Glossary and symbols¶
One line per symbol or term, with the field or column where groundinsight
reports it. The symbols follow EN 50522 where the standard has one.
Z_B and Z_E are two different impedances
The impedance of a single bus electrode to remote earth is Z_B, never
Z_E. Z_E is the earthing impedance of EN 50522: the driving-point
impedance of the whole earthing network at the fault location, the
electrodes bonded through cable screens and earth wires included. In a
cable network it is well below the electrode of the faulted station.
Quantities at the fault¶
| Symbol or term | Meaning | In groundinsight |
|---|---|---|
| EPR | earth potential rise: the potential of an earthing system against remote earth | ResultBus.uepr, uepr_freq; column EPR_V of res_buses() |
U_E |
earth potential rise of the earthing system at the fault location (EN 50522) | ResultReductionFactor.u_earthing, equal to the uepr_freq of the fault bus |
Z_E |
earthing impedance of EN 50522: the driving-point impedance of the earthing network at the fault bus (electrodes and shields, without coupling and without Thévenin loops) | ResultReductionFactor.z_earthing, ResultGroundingImpedance.value |
Z_G |
the name of Z_E in the result tables (grounding impedance) |
columns grounding_impedance_Ohm, grounding_impedance_deg of res_all_impedances() |
Z_dp |
driving-point impedance: the voltage at a bus per ampere injected there against remote earth | Z_E is Z_dp at the fault bus; gi.bus_response, gi.analyze_cuts |
I_F, 3I_0 |
fault current, the earth-fault current 3I_0 of EN 50522: the scaled source currents that reach the fault |
ResultReductionFactor.i_fault |
I_E |
earth current: the part of the fault current that returns through the soil, summed over the electrodes of the earth group | ResultReductionFactor.i_earth |
| earth group | the buses whose electrodes feed the soil, from the fault outwards up to where the potential profile turns | ResultReductionFactor.earth_buses |
r |
reduction factor of EN 50522, the earth current over the fault current | ResultReductionFactor.value_current; column reduction_factor_current |
value |
EPR ratio at the fault bus with and without the inductive coupling; for a single line the magnitude of 1 − k, whatever the electrodes |
ResultReductionFactor.value; column reduction_factor |
U_T, U_vT |
touch voltage and prospective touch voltage | not computed; U_E is their upper bound |
U_Tp |
permissible touch voltage of EN 50522, a function of the fault duration | not part of the package |
t_F |
fault duration, set by the protection; the argument of U_Tp |
not used by the stationary solve |
T_k |
short-circuit duration of IEC 60909-0, used by the thermal checks | Fault.t_k_s |
Impedances of the model¶
| Symbol or term | Meaning | In groundinsight |
|---|---|---|
Z_B |
impedance of the electrode of one bus (Erder) to remote earth | BusType.impedance_formula, Bus.impedance |
Z_s |
self impedance of the shield–earth loop of a branch: cable screen or earth wire with earth return | BranchType.self_impedance_formula, Branch.self_impedance |
Z_m |
mutual impedance between the loop of the faulted phase and the shield–earth loop, both with earth return | BranchType.mutual_impedance_formula, Branch.mutual_impedance |
k |
coupling ratio Z_m/Z_s; the shield carries k times the phase current when both ends are ideally bonded |
– |
Z_pp |
self impedance of the phase–earth loop | – |
Z_red |
phase–earth loop impedance with the shield bonded at both ends, Z_pp − Z_m²/Z_s; what the phase-current split needs |
BranchType.phase_impedance_formula, Branch.phase_impedance |
D_E |
equivalent earth-return depth of Carson's formula, 658·√(ρ/f) m |
the Carson formulas of the how-to on data sheets |
GMR |
geometric mean radius of a conductor or bundle | the radius in a Carson formula |
ρ (rho) |
specific earth resistance of the soil | specific_earth_resistance of buses and branches; formula symbol rho |
Conductors and terms¶
| Symbol or term | Meaning | In groundinsight |
|---|---|---|
| earthing conductor | the lumped connection (Erdungsleiter) that carries the current between the installation and the earthing system | ResultBus.i_inj; columns I_inj_A, I_inj_degree |
| earth electrode | the part in the soil (Erder); carries the current that leaves into the soil at this bus | ResultBus.ia; columns I_bus_A, I_bus_degree |
| shield, screen | metallic screen of a cable, the earthing conductor of a cable branch | a branch with grounding_conductor=True |
| earth wire | conductor of an overhead line that bonds the towers to the stations | a branch with grounding_conductor=True |
| RMS | root mean square; every phasor of the stationary model is an RMS phasor, and the RMS rows combine the frequencies as the root of the summed squares | column is_rms |
| grounding, earthing | the same thing; result names use "grounding", the EN 50522 terms "earthing" | – |