Diagnostics, logging and warnings¶
A result can be correct and still need a remark: the phase current of a ring
was split with a proxy, a frequency was scaled by default, a reactance had no
meaning at 0 Hz. groundinsight delivers such remarks as diagnostics —
warnings with a stable code, a severity and the elements they concern — so a
script, a GUI or a server can act on them. This guide reads them from a
result, checks a network before solving, collects them around other calls,
makes them errors in a test run and switches on logging. The script is
diagnostics.py; its output is at the
end of the page. Every code is listed in
Warnings and diagnostics.
| Where the remark arises | How you get it |
|---|---|
| during a solve | Result.diagnostics of the result |
| before a solve | gi.check_network |
| around any other call | collecting() from groundinsight.diagnostics |
| as a Python warning | the warning filters, e.g. to make it an error |
| what the library does | logging, switched on with set_log_level |
Read the diagnostics of a result¶
gi.run_fault and gi.solve collect every package warning raised during the
run into Result.diagnostics, a list of gi.Diagnostic records:
| Field | Meaning |
|---|---|
code |
stable identifier such as PHASE_PROXY — branch on it, never on the message text |
severity |
info, warning or error |
category |
the warning class, e.g. ModelAssumptionWarning (a modelling assumption) or InputWarning (incomplete input) |
message |
the text a person reads |
elements |
the elements concerned, as (kind, name) pairs |
The records are kept even when the warnings themselves are filtered or shown
only once, so a result always carries its complete set; net.res_fault(fault)
counts them in n_diagnostics. The records are pydantic models:
model_dump() gives a JSON-ready dict.
In the example the cable type declares no phase_impedance_formula, so the
phase current of the ring is split with proxy impedances, and the result says
which branches that concerns (PHASE_PROXY):
station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
impedance_formula="2.0")
cable = gi.BranchType(name="cable without phase impedance", grounding_conductor=True,
self_impedance_formula="(0.2 + j*2*pi*f*1.2e-3)*l",
mutual_impedance_formula="(j*2*pi*f*1.0e-3)*l")
ring = gi.create_network(name="ring", frequencies=[50.0])
for name in ("S0", "S1", "S2", "S3"):
gi.create_bus(name=name, type=station, network=ring)
for name, a, b in (("K1", "S0", "S1"), ("K2", "S1", "S2"), ("K3", "S2", "S3"), ("K4", "S3", "S0")):
gi.create_branch(name=name, type=cable, from_bus=a, to_bus=b, length=1.0, network=ring)
gi.create_source(name="infeed", bus="S0", values={50.0: 1000.0}, network=ring)
gi.create_fault(name="F", bus="S2", network=ring)
result = gi.run_fault(ring, "F")
for record in result.diagnostics: # code, severity, category, message, elements
if record.code == "PHASE_PROXY":
proxy_branches = sorted(name for kind, name in record.elements if kind == "branch")
payload = json.dumps([record.model_dump() for record in result.diagnostics]) # for a front end
Check a network before solving¶
gi.check_network(net, fault=None) returns every problem of a network at once
as gi.Diagnostic records and never raises: error where run_fault would
raise or describe another network than the one you built (a branch or source
on a bus that does not exist is otherwise dropped without a word), warning
where the network solves but part of the input has no effect (ISOLATED_BUS,
SOURCE_FREQUENCY_GAP, …). The check neither assembles nor solves, so it is
cheap enough to run after every edit. Its topology checks — isolated buses,
earthing islands, whether a source reaches the fault — run only on a network
whose references are consistent: fix the reference errors first, then check
again. In the example the first check finds the unconnected bus
(ISOLATED_BUS); after a source on a bus that does not exist is added, the
check reports that error (SOURCE_UNKNOWN_BUS, which would make the solver
ignore the source) and holds back the topology checks until it is fixed.
gi.create_bus(name="X", type=station, network=ring) # no branch to it
first_check = gi.check_network(ring)
ring.sources["ghost"] = gi.Source(name="ghost", bus="nowhere", # as a hand-edited
values={50.0: 10.0}) # file could carry it
issues = gi.check_network(ring)
blocking = [d.code for d in issues if d.severity == "error"]
Collect warnings outside a solve¶
Creating elements, importing, the thermal checks and the transient solvers
raise their warnings directly. Collect them with
groundinsight.diagnostics.collecting(): inside the with block every
package warning is also recorded as a gi.Diagnostic. The collection belongs
to the current thread or asyncio task, so two runs in parallel never mix
their records.
with collecting() as records: # warnings raised outside a solve
gi.create_source(name="extra", bus="S1", values={50.0: 5.0, 150.0: 1.0}, network=ring)
Filter warnings, or make them errors¶
Diagnostics are ordinary Python warnings of the classes
gi.ModelAssumptionWarning, gi.InputWarning, gi.DCLimitWarning,
gi.TransientModelWarning and gi.NetworkFrequencyOrderWarning, all
subclasses of gi.GroundinsightWarning. The usual tools apply:
warnings.simplefilter("ignore", gi.InputWarning) silences a category on the
screen (the result still records it), warnings.simplefilter("error", ...)
turns it into an exception that carries code and elements, and on the
command line python -W error::groundinsight.ModelAssumptionWarning does the
same — useful in a test suite that must not accept a heuristic result.
del ring.sources["ghost"]
with warnings.catch_warnings():
warnings.simplefilter("error", gi.ModelAssumptionWarning) # e.g. in a CI job
try:
gi.run_fault(ring, "F")
except gi.ModelAssumptionWarning as raised:
strict_code = raised.code
Logging is opt-in¶
The library logs what it does — sessions, migrations, cache use, the summary
of a study — to the logger groundinsight, which has a NullHandler, so
nothing is printed unless you ask. Anything that qualifies a result is a
diagnostic, not a log line. gi.set_log_level("INFO") attaches a console
handler (repeated calls do not stack handlers); logging.captureWarnings(True)
routes the warnings into logging as well, as text — code and elements stay
with the records.
import groundinsight as gi
gi.set_log_level("INFO") # console output of the "groundinsight" logger
gi.set_log_level("WARNING") # quieter again
For a bug report, gi.show_versions() returns the versions of
groundinsight, Python, the platform and the companion packages.
In a GUI or a server¶
The service layer groundinsight.api hands the records to a front end as
DiagnosticDTO (code, severity, category, message and element references) in
every result DTO and in the report of the pre-flight check, unchanged. A
front end branches on code to choose an icon or a help text, highlights the
elements in its views and shows message as it is. See
Service layer and command line.
Output¶
result: PHASE_PROXY (warning, ModelAssumptionWarning)
proxy split on: ['K1', 'K2', 'K3', 'K4']
as JSON for a front end: 1 record(s)
check: warning ISOLATED_BUS [('bus', 'X')]
check again: error SOURCE_UNKNOWN_BUS [('source', 'ghost'), ('bus', 'nowhere')]
blocking: ['SOURCE_UNKNOWN_BUS']
collected: [('SOURCE_FREQUENCY_OUTSIDE_NETWORK', [('source', 'extra')])]
turned into an error: PHASE_PROXY
PHASE_PROXY names exactly the four branches of the ring; the test suite
finds the ring branches from the topology and compares.
SOURCE_FREQUENCY_OUTSIDE_NETWORK is raised when the source is created, not
by a solve, which is why it has to be collected.