Transient studies

A real earth-fault current switches on, may carry a decaying DC offset and switches off again. This guide computes the earth potential rise and the screen currents over time with gi.TransientStudy, chooses between its two solvers and reads the warnings that come with them. The script is transient.py; its output is at the end of the page. The derivations of both solvers are in Transient simulation.

Choose the solver

solver="fft" solver="state_space"
model the stationary nodal system at every FFT bin, from the impedance formulas a state-space model from the lumped R/L/C fields, evaluated at one frequency f_eval
needs the impedance formulas only R_formula (and optionally L_formula, C_formula) on the bus types, R_self_formula, L_self_formula (C_self_formula, R_mutual_formula, M_mutual_formula) on the branch types
sources current sources with a galvanic connection to the fault bus current and voltage (Thévenin) sources
mutual coupling not modelled — the earth potential rise comes out higher (conservative), and the solve says so modelled for current sources
frequency dependence exact per bin fixed at f_eval (the smallest positive network frequency, or solve(..., f_eval=...))
watch for the window: the response must have decayed before t_end branches without R_self/L_self are left out

Use the FFT solver for a fast answer on a network without coupling, or as a conservative bound; use the state-space solver when the coupling between phase conductor and screens matters — in a cable network it usually does. On a network without coupling, with a window long enough, the two agree to numerical precision: that is the cheapest cross-check the package offers.

Describe the network for both solvers

The impedance formulas serve the stationary solve and the FFT solver; the lumped fields serve the state-space solver. Declare both when you want to compare:

L_SELF_H_PER_KM = 1.2e-3     # screen-earth loop inductance (illustrative)
L_MUTUAL_H_PER_KM = 1.0e-3   # screen-phase mutual inductance
LENGTH_KM = 3.0

substation = gi.BusType(name="substation", system_type="Substation", voltage_level=20.0,
                        impedance_formula="0.5", R_formula="0.5")
station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
                     impedance_formula="2.0", R_formula="2.0")
cable = gi.BranchType(
    name="cable", grounding_conductor=True,
    self_impedance_formula=f"(0.2 + j*2*pi*f*{L_SELF_H_PER_KM})*l",   # stationary, FFT
    mutual_impedance_formula=f"(j*2*pi*f*{L_MUTUAL_H_PER_KM})*l",
    R_self_formula="0.2*l", L_self_formula=f"{L_SELF_H_PER_KM}*l",    # state space
    R_mutual_formula="0", M_mutual_formula=f"{L_MUTUAL_H_PER_KM}*l",
)
net = gi.create_network(name="transient", frequencies=[50.0])
gi.create_bus(name="UW", type=substation, network=net)
gi.create_bus(name="S", type=station, network=net)
gi.create_branch(name="K", type=cable, from_bus="UW", to_bus="S", length=LENGTH_KM, network=net)
gi.create_source(name="infeed", bus="UW", values={50.0: 1000.0}, network=net)  # RMS
gi.create_fault(name="F", bus="S", network=net)
stationary = gi.run_fault(net, "F")
stationary_epr = next(b.uepr for b in stationary.buses if b.name == "S")

The source waveform

The waveform factories of gi.waveforms take peak values of the instantaneous current, whereas Source.values holds RMS phasors: a fault current of 1000 A RMS has the amplitude \(\sqrt 2 \cdot 1000\) A. step, sinusoidal_with_dc_offset (switched sinusoid with a decaying DC offset, dc_amplitude, dc_decay_tau) and damped_oscillation are provided; any vectorised callable f(t) works. Both solvers use the waveform as the literal injection and ignore Fault.scalings — scale the waveform itself; a fault with scalings other than 1 is announced (TRANSIENT_MODEL).

fault_current = gi.waveforms.sinusoidal_with_dc_offset(
    amplitude=math.sqrt(2) * 1000.0,  # peak of 1000 A RMS
    frequency_hz=50.0, t_on=0.02, t_off=0.12, dc_amplitude=0.0,
)

Solve and read the result

study.set_observation(buses=..., branches=...) names what is recorded; study.solve(t_end=..., dt=..., solver=...) returns a ResultTransient with time_s, epr_t[bus] and i_branch_t[branch] (instantaneous values, in the earth-side sign frame of the stationary results) and to_polars() for a long frame. progress= and should_cancel= report and stop a long solve.

results, diagnostics = {}, {}
for solver in ("fft", "state_space"):
    study = gi.TransientStudy(net, "F")
    study.set_source_waveform("infeed", fault_current)
    study.set_observation(buses=["S"], branches=["K"])
    with collecting() as records:
        results[solver] = study.solve(t_end=0.3, dt=1e-4, solver=solver)
    diagnostics[solver] = records
def steady_rms(result, bus, start=0.08, stop=0.10):
    """RMS of an EPR trace over one full period of the steady state."""
    t = np.asarray(result.time_s)
    u = np.asarray(result.epr_t[bus])
    window = (t >= start - 1e-9) & (t < stop - 1e-9)
    return float(np.sqrt(np.mean(u[window] ** 2)))

rms_fft = steady_rms(results["fft"], "S")
rms_state_space = steady_rms(results["state_space"], "S")

The warnings of a transient study

Code Solver Meaning
TRANSIENT_MODEL FFT the network has mutual coupling, which the FFT solver ignores (the coupled branches are named); also: the window ends while the response still rings — lengthen t_end or pass zero_pad=True —, the fault carries scalings, or M_mutual exceeds L_self (a unit slip)
TRANSIENT_SOURCE_NOT_CONNECTED FFT a source with a waveform has no galvanic connection to the fault bus and injects nothing
TRANSIENT_PHASE_SPLIT state space meshed network: the phase current is split as at f_eval, and the split depends on frequency, so a DC offset and harmonics are split as at f_eval (below 1 % of the peak on a mixed cable/line ring)
TRANSIENT_BRANCH_SKIPPED state space branches without R_self/L_self are left out
TRANSIENT_COUPLING_SKIPPED state space the coupling is modelled for current sources only
TRANSIENT_RESISTIVE_COUPLING_IGNORED state space mutual data on branches without inductance is ignored
DC_LIMIT FFT every FFT grid contains a 0 Hz bin, so every formula is evaluated at DC; see Harmonics, fault scalings and DC

They arrive as warnings; collect them with groundinsight.diagnostics.collecting() around solve. Details: Warnings and diagnostics.

Memory and time

The FFT solver assembles a dense \(n \times n\) admittance matrix per frequency bin — \(16\,n^2\) bytes for \(n\) active buses — in batches of at most 512 bins that stay within the byte budget fft_block_bytes of solve, 256 MiB by default. The budget binds from about 180 buses on; a 400-bus solve over 1001 bins peaks at about 0.3 GB. A smaller budget saves memory and costs time on mid-size networks (150 buses, 1001 bins: 0.7 s at the default, 4.5 s at 1 MiB); the result does not change. The state-space solver's cost grows linearly with the number of samples.

Output

Output of transient.py
stationary EPR at S: 381.2 V (RMS)
        fft: steady-state RMS 776.0 V, peak 1097.3 V, codes ['TRANSIENT_MODEL']
state_space: steady-state RMS 381.2 V, peak 539.3 V, codes []

The state-space solver reproduces the stationary result in the steady state; its peak is √2 times the RMS value plus a small switching transient. The FFT solver ignores the coupling and reports twice the earth potential rise — and says so.

Check it by hand. For the two-bus line the earth current is \(I_E = I\,(Z_s - Z_m)/(Z_{UW} + Z_S + Z_s)\) with \(Z_s = (0.2 + j\,2\pi\,50 \cdot 1.2\cdot10^{-3}) \cdot 3 = 0.6 + 1.131j\ \Omega\) and \(Z_m = j\,2\pi\,50 \cdot 10^{-3} \cdot 3 = 0.942j\ \Omega\): \(U_E = 2 \cdot 1000 \cdot |0.6 + 0.188j| / |3.1 + 1.131j| = 381.2\) V. Without the coupling (\(Z_m = 0\)): \(2 \cdot 1000 \cdot |0.6 + 1.131j| / |3.1 + 1.131j| = 776.0\) V — the FFT value. The test suite checks both steady states against these closed forms.