Formula syntax¶
Bus and branch types describe their impedances with formula strings. A formula is evaluated once per network frequency and per element, with the element's own soil resistivity and, for a branch, its length. This page lists what a formula may contain, the limits the formula guard enforces, why that guard exists, and the messages you get when a formula is refused.
How to derive a formula from a cable or electrode data sheet is the subject of the how-to Bus and branch types from data sheets.
Where formulas appear¶
| Type | Field | Unit of the result | Used by |
|---|---|---|---|
BusType |
impedance_formula |
Ω | the frequency-domain solve |
BusType |
R_formula, L_formula, C_formula |
Ω, H, F | the transient solvers only |
BranchType |
self_impedance_formula |
Ω per branch | the solve (shield–earth loop Z_s) |
BranchType |
mutual_impedance_formula |
Ω per branch | the solve (phase–shield coupling Z_m) |
BranchType |
phase_impedance_formula |
Ω per branch | the phase-current split in rings and meshes (Z_red) |
BranchType |
R_self_formula, L_self_formula, C_self_formula, R_mutual_formula, M_mutual_formula |
Ω, H, F | the transient solvers only |
A branch formula gives the impedance of the whole branch: write a per-km
expression and multiply it by l.
Symbols¶
| Symbol | Meaning | Unit | Available in |
|---|---|---|---|
f |
frequency | Hz | bus and branch formulas |
rho |
specific earth resistance ρ of the element (specific_earth_resistance of the bus or branch) |
Ω·m | bus and branch formulas |
l |
branch length (Branch.length) |
km | only in branch formulas |
j, I |
imaginary unit | – | bus and branch formulas |
pi |
π | – | bus and branch formulas |
E |
Euler's number e | – | bus and branch formulas |
Any other name is rejected when the type is created. Names are
case-sensitive, and the message suggests the case-insensitive match when there
is one (L → l, Rho → rho). A bus has no length, so l in a bus
formula is rejected as well, with the hint that it is defined only in branch
formulas. Constants such as a screen radius are therefore written as numbers
into the formula; the how-to on data sheets builds those strings with a few
lines of Python.
Numbers and operators¶
- Numbers are decimal, with an optional exponent:
0.25,658,1.5e-3. Hexadecimal, octal and binary literals are refused. Write very small or very large factors with an exponent part,1e-15rather than10**-15. - The operators are
+,-,*,/,**and parentheses, plus the comma between the arguments of a call. Nothing else is accepted: no attribute access (.), indexing ([]), comparison, assignment,;,@, lambda or string literal. - Precedence is Python's:
**binds tighter than a leading minus, so-f**2is −(f²).
Functions¶
A name followed by ( must be one of these 28 functions. Every one of them is
a SymPy function that is translated to NumPy for the evaluation.
| Group | Functions |
|---|---|
| roots, exponential, logarithm | sqrt, exp, log, ln — log(x) is the natural logarithm, log(x, b) the logarithm to base b, ln is the same as log |
| complex numbers | Abs, abs (magnitude), re, im, arg, conjugate, sign |
| trigonometric | sin, cos, tan, asin, acos, atan, atan2 |
| hyperbolic | sinh, cosh, tanh, asinh, acosh, atanh |
| piecewise | Min, Max (at most three arguments each), floor, ceiling |
A formula is parsed by SymPy (sympify), compiled with lambdify and
evaluated for all network frequencies at once. A result may be complex. Where
the evaluation on the real axis returns NaN — the square root or logarithm of
a negative number — it is repeated on the complex plane, so
sqrt(1 - (f/40)**2) at 50 Hz is 0.75j, as SymPy defines it.
import groundinsight as gi
rod = gi.BusType(
name="rod 3 m", system_type="Station", voltage_level=20.0,
impedance_formula="rho/(2*pi*3.0)*(log(4*3.0/0.01) - 1)",
)
cable = gi.BranchType(
name="illustrative cable", grounding_conductor=True,
self_impedance_formula="(0.25 + j*2*pi*f*0.4e-3)*l",
mutual_impedance_formula="(j*2*pi*f*0.35e-3)*l",
)
net = gi.create_network(name="syntax", frequencies=[50.0, 250.0])
bus = gi.create_bus(name="A", type=rod, specific_earth_resistance=100.0, network=net)
print(bus.impedance[50.0]) # 32.31 Ohm, the same at 250 Hz: the formula has no f
The open end: "nan"¶
A formula string that is exactly nan — any case, surrounding whitespace
allowed — is not evaluated: it stands for an infinite impedance at every
frequency. Use it for an open end, for example the self impedance of a broken
shield. A formula that merely contains the three letters (resonance) is an
ordinary formula.
Direct current (f = 0)¶
0.0 is an ordinary network frequency. Several common formulas cannot be
evaluated at 0 Hz as written — Carson's f*log(658*sqrt(rho/f)/r) is
0·∞ there — and the evaluator decides by approaching 0 Hz on
1e-6, 1e-7, 1e-8 Hz:
- a finite limit (a removable singularity) is used as the value; a conductor then tends to its DC resistance;
- a growing sequence (a pole,
1/(j*2*pi*f*C)) is an open circuit; - a finite reactance that survives at 0 Hz (
0.25 + j*0.6) has no physical reading; the real part is used and aDCLimitWarningnames the formula; - a limit that is still moving over the last decade is used and announced by a
DCLimitWarning("converges only slowly") — unless the step shrinks at least five-fold per decade, which counts as converged however small the value is: anything linear infshrinks it ten-fold, Carson'spi**2*1e-4*fincluded, whilesqrt(f)(3.2-fold) andlog(f)(not at all) are reported; - a real part of −∞ —
log(f)with no factorfin front — is refused for a bus, a grounding conductor and a source impedance: it is the limit of a negative resistance, not an open circuit. A study that does not list 0 Hz never evaluates it there; a transient study always does.
The how-to on data sheets shows what this means for the Carson formulas
(At 0 Hz); the full treatment is
in Direct current (f = 0).
Why the guard exists¶
Formula strings reach sympy.sympify and sympy.lambdify, and both evaluate
Python. Formulas also travel inside files: a JSON project file, a SQLite
database, the import defaults of a colleague. Without a check, opening such a
file could run arbitrary code, or stall the machine with a short string such as
9**9999999, which SymPy would expand into millions of digits while it
parses. The guard therefore checks every formula before SymPy sees it, with
Python's own tokenizer: names, calls and operators against the whitelists
above, and the size of every number the formula can build against the limits
below. A string the tokenizer cannot split is refused rather than passed on.
Types are validated wherever they are created, so the same check runs when a
network is loaded from JSON or from a database.
Resource limits¶
| Limit | Value | Why |
|---|---|---|
| characters in a formula string | 4096 | an impedance formula is a handful of terms |
| digits of a number literal | 100 (decimal notation only) | SymPy computes with such a number exactly |
| exponent of a power | 12 (written out or computed; a power in the exponent is refused) | the exponent multiplies the size of an exact result |
| digits of an exact intermediate number | 10 000 | bounds nested powers and products of exact numbers |
digits of the integer built by floor/ceiling |
100 | SymPy evaluates the argument to every digit first |
argument of exp, sinh, cosh |
10100 in magnitude | the evaluation cost grows with the argument |
| terms (numbers, names, operations and calls) | 512 | SymPy simplifies the whole expression while parsing |
| function calls | 8 | SymPy simplifies every call while parsing |
| arguments of one call | 3 | Max and Min compare their arguments pairwise |
The longest formula in this documentation, the phase impedance of a three-phase cable system in the how-to on data sheets, has 213 characters, 99 terms, 6 calls and exponent 2.
Common errors¶
Mistakes caught when the type is created (the message excerpt is what
BranchType(..., self_impedance_formula=<formula>) reports):
| Formula | Message (excerpt) | Remedy |
|---|---|---|
rho*L |
uses the unknown symbol 'L' (did you mean 'l'?) |
names are case-sensitive |
x*l |
uses the unknown symbol 'x' |
write the value of x as a number |
10**-15*f |
uses the exponent -15 -- above the limit of 12 |
write 1e-15*f |
f**f**2 |
contains a nested exponentiation |
no power in an exponent |
eval(rho) |
calls 'eval', which is not an allowed function |
only the 28 functions above |
rho.real |
contains a disallowed operator '.' |
write re(rho) |
f == 50 |
contains a disallowed operator '==' |
use Min/Max/sign for case distinctions |
'1'*l |
must not contain string literals |
write the number without quotes |
0x10*l |
hexadecimal, octal or binary literal |
write 16*l |
Max(f, rho, l, 1)*l |
calls Max() with 4 arguments, above the limit of 3 |
nest: Max(Max(f, rho), Max(l, 1)) |
exp(1e101)*l |
evaluates exp() at an argument of up to about 1e101 |
rescale the argument |
sqrt(rho*l |
could not be tokenized |
close the parenthesis |
lambda: 1 |
contains a disallowed name 'lambda' |
formulas are expressions |
Values that are refused when an element is evaluated, here as the
impedance_formula of a bus in a 50 Hz network with ρ = 100 Ω·m:
| Bus formula | Message (excerpt) | Remedy |
|---|---|---|
0 |
It is exactly zero at 50 Hz |
an ideal earth is a small finite value, e.g. 1e-6 |
0.05*rho - 10 |
Its real part is negative |
the fit is used outside its range; check the lowest ρ |
A formula that evaluates to NaN at some frequency — 0/0, 0*log(0) away
from 0 Hz, a NaN parameter — is refused with a message that names the
formula, the frequency and the parameters. log(0) itself is −∞, and a real
part of −∞ is refused as well (at 0 Hz). Check a new
formula at the lowest ρ, the lowest frequency and the shortest length of the
model.
See also¶
- Conventions and units — units of
f,rho,l, RMS phasors. - Glossary — the symbols
Z_s,Z_m,Z_red,Z_B. - API:
BusType,BranchTypeandcheck_formula_symbols.