Outage and what-if studies

What happens to the earth potential rise when a cable is out of service, a ring is opened or a station is cut off? This guide takes elements out of service with gi.Outage, compares the scenarios with gi.run_outage_study and reads the comparison frames. The script is outage.py; its output is at the end of the page.

The example is a 20 kV ring: substation UW and three stations, bonded through the screens of the cable system of the data-sheet how-to (with its phase impedance, so the phase current divides over both halves of the ring), earth fault at S2.

cable_system = gi.BranchType(
    name="3x NA2XS(F)2Y 1x300RM/25 12/20 kV, trefoil",
    grounding_conductor=True,
    self_impedance_formula=(
        "(0.727/3 + pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272))*l"
    ),
    mutual_impedance_formula=(
        "(pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272))*l"
    ),
    phase_impedance_formula=(
        "((0.1 + pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.00806059))"
        " - (pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272))**2"
        "/(0.727/3 + pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272)))*l"
    ),
)
substation = gi.BusType(name="substation", system_type="Substation", voltage_level=20.0,
                        impedance_formula="0.5")
station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
                     impedance_formula="2*rho/(3*1.13*sqrt(100.0))")

FAULT_BUS = "S2"
net = gi.create_network(name="ring", frequencies=[50.0])
gi.create_bus(name="UW", type=substation, specific_earth_resistance=100.0, network=net)
for name in ("S1", "S2", "S3"):
    gi.create_bus(name=name, type=station, specific_earth_resistance=100.0, network=net)
for name, a, b in (("K1", "UW", "S1"), ("K2", "S1", "S2"), ("K3", "S2", "S3"), ("K4", "S3", "UW")):
    gi.create_branch(name=name, type=cable_system, from_bus=a, to_bus=b, length=1.2,
                     specific_earth_resistance=100.0, network=net)
gi.create_source(name="infeed", bus="UW", values={50.0: 1000.0}, network=net)
gi.create_fault(name="F", bus=FAULT_BUS, network=net)

Scenarios

A gi.Outage names the buses and branches to take out of service. While a scenario is solved their active flag is False: an inactive bus leaves the nodal system, an inactive branch carries no current — neither screen nor phase current — and induces no coupling. Nothing else changes, so scenarios need no copy of the network.

gi.run_outage_study(network, fault=..., scenarios=[...]) solves the base case (include_base=True, labelled base) and every scenario, and puts the elements back in service afterwards.

  • With on_error="raise" (the default) a scenario whose solve fails ends the study. With on_error="record" it is noted in OutageStudyResult.failures and the study goes on — the scenarios that disconnect something are often the interesting ones. The base case always raises, because every comparison needs it.
  • A scenario that islands the faulted station gives 0 V everywhere: no source reaches the fault any more, so no current flows. That is the answer, not an error (gi.check_network calls it FAULT_NOT_REACHED). Taking the faulted bus itself out leaves nothing to solve and fails.
  • progress= and should_cancel= report and stop a long study; a cancelled study restores the network to the state it had before.
SCENARIOS = [
    gi.Outage(name="K2 out", disabled_branches=["K2"]),
    gi.Outage(name="K4 out", disabled_branches=["K4"]),
    gi.Outage(name="S2 islanded", disabled_branches=["K2", "K3"]),
]
study = gi.run_outage_study(
    net, fault="F",
    scenarios=SCENARIOS + [gi.Outage(name="fault bus out", disabled_buses=[FAULT_BUS])],
    on_error="record",
)
compared = study.compare_buses()
at_fault_bus = compared.filter(
    (pl.col("bus_name") == FAULT_BUS) & (pl.col("frequency_Hz") == "RMS")
)

Reading the comparison

OutageStudyResult.compare_buses() and .compare_branches() return one row per element, frequency, scenario and metric (EPR_V and I_branch_A unless columns= names others), with value, the difference delta_vs_base to the reference scenario and the relative difference delta_pct_vs_base in per cent. Two things differ from the frames of a single solve:

  • frequency_Hz is text here — "50.0" for a frequency and "RMS" for the RMS row — because it is the key the scenarios are joined on. Filter with pl.col("frequency_Hz") == "RMS", not with is_rms, which these frames do not have.
  • delta_pct_vs_base is null where the reference value is 0 — a frequency the fault does not excite, a bus islanded in the reference scenario, an element without current. "Ten per cent of nothing" has no answer, and because the marker is null rather than NaN, Polars aggregations skip it. Rank by the absolute difference when a zero reference is possible.

against= compares with another scenario than the base case; the column suffix follows its label:

against_islanded = study.compare_buses(against="S2 islanded").filter(
    (pl.col("bus_name") == FAULT_BUS) & (pl.col("frequency_Hz") == "RMS")
    & (pl.col("scenario") == "K2 out")
).row(0, named=True)

Columns: Result tables.

One scenario by hand

outage_context — gi.outage_context(network, outage) — takes the elements out for the duration of a with block and restores them — and the network's path memo — on exit, also after an exception. Inside it, gi.solve returns the result without storing it, or gi.run_fault stores it as usual.

with gi.outage_context(net, gi.Outage(name="K2 out", disabled_branches=["K2"])):
    one_off = gi.solve(net, "F")  # the network itself stays untouched by solve
k2_out_epr = next(b.uepr for b in one_off.buses if b.name == FAULT_BUS)

Output

Output of outage.py
    scenario EPR S2 / V  delta / V delta / %
        base      231.9        0.0       0.0
      K2 out      447.7      215.7      93.0
      K4 out      369.4      137.5      59.3
 S2 islanded        0.0     -231.9    -100.0
K2 out against S2 islanded: delta = 447.7 V, delta / % = None
recorded failures: {'fault bus out': "Fault bus 'S2' is inactive or missing; cannot solve."}
outage_context, K2 out: EPR S2 = 447.7 V
out of service after the study: []

Opening the ring next to the fault (K2 out) almost doubles the earth potential rise at S2: the screens of only one side of the ring carry the current back. None is the null of the percentage column, because the islanded reference is 0 V. The test suite recomputes every scenario with the independent reference solver of the tests, with the same elements inactive.