Standards and scope

groundinsight computes the quantities that an earthing study according to the standards needs. It does not carry out the assessment a standard prescribes. This page lists, standard by standard, what the package implements and what it leaves to the engineer.

Scope of the results

groundinsight is a research and engineering tool. Its results support, but do not replace, an assessment according to EN 50522 / IEC 61936-1 by a qualified person, including the measurements the standards require. The software is provided under the MIT License, without warranty of any kind.

EN 50522:2022 — earthing of installations above 1 kV AC

The European standard for the design and erection of earthing systems of installations above 1 kV with nominal frequencies up to 60 Hz; the current edition carries the amendment A1:2024.

Implemented

  • The quantities of the touch-voltage verification at the fault location: earth-fault current 3I_0, reduction factor r, earth current I_E, earthing impedance Z_E and earth potential rise U_E (how-to).
  • Reduction factors of cable screens and earth wires from their impedances, for any topology — the standard's informative Annex I gives typical values at 50 Hz.
  • Earth potential rise of every bus, for the transfer of potentials between bonded stations.
  • The final temperatures of uninsulated earthing conductors and electrodes used by the thermal checks (FINAL_TEMPERATURES, EN 50522:2022 Table 2).

Not implemented

  • The permissible touch voltage U_Tp(t_F) (5.4.1, Annexes A and B) and the decision of the design procedure (5.4.3) with the measures M (Annex E).
  • Touch and step voltages, surface potentials, additional resistances.
  • Transferred potentials to low-voltage and telecommunication systems (Clause 6), dimensioning for corrosion and mechanical strength (5.2), the construction rules (Clause 7).
  • The measurements (Clause 8, 9.2, Annexes H and L) — the model needs them to be validated, it does not replace them.

IEC 61936-1:2021 — power installations above 1 kV AC

The international standard for the design and erection of AC power installations; its Clause 10 "Earthing systems" sets the earthing requirements that EN 50522 details for Europe. The same split applies: groundinsight supplies U_E, Z_E, I_E and r, the assessment is the engineer's.

IEC 60909-0:2016 — short-circuit currents

Implemented: the factors that turn a symmetrical short-circuit current into the peak and thermal quantities — the peak factor κ from R/X (kappa_from_r_to_x), the peak current, the DC heat factor m (iec60909_m) and the thermally equivalent short-time current I_th = I_k·√(m + n). They are applied to the current that the linear solve superposes, not to the source currents one by one.

Not implemented: the short-circuit calculation of the network itself. The fault current is an input — from the network operator, or from a pandapower calc_sc run imported with read_shortcircuit_results / apply_shortcircuit_characteristics (I/O).

IEC 60949:1988 — thermally permissible short-circuit currents

Implemented: the adiabatic rating I_adm = k·S/√t_k of an earthing conductor or electrode, with k = K·√ln((θ_f + β)/(θ_i + β)) and the material constants of the standard (IEC60949_MATERIALS), in check_conductor_limits and check_node_limits (Analysis).

Not implemented: the non-adiabatic factor of IEC 60949 (heat given off during the fault). Leaving it out underestimates the permissible current, which is on the safe side.

IEC 60479-1:2018 and IEC 60479-2:2019 — effects of current on the body

Not implemented. They are the physiological basis of the permissible touch voltages of EN 50522, and the documentation uses IEC 60479-2 for one argument: its frequency factors describe thresholds that rise with frequency, which is why comparing the total RMS earth potential rise with the 50 Hz curve is conservative for the body current. The impedance of the skin falls with frequency (DIN IEC/TS 60479-1:2007-05, 4.2), so for the touch voltage this is not shown (how-to).

Model assumptions behind every result

The results rest on the model described in Model and assumptions and Verification: a quasi-stationary phasor solve per frequency (transient solvers aside), lumped electrodes without resistive coupling between them, homogeneous soil per element through rho, the coupling of the faulted phase to the earthing conductors as Norton sources, and the formulas the user supplies. An assessment has to check that these assumptions fit the installation.

References

  1. EN 50522:2022, Earthing of power installations exceeding 1 kV a.c., and EN 50522:2022/A1:2024; table of contents of the national edition STN EN 50522:2022: https://normy.normoff.gov.sk/norma/134904/nahlad.
  2. IEC 61936-1:2021, Power installations exceeding 1 kV AC and 1,5 kV DC — Part 1: AC, edition 3.0.
  3. IEC 60909-0:2016, Short-circuit currents in three-phase a.c. systems — Part 0: Calculation of currents.
  4. IEC 60949:1988 + A1:2008, Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects.
  5. IEC 60479-1:2018, Effects of current on human beings and livestock — Part 1: General aspects.
  6. IEC 60479-2:2019, Effects of current on human beings and livestock — Part 2: Special aspects.
  7. DIN IEC/TS 60479-1 (VDE V 0140-479-1):2007-05, Effects of current on human beings and livestock — Part 1: General aspects (IEC/TS 60479-1:2005
  8. Corrigendum October 2006).