Skip to content

Save, load and migrate

A network can be kept in two ways: as a project file — one network in one JSON file, to mail, to version or to open in the GUI — or in a SQLite database that holds a catalogue of bus and branch types and many networks. This guide uses both, migrates a database written by an earlier release and shows what happens to files from an untrusted source. The script is persistence.py; its output is at the end of the page.

station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
                     impedance_formula="2*rho/(3*1.13*sqrt(100.0))")
substation = gi.BusType(name="substation", system_type="Substation", voltage_level=20.0,
                        impedance_formula="0.5")
cable = gi.BranchType(name="cable", grounding_conductor=True,
                      self_impedance_formula="(0.2 + j*2*pi*f*1.2e-3)*l",
                      mutual_impedance_formula="(j*2*pi*f*1.0e-3)*l")
net = gi.create_network(name="Umspannwerk Süd", frequencies=[50.0, 250.0])
gi.create_bus(name="UW", type=substation, specific_earth_resistance=100.0, network=net)
gi.create_bus(name="S", type=station, specific_earth_resistance=100.0, network=net)
gi.create_branch(name="K", type=cable, from_bus="UW", to_bus="S", length=3.0, network=net)
gi.create_source(name="infeed", bus="UW", values={50.0: 1000.0, 250.0: 50.0}, network=net)
gi.create_fault(name="F", bus="S", scalings={50.0: 1.0, 250.0: 1.0}, network=net)
gi.run_fault(net, "F")

The project file

gi.save_network_to_json(network, path) writes the network — elements, types, frequencies and the stored results — as JSON, and gi.load_network_from_json(path) reads it back.

  • UTF-8 on every platform. Names with Ω, ρ or ü are stored the same on Windows, macOS and Linux. A file that is not UTF-8 — only 0.6.0 and earlier on a non-UTF-8 system wrote such files — is read with the platform encoding and announced (PROJECT_FILE_LEGACY_ENCODING); saving it again writes UTF-8.
  • Atomic. The file is written to a temporary file next to the target and then moved over it, so a failure leaves an existing project file intact.
  • Versioned. The file starts with schema_version (the version of the file layout) and groundinsight_version (the release that wrote it).
gi.save_network_to_json(net, "project.json")       # UTF-8, atomic, with schema_version
header = list(json.loads(Path("project.json").read_text(encoding="utf-8")))[:2]
from_json = gi.load_network_from_json("project.json")

Network.model_dump_json() and gi.Network.model_validate_json(text) remain available for a network embedded in your own file format; the project-file functions add the header, the encoding rules and the atomic write.

What is promised for old and new files

  • Files of every earlier release load. A project file without schema_version (0.6.0 and earlier) is read unchanged. A database is migrated to the current schema when it is opened, after a copy of the original is kept as <name>.db.bak. Results stored before the earthing voltage and impedance were redefined at the fault bus load with those quantities empty and an info record LEGACY_EARTHING_DEFINITION in Result.diagnostics; solve the fault again.
  • Files of a newer schema are refused with a ValueError that names both schema versions, instead of being read with whatever the newer release added silently dropped. Update groundinsight to open them.
newer = json.loads(Path("project.json").read_text(encoding="utf-8"))
newer["schema_version"] = 99                          # as if a later release wrote it
Path("from_the_future.json").write_text(json.dumps(newer), encoding="utf-8")
try:
    gi.load_network_from_json("from_the_future.json")
except ValueError as refused:
    newer_refused = str(refused).split(" (written")[0]

The database

gi.Database — gi.Database(path) — opens (or creates) a SQLite file and offers the operations as methods: save_bustype, load_bustypes, save_branchtype, load_branchtypes, save_network (with its types and stored results), load_network, list_networks, delete_network, and their counterparts for types. It is a context manager; every operation runs in a short-lived session of its own, and two Database objects on the same file share a lock, so a GUI or a server may use them from several threads. gi.Database(":memory:") gives a private in-memory database. The module-level helpers (gi.start_dbsession, gi.save_network_to_db, gi.load_network_from_db, …) work as before on a default Database; the old globals gi.session and gi.db_session still resolve but are deprecated. Details: Database API.

for old_file in ("library.db", "library.db.bak"):     # start from a fresh file
    Path(old_file).unlink(missing_ok=True)
with gi.Database("library.db") as db:
    db.save_bustype(station)                          # a reusable type catalogue
    db.save_branchtype(cable)
    db.save_network(net)                              # with its types and stored results
with gi.Database("library.db") as db:
    stored = db.list_networks()
    from_database = db.load_network("Umspannwerk Süd")

Migrate a database

needs_migration — gi.needs_migration(path) — classifies a file: "none" (current), "add_columns" (columns of a later release missing), "legacy_scoped" (elements keyed by name alone, up to 0.4.0) or "pickle_frequencies" (frequency lists stored with pickle, up to 0.6.0). migrate_database — gi.migrate_database(path, backup=True) — converts the file in place after copying it to .bak, and returns a gi.MigrationReport — migrated, kind, backup_path, the rows written, the columns added, and in needs_attention whether anything was filled in or left out that you should look at. gi.Database(path) does the same on opening (migrate=True, the default); with migrate=False the file stays untouched and its first use raises an error that names migrate().

connection = sqlite3.connect("library.db")            # simulate a file of an earlier release:
connection.execute("ALTER TABLE bus_types DROP COLUMN electrode_current_split")
connection.commit()
connection.close()

kind_before = gi.needs_migration("library.db")       # "add_columns"
report = gi.migrate_database("library.db")            # copies library.db to library.db.bak first
kind_after = gi.needs_migration("library.db")         # "none"
with gi.Database("library.db") as db:                 # Database(...) migrates on opening by default
    after_migration = db.load_network("Umspannwerk Süd")

The script simulates a file of an earlier release by removing a column that a later release added; a real file from 0.5.0 lacks exactly such columns.

Files from an untrusted source

A .db or .json file is shared like a document — mailed, checked into a repository, downloaded. Two properties keep opening one from running code:

  • The formula guard. Impedance formulas are parsed with SymPy, which evaluates Python. Every formula — typed, imported or loaded — passes the formula guard first: arithmetic over names and numbers, a fixed list of functions, and bounds on the size of numbers, exponents and terms; string literals, attribute access, other calls and dunder names are refused (Formula syntax).
  • No pickle. Databases store frequency lists as JSON. Files of 0.6.0 and earlier stored them with pickle; the migration converts them with an unpickler that resolves nothing but list, float and int, and aborts on anything else.

The guard bounds the work per formula, not the size of a file: a file with many types and elements still takes time to load. A server that opens files from strangers should do so in a worker process with a time limit; a session of the service layer also refuses files above its max_buses and max_branches on opening.

untrusted = json.loads(Path("project.json").read_text(encoding="utf-8"))
untrusted["buses"]["S"]["type"]["impedance_formula"] = "__import__('os').getcwd()"
Path("untrusted.json").write_text(json.dumps(untrusted), encoding="utf-8")
try:
    gi.load_network_from_json("untrusted.json")
except ValueError as refused:  # a pydantic ValidationError is a ValueError
    untrusted_refused = re.search(r"Impedance formula [^(]*", str(refused)).group(0).strip()

Output

Output of persistence.py
project file header: ['schema_version', 'groundinsight_version']
JSON round trip identical: True
newer schema: ValueError: 'from_the_future.json' uses project-file schema version 99
database holds: ['Umspannwerk Süd']
database round trip identical: True
migration: add_columns -> none, backup library.db.bak, added {'bus_types': ['electrode_current_split']}
after migration identical: True
stored EPR (RMS): {'UW': 44.46, 'S': 524.57}
untrusted formula refused: Impedance formula must not contain string literals or other non-arithmetic tokens

"Identical" compares the complete JSON serialisation of the network — every element, type, frequency and stored result — before saving and after loading.