Skip to content

Admissible soil resistivity (inverse rho / rho-f)

The forward question is "what earth potential rise does this soil give?". The inverse one is "how poor may the soil become before the earth potential rise exceeds the limit?" — the margin of an installation against seasonal or uncertain soil resistivity. This guide answers it with gi.find_max_rho_scaling and, for a fitted rho-f characteristic, with gi.find_max_rho_f_scaling. The script is inverse_rho.py; its output is at the end of the page.

The example is the 20 kV feeder of the EN 50522 how-to: earth fault at S3, 1000 A at 50 Hz and 50 A at 250 Hz, station electrodes of 5.90 Ω at ρ = 100 Ω·m.

cable_system = gi.BranchType(
    name="3x NA2XS(F)2Y 1x300RM/25 12/20 kV, trefoil",
    grounding_conductor=True,
    self_impedance_formula=(
        "(0.727/3 + pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272))*l"
    ),
    mutual_impedance_formula=(
        "(pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272))*l"
    ),
)
substation = gi.BusType(name="substation", system_type="Substation", voltage_level=20.0,
                        impedance_formula="0.5")
station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
                     impedance_formula="2*rho/(3*1.13*sqrt(100.0))")

STATIONS = ["S1", "S2", "S3", "S4", "S5"]
FAULT_BUS = "S3"
net = gi.create_network(name="feeder", frequencies=[50.0, 250.0])
gi.create_bus(name="UW", type=substation, specific_earth_resistance=100.0, network=net)
for name in STATIONS:
    gi.create_bus(name=name, type=station, specific_earth_resistance=100.0, network=net)
names = ["UW"] + STATIONS
for i, (a, b) in enumerate(zip(names[:-1], names[1:], strict=True), start=1):
    gi.create_branch(name=f"K{i}", type=cable_system, from_bus=a, to_bus=b, length=1.2,
                     specific_earth_resistance=100.0, network=net)
gi.create_source(name="infeed", bus="UW", values={50.0: 1000.0, 250.0: 50.0}, network=net)
gi.create_fault(name="F", bus=FAULT_BUS, scalings={50.0: 1.0, 250.0: 1.0}, network=net)

Choose the limit

u_limit is a limit on the earth potential rise at the fault bus, RMS over all frequencies — not the touch voltage. The earth potential rise U_E is an upper bound of the touch voltage; EN 50522 compares it with the permissible touch voltage U_Tp(t_F) of the fault duration in its design procedure, and that procedure (with the recognised measures M of the standard) says which value U_E may reach for your installation. Take u_limit from there: the procedure, the clauses and the treatment of harmonics are in Compare results with EN 50522 limits. The package contains no permissible values; the 500 V of the example are illustrative.

The largest admissible scaling of rho

gi.find_max_rho_scaling(network, fault, bus_names, u_limit) multiplies the specific_earth_resistance of every bus in bus_names by one factor c, evaluates the bus-type formulas again and finds by log-bisection over c_bounds (default (1e-3, 1e3)) the largest c whose RMS earth potential rise at the fault bus stays at or below u_limit.

  • Only the buses are scaled. The specific_earth_resistance of the branches — the soil in the earth-return terms of a Carson-type cable formula — stays as it is.
  • Before the bisection a scan of monotonicity_grid points (default 9) over c_bounds checks that the earth potential rise grows with c, which a bisection assumes; a formula whose reactance does not scale with ρ can turn, and the search then says so instead of returning a wrong maximum.
  • The network is left as it was, also when the search fails or is cancelled (should_cancel=); progress= reports every solve.
  • Every trial after the first one per fault location re-solves only the matrix values, bit for bit like a full run_fault, so a search costs little more than its first solve (see Large and meshed networks).
U_LIMIT_V = 500.0  # illustrative: the EPR limit your EN 50522 assessment sets

result = gi.find_max_rho_scaling(net, "F", bus_names=STATIONS, u_limit=U_LIMIT_V)
if not result["converged"]:
    raise RuntimeError(f"no maximum: {result['status']}, bracket {result['c_bracket']}")

Read the result

c_max is always a factor whose earth potential rise was computed and found admissible. Whether it is also the largest one depends on how the search ended — read converged (or status) before using it:

status converged What c_max means
"converged" True The bracket closed to within tol_rel; the threshold lies in c_bracket.
"bracket_within_tol_on_entry" True The bracket was narrower than tol_rel from the start; same guarantee.
"bracket_fully_admissible" False Every factor up to c_bounds[1] was admissible: c_max is that bound, a lower bound of the true maximum, and c_bracket is (c_hi, inf). Widen c_bounds.
"max_iter_reached" False The step cap ended the search; c_max is admissible but possibly far below the threshold. Raise max_iter.
"non_monotone" False The earth potential rise turns inside c_bounds; c_max is the largest admissible factor the scan measured, refined inside its interval — a lower bound.

c_bracket is the interval that provably contains the threshold, bracket_rel_width its relative width (compare it with tol_rel), rho_max the scaled resistivity per bus and u_epr_rms_at_c_max the earth potential rise at c_max. Do not branch on iterations: two different statuses can both end with zero steps.

A rho-f characteristic

When the electrodes are described by a fitted rho-f vector \(Z = k_1\rho + (k_2 + jk_3)f + (k_4 + jk_5)\rho f\) (the form groundfield exports), gi.find_max_rho_f_scaling(network, bus_names, u_limit, k_ref) scales the whole vector, \(k = c \cdot k_\text{ref}\), gives it to every bus of bus_names (evaluated with each bus's own ρ) and sweeps each of those buses as the fault location: an existing fault at the bus is used, otherwise a temporary one with fault_scalings (default 1.0) is created and removed again. It finds the largest c for which no swept bus exceeds u_limit, and returns k_max, max_epr_rms_at_c_max, epr_rms_per_bus_at_c_max and the same status, converged and c_bracket as above. gi.evaluate_max_epr_under_k evaluates one vector without a search, and gi.select_rho_f_from_catalog ranks a whole catalogue against the limit.

K_REF = (0.059, 0.0, 2e-4, 0.0, 1e-6)  # fitted rho-f vector of the station electrodes

rho_f = gi.find_max_rho_f_scaling(net, bus_names=STATIONS, u_limit=U_LIMIT_V, k_ref=K_REF)

Output

Output of inverse_rho.py
rho search: status = converged, converged = True
c_max = 1.6939, bracket = (1.6939, 1.6953), EPR at c_max = 500.0 V
rho_max at S3 = 169.4 Ohm*m
rho-f search: status = converged, c_max = 0.6127, k1_max = 0.03615 Ohm/(Ohm*m)
largest EPR at c_max: 499.8 V, fault at S5

The station electrodes may see 1.69 times the assumed resistivity before the earth potential rise at S3 reaches 500 V. The rho-f search is stricter because it also faults the other stations: with the fitted characteristic the station at the end of the feeder, S5, exceeds the limit first, so the characteristic may only be 0.61 times the fit. The test suite recomputes the earth potential rise at both ends of the bracket with the independent reference solver of the tests.