conductor may fail; the DC heat factor $m$ falls at the same time, because the DC offset has decayed for a larger part of the fault:
for t_k in [0.1, 0.5, 1.0, 3.0]:
r = gi.check_conductor_limits(build(50.0), "F", t_k_s=t_k, r_to_x=0.1).to_dicts()[0]
print(f"t_k={t_k:4.1f} s m={r['m']:.3f} I_adm={r['I_admissible_A']:8.0f} A "
f"util={r['utilization']:.2f} ok={r['within_limit']}")
t_k= 0.1 s m=0.340 I_adm= 30781 A util=0.16 ok=True t_k= 0.5 s m=0.068 I_adm= 13766 A util=0.33 ok=True t_k= 1.0 s m=0.034 I_adm= 9734 A util=0.46 ok=True t_k= 3.0 s m=0.011 I_adm= 5620 A util=0.78 ok=True
Notes¶
kappa(peak factor) comes fromr_to_xvia $1.02 + 0.98\,e^{-3R/X}$, or is passed directly.n = 1is the far-from-generator default (distribution earthing); passn_factorotherwise.gi.check_node_limitschecks the earthing conductor and the electrode of every bus in the same way, andgi.read_shortcircuit_resultstakes $\kappa$ and the short-circuit current from a pandapowercalc_scrun (Analysis, I/O).- The check is adiabatic: the heat given off during the fault is neglected, which underestimates the admissible current and is on the safe side (Standards and scope).
References: IEC 60909-0:2016, IEC 60949:1988, IEC 60364-5-54, EN 50522.