Splitting the network, location response¶
Two analyses sit on top of a fault solve and answer questions about one
location rather than about one fault: what the rest of the network contributes
at the fault bus, direction by direction (gi.analyze_cuts), and how the
network responds to any electrode at a bus (gi.bus_response). Both rest
on the same nodal model as the solve, described in
Model and assumptions.
Characterising a location without its electrode¶
Adding an electrode Y_B at bus b is a rank-one change to the nodal matrix, so
by Sherman-Morrison every nodal voltage is a Möbius function of it:
Three objects on the right, none of which needs the electrode to be known:
u_0, the fault solve with the electrode removed; z, the voltage everywhere
per ampere injected at b; and Z_net = z_b, the driving-point impedance of
everything except the local electrode — the parallel impedance the network
offers at that point.
gi.bus_response(network, fault=..., bus=...) builds those from two solves.
Evaluating it afterwards costs nothing, for any electrode, including the two
extremes as exact limits: Z_B → ∞ (none installed) and Z_B → 0 (ideal, which
the solver itself will not accept because a zero impedance cannot be inverted).
.extremes() returns the bracket, .evaluate(z) a single electrode and
.sweep([...]) any number of them.
The driving-point impedance is exactly Z_dp = 1/(Y_B + 1/Z_net). Its magnitude
falls monotonically from |Z_net| to zero as the electrode improves only for an
electrode whose admittance lies within 90° of 1/Z_net: along
Y_B = t·e^{jφ}, |Z_dp| decreases for every t if and only if
cos(φ − arg(1/Z_net)) ≥ 0. A resistive electrode (real Y_B ≥ 0) always
qualifies, since Re(1/Z_net) ≥ 0 in a passive network. A reactive electrode of
the opposite sign to the network's susceptance first raises |Z_dp| above
|Z_net|; the largest magnitude over all passive electrodes is reached at
Y_B = -j·Im(1/Z_net), which cancels that susceptance and gives
|Z_dp| = 1/Re(1/Z_net) = |Z_net|/cos(arg Z_net). That is 0.08 % above
|Z_net| where the network seen from the bus is nearly resistive
(arg Z_net = 2.2°), but 57 % at the far end of a four-bus cable chain
(arg Z_net = 50°). .extremes() therefore reports it as the worst_passive
row instead of assuming it away.
The closed form also derives the invariance of the EPR-based reduction factor
that the sensitivity work runs into: u_b(Y_B) = u_{0,b}/(1 + Y_B Z_net) holds
with and without mutual coupling alike, so the factor cancels out of the
quotient exactly. It is algebra, not a numerical accident. The current-based
factor has no such cancellation and responds to the electrode — see
Reduction factors and earthing impedance.
Splitting the network at the fault¶
A cut is a named set of branches, all incident to the fault bus. Cuts turn the question "how much grounding does each direction contribute" into numbers:
gi.analyze_cuts(network, fault=..., cuts=[...]) reports two families of
quantity per direction.
Impedances — a property of the network, not of the fault. One ampere is
injected at the fault bus with all sources and all mutual injections removed;
the share leaving through each cut is read off, and Z_side = u_fault / i_cut.
Because the shares and the local electrode current add up to the injected
ampere, the decomposition closes by construction,
and the residual of that identity is reported next to the values. Being
source-free, Z_side does not change when the fault bus's own characteristic is
varied — which is the useful statement: the network's parallel contribution is a
fixed property, the local electrode is the variable, and the total is their
parallel combination.
Isolating each side into its own sub-network would be equivalent wherever the sides are galvanically separate, and wrong in a ring: removing one branch of a ring separates nothing, so the far side comes out empty and the impedance infinite. Current division has no such blind spot.
Currents — how the fault current actually divides. From a solved fault:
i_shield per direction, and current_share = |i_shield| / |i_inj|. KCL at the
fault bus closes, i_inj = i_local + Σ i_shield, and the residual is reported.
Where the directions are disjoint — no ring — the far-side sums also give
i_earth, i_total and the side reduction factor r = |i_earth| / |i_total|.
Where they overlap, those three are None and current_share carries the
meaning; sides_are_disjoint says which case you are in.
Every cut branch has to be incident to the fault bus. A cut placed further out
still separates the network, but its far side is no longer a parallel element of
the fault location and the impedances would not sum. Incident branches that no
cut claims form the implicit side "rest", so the decomposition always covers
the whole network.
In a network without voltage sources the driving-point impedance that the cuts decompose is the earthing impedance \(Z_E\) of the fault bus, the number Reduction factors and earthing impedance defines.
See also¶
- Location response bracket — the response of a station to every electrode from two solves, checked against solved networks, and what the bracket of the extremes does not cover.
- Electrode at the fault location — the cuts on a feeder with harmonics against the closed forms of the ladder, a catalogue of electrodes in the \(\rho\)–\(f\) form, and a closed ring.