The coupling between the faulted phase conductor and the shields is driven by the phase current in every branch. On a radial feeder that current is the source current on every branch between source and fault. In ring or meshed topologies a single source–fault pair yields multiple routes, and the source current has to be divided between them. This page explains how groundinsight divides it, what phase_impedance_formula must describe, when the result is exact, and what the legacy path-based mode does differently.

The phase-conductor network

The division is the default and is computed, not declared: run_fault(..., phase_current_mode="auto") solves a reduced phase-conductor network per source — the fault bus as reference node, the source current injected at the source bus — and reads the branch phase currents off that solution. The split then follows the topology and the conductor impedances, is independent of the order the branches were declared in, and needs no user input.

The solve runs on the galvanic component of the phase network that contains the fault bus; inactive branches and a phase conductor declared open (phase_impedance_formula="nan") are not part of it. A source that reaches the fault through the earthing network but has no phase-conductor connection to it cannot feed the fault; run_fault still injects its current into the earthing system — as if it returned entirely through soil and shields, which is conservative for its share — and says so with a ModelAssumptionWarning, code SOURCE_WITHOUT_PHASE_PATH.

What phase_impedance_formula describes

The phase impedance used for that solve comes from BranchType.phase_impedance_formula (symbols f, rho, l, same as the other formulas). It is optional, because in a network without cycles the split is fixed by the topology alone and the impedance value cannot change it.

Where it matters, it has to be the impedance the one-way model needs. Per branch, the phase conductor (voltage \(V\)) and the shield (potential \(u\)) obey, both loops with earth return and both currents in the same direction,

\[ \begin{pmatrix} V_a - V_b \\ u_a - u_b \end{pmatrix} = \begin{pmatrix} Z_{pp} & Z_m \\ Z_m & Z_s \end{pmatrix} \begin{pmatrix} I_p \\ I_s \end{pmatrix}. \]

Eliminating the shield current \(I_s\) gives

\[ (V_a - k\,u_a) - (V_b - k\,u_b) = Z_\text{red}\, I_p, \qquad Z_\text{red} = Z_{pp} - \frac{Z_m^2}{Z_s}, \qquad k = \frac{Z_m}{Z_s}. \]

phase_impedance_formula is therefore the phase–earth loop impedance with the shield bonded at both ends, \(Z_\text{red}\), for a branch with a grounding conductor, and the plain phase–earth loop impedance \(Z_{pp}\) for a branch without one. It is neither the positive-sequence impedance \(R_1 + jX_1\) nor the resistance of the conductor alone. Bus and branch types from data sheets computes \(Z_\text{red}\) for a real cable.

Without the formula: the proxy

Where cycles exist and the formula is missing, the solve falls back to a proxy — 1/Z_self for a branch with a grounding conductor, 1/length for one without — and says so once per solve with a ModelAssumptionWarning, code PHASE_PROXY, that names the branches. Those two quantities are not comparable, so the split between routes of different construction is then a heuristic. Declare the formula whenever the ring mixes cable and overhead line.

The warning is raised only where it means something: in a network without a cycle around the fault, the proxy cannot change the result, and it stays silent. A branch whose shield is broken (self_impedance_formula="nan") keeps its phase conductor in the phase network with the length proxy — a broken screen does not open the conductor next to it.

One-way coupling: when the split is exact

The model determines the phase currents first and lets them drive the shields afterwards; the shield currents do not act back on the split. The elimination above shows when that is exact. If \(k\) has the same value on every branch of a mesh, \(W = V - k\,u\) is a potential on that mesh, the phase network written in \(W\) no longer contains the shields, and the split it gives is the split of the fully coupled system. If \(k\) differs between the routes of a mesh, the term \((k_1 - k_2)(u_S - u_F)\) drives a circulating current that the one-way model does not see.

The example below makes this concrete (phase_split.py). A ring S – A – F – B – S is fed with 1 kA at S and faulted at F; route 1 is a cable (2 × 1.2 km), route 2 the same cable (homogeneous) or an overhead line with an earth wire (mixed, 2 × 1.5 km). The per-km values are illustrative 50 Hz values:

CABLE = {"zs": 0.29 + 0.625j, "zm": 0.049 + 0.625j, "zpp": 0.174 + 0.740j}
OVERHEAD_LINE = {"zs": 0.65 + 0.785j, "zm": 0.049 + 0.372j, "zpp": 0.355 + 0.759j}


def z_red(construction):
    """Phase-earth loop with the shield bonded at both ends: Z_pp - Z_m^2/Z_s."""
    return construction["zpp"] - construction["zm"] ** 2 / construction["zs"]


def per_km(z):
    """A per-km impedance at 50 Hz as a formula (reactance proportional to f)."""
    return f"({z.real!r} + {z.imag!r}*j*f/50)*l"
def ring(route_2, phase):
    """The ring S-A-F-B-S; ``phase`` is "Z_red", "Z_pp" or "proxy"."""
    net = gi.create_network(name=f"ring_{phase}", frequencies=[50.0])
    electrodes = {"S": "0.2", "A": "2.0", "F": "2.0",
                  "B": "15.0" if route_2 is OVERHEAD_LINE else "2.0"}
    for bus, z_b in electrodes.items():
        bus_type = gi.BusType(name=f"electrode_{bus}", system_type="MV",
                              voltage_level=20.0, impedance_formula=z_b)
        gi.create_bus(name=bus, type=bus_type, network=net)

    def branch_type(name, construction):
        phase_formula = {"Z_red": per_km(z_red(construction)),
                         "Z_pp": per_km(construction["zpp"]),
                         "proxy": None}[phase]
        return gi.BranchType(name=name, grounding_conductor=True,
                             self_impedance_formula=per_km(construction["zs"]),
                             mutual_impedance_formula=per_km(construction["zm"]),
                             phase_impedance_formula=phase_formula)

    route_1_type = branch_type("route_1", CABLE)
    route_2_type = branch_type("route_2", route_2)
    for name, a, b, kind, length in (("SA", "S", "A", route_1_type, 1.2),
                                     ("AF", "A", "F", route_1_type, 1.2),
                                     ("SB", "S", "B", route_2_type, 1.5),
                                     ("BF", "B", "F", route_2_type, 1.5)):
        gi.create_branch(name=name, type=kind, from_bus=a, to_bus=b, length=length,
                         network=net)
    gi.create_source(name="infeed", bus="S", values={50.0: 1000.0}, network=net)
    gi.create_fault(name="F1", bus="F", network=net)
    return net


def split(route_2, phase):
    """Phase current on route 1 in A: the current divider of the two routes.

    The proxy of a branch with a grounding conductor is its shield impedance.
    """
    per_km = {"Z_red": z_red, "Z_pp": lambda c: c["zpp"], "proxy": lambda c: c["zs"]}[phase]
    z_route_1 = per_km(CABLE) * 2 * 1.2
    z_route_2 = per_km(route_2) * 2 * 1.5
    return abs(1000.0 * z_route_2 / (z_route_1 + z_route_2))


def epr_at_fault(net):
    """EPR at the fault bus F in V."""
    with warnings.catch_warnings():
        # the proxy variant is announced by a ModelAssumptionWarning PHASE_PROXY
        warnings.simplefilter("ignore", gi.ModelAssumptionWarning)
        result = gi.run_fault(net, "F1")
    return abs(complex(next(b.uepr_freq[50.0] for b in result.buses if b.name == "F")))


TABLE = {
    (label, phase): (split(route_2, phase), epr_at_fault(ring(route_2, phase)))
    for label, route_2 in (("homogeneous", CABLE), ("mixed", OVERHEAD_LINE))
    for phase in ("Z_red", "Z_pp", "proxy")
}

The one-way model divides the source current between the two routes like a current divider of their phase impedances; split computes that share for route 1. The results against a fully coupled multi-conductor model — phase conductors, shields and electrodes solved as one system, the test oracle of the suite:

Ring phase_impedance_formula phase current, route 1 |EPR| at F coupled model
homogeneous Z_red 555.56 A 205.863 V 555.56 A, 205.863 V
homogeneous Z_pp 555.56 A 205.863 V
homogeneous proxy 555.56 A 205.863 V
mixed Z_red 728.39 A 310.735 V (+7.4 %) 764.90 A, 289.231 V
mixed Z_pp 582.47 A 298.635 V (+3.3 %)
mixed proxy 653.92 A 278.187 V (−3.8 %)

In the homogeneous ring all three choices give the coupled result — any phase impedance proportional to length divides the current in inverse proportion to the route lengths (3.0 km against 2.4 km: 555.56 A on route 1). In the mixed ring none is exact. Z_red is the quantity the elimination defines and gives the split closest to the coupled one; the smaller EPR error of the other two choices in this ring is a cancellation of a wrong split against the missing circulating current, not a better model. The size and the sign of the error depend on the network; it grows with the difference in \(k\) between the routes and is largest where a route without an earth wire (\(k = 0\)) runs parallel to a cable.

One phase conductor

The phase network contains the faulted conductor only. In a ring, the two healthy phases form closed loops as well, and the fault currents induce currents in them that couple back to the faulted phase and to the shields. The model does not represent them, and the size of the effect has not been quantified.

Enumerated paths and the legacy mode

Mutual-coupling injections require a direction. In the legacy phase_current_mode="paths" groundinsight derives that direction by enumerating every simple path from each source bus to the active fault bus via a depth-first search (PathFinder). Each path is stored as an ordered list of Branch objects; its injection signs follow the traversal order.

The enumeration is exponential in the number of loops

The number of simple paths grows exponentially with the number of independent loops, not with the number of buses: a 500-bus ring has two paths, a 5×5 grid 8 512 and a 6×6 grid 1 262 816 — roughly a minute of enumeration against milliseconds in the solver. The default phase_current_mode="auto" therefore does not enumerate: it only needs to know which sources reach the fault, and Network.sources_reaching(...) answers that with a breadth-first search. network.paths is empty after a default run_fault; call gi.create_paths on the network if you want the paths as data.

phase_current_mode="paths" selects the pre-0.6 behaviour: every branch on every enumerated path receives the full source current, scaled by that branch's parallel_coefficient. This is correct for a radial network — where both modes agree exactly — but in a meshed one it multiplies the current instead of dividing it. In a ring of two routes of the same construction, at the default coefficient of 1.0, the Norton injections add up to \((1-2k)\,I\) instead of \((1-k)\,I\). With \(Z_m = Z_s/2\) (\(k = 0.5\)) the symmetric ring then solves to EPR = 0 V at the fault, an EPR ratio value = 0 and no current-based factor at all (value_current is None: no current reaches the soil), because the doubled mutual injections cancel the source exactly. With the cable of the tutorials, \(\lvert 1-2k\rvert = 1\) and the EPR comes out as if the shields did not couple at all, 2.6 times the correct value (From a line to a ring). The earthing impedance \(Z_E\) is a property of the earthing network alone and does not change with the mode. The mode is kept so studies produced before 0.6.0 stay reproducible, and for networks where the split is known from measurement and set by hand. When a source reaches the fault over more than one path and the coefficients are still at their default, the mode says so (ModelAssumptionWarning, code PARALLEL_COEFFICIENT_DEFAULT).

The deprecated auto_parallel_coefficients argument still works and still wins when passed: True maps to "auto", False to "paths".

When there is no path

Two different situations both end in "no paths", and groundinsight treats them differently on purpose. No sources or no faults at all is rejected: the enumeration runs over sources × faults, so an empty side means nothing was ever asked, and the all-zero result that follows is an artefact of an incomplete model rather than a statement about the system. No path between an existing source and an existing fault is accepted: that is the signature of an islanded fault bus — the normal outcome of an outage scenario — and 0 V is then the physically correct answer.

See also

  • From a line to a ring — the tutorial: a symmetric ring, the phase impedance and the legacy mode.
  • Phase currents in meshes — the example notebook: a line, a ring, two parallel cables and a mesh in both modes, checked against a fully coupled multi-conductor solve; with the same \(k\) on every branch the split moves the shield currents but no earth potential.