Harmonics, fault scalings and DC¶
This guide sets up a fault study with several frequencies — the fundamental,
harmonics, direct current — and shows what the solver does when the input
covers only part of them. It uses one script,
harmonics.py; its output is at the
end of the page.
Frequencies and source values¶
Network.frequencies lists the frequencies the network is solved at, in Hz,
as floats; 0.0 is DC. Every bus and branch evaluates its impedance formulas
at each of them, and each frequency is an independent solve of the same
nodal system. Keep the list strictly increasing — a shuffled list is kept
but announced (FREQUENCY_ORDER), because the FFT transient solver maps bins
by position.
Source.values holds the RMS phasor of the source current per frequency,
in A: the fundamental and the harmonic content of the earth-fault current at
the infeed, from a measurement or a harmonic study. A peak value from a
waveform record has to be divided by √2 first
(Conventions).
The example: a substation UW (0.5 Ω) feeds an earth fault at station S
(ring electrode, 5.90 Ω at ρ = 100 Ω·m) over 3 km of the cable system of the
data-sheet how-to, with 1000 A at 50 Hz, 60 A at
250 Hz and 40 A at 350 Hz (illustrative values):
cable_system = gi.BranchType(
name="3x NA2XS(F)2Y 1x300RM/25 12/20 kV, trefoil",
grounding_conductor=True,
self_impedance_formula=(
"(0.727/3 + pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272))*l"
),
mutual_impedance_formula=(
"(pi**2*1e-4*f + j*4*pi*1e-4*f*log(658*sqrt(rho/f)/0.03151272))*l"
),
)
substation = gi.BusType(name="substation", system_type="Substation", voltage_level=20.0,
impedance_formula="0.5")
station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
impedance_formula="2*rho/(3*1.13*sqrt(100.0))") # ring electrode
FREQUENCIES = [50.0, 250.0, 350.0]
SOURCE_VALUES = {50.0: 1000.0, 250.0: 60.0, 350.0: 40.0} # A, RMS per frequency
LENGTH_KM = 3.0
net = gi.create_network(name="harmonics", frequencies=FREQUENCIES)
gi.create_bus(name="UW", type=substation, specific_earth_resistance=100.0, network=net)
gi.create_bus(name="S", type=station, specific_earth_resistance=100.0, network=net)
gi.create_branch(name="K", type=cable_system, from_bus="UW", to_bus="S", length=LENGTH_KM,
specific_earth_resistance=100.0, network=net)
gi.create_source(name="infeed", bus="UW", values=SOURCE_VALUES, network=net)
gi.create_fault(name="F", bus="S", scalings={50.0: 1.0, 250.0: 1.0, 350.0: 1.0}, network=net)
Fault scalings¶
Fault.scalings multiplies the current of every source that reaches the
fault, per frequency. The source values describe the infeed; the scalings
describe the fault — which share of each frequency this fault draws. The
rules:
scalingsleft out,Noneor{}means 1.0 at every frequency, without a warning.- A frequency missing from a non-empty mapping is scaled with 1.0 (full
contribution), and the run announces it once (
SCALINGS_INCOMPLETE). Write every frequency to make the choice explicit. 0.0excludes a frequency from this fault:{50.0: 1.0, 250.0: 0.0}solves the fault at 50 Hz alone, whatever the source carries at 250 Hz.Fault.scaling_at(frequency)returns the factor the solve uses.
net.faults["F"].scalings = {50.0: 1.0, 250.0: 0.0, 350.0: 0.0} # this fault: 50 Hz only
gi.run_fault(net, "F")
u_e_rms_fundamental_only = net.res_fault("F").filter("is_rms")["U_E_V"][0]
Per-frequency and RMS results¶
res_fault, res_buses and res_branches have one row per frequency and one
RMS row per element, which combines the frequencies as
\(\sqrt{\sum_f |X(f)|^2}\) — the 0 Hz term with its full magnitude. The RMS row
has is_rms true and frequency_Hz null, and its ratios, impedances and
angles are null: a reduction factor has no RMS. Select a frequency with
pl.col("frequency_Hz") == 250.0 and the RMS row with pl.col("is_rms").
res_all_impedances has no RMS row; the comparison frames of an outage study
write frequency_Hz as text. All columns:
Result tables.
For the comparison with the permissible touch voltage of EN 50522, use the
total RMS of U_E against the 50 Hz curve. That is conservative for the body
current, not shown for the touch voltage; see
Compare results with EN 50522 limits.
Check it by hand. For one line between two stations the earth current
has a closed form: with the source at UW and the fault at S,
\(I_E = I\,(Z_s - Z_m)/(Z_{UW} + Z_S + Z_s)\) and \(U_E = Z_S\,I_E\). At 50 Hz the
cable gives \(Z_s - Z_m = 3 \cdot 0.727/3 = 0.727\ \Omega\) (the screens'
resistance; the earth-return terms cancel) and
\(Z_{UW} + Z_S + Z_s = 7.275 + 1.940j\ \Omega\), so
\(I_E = 1000 \cdot 0.727 / 7.529 = 96.56\) A, \(r = 0.0966\) and
\(U_E = 5.900 \cdot 96.56 = 569.67\) V — the first row of the output. The test
suite recomputes every row this way.
When the input does not cover every frequency¶
| Input | What the solve does | Announced as |
|---|---|---|
a non-empty scalings without some network frequencies |
scales those with 1.0 | SCALINGS_INCOMPLETE (InputWarning), once per run |
| a source that reaches the fault, without a value at some network frequencies | the source contributes 0 A there | SOURCE_FREQUENCY_GAP (InputWarning), once per source and run |
| a source that reaches the fault, without a value at any network frequency | refuses: it would contribute 0 A everywhere | ValueError naming the source, its keys and the network frequencies |
| a source value at a frequency the network does not solve | ignores the value | SOURCE_FREQUENCY_OUTSIDE_NETWORK (InputWarning), when the source is created |
The first two arrive in Result.diagnostics; the last one is raised by
create_source before any solve, so collect it with
groundinsight.diagnostics.collecting(). gi.check_network(net) reports all
three before a solve. Every code: Warnings and diagnostics.
net.faults["F"].scalings = {50.0: 1.0, 250.0: 1.0} # 350 Hz missing: scaled with 1.0
missing_scaling = gi.run_fault(net, "F")
net.faults["F"].scalings = None # 1.0 at every frequency, no warning
net.sources["infeed"].values = {50.0: 1000.0, 250.0: 60.0} # 350 Hz missing: 0 A there
missing_value = gi.run_fault(net, "F")
net.sources["infeed"].values = {16.7: 1000.0} # no network frequency at all
try:
gi.run_fault(net, "F")
except ValueError as refused:
no_value = str(refused).split(". ")[0]
with collecting() as outside: # announced when the source is created
gi.create_source(name="extra", bus="UW", values={50.0: 10.0, 150.0: 5.0}, network=net)
Direct current (f = 0)¶
A DC study is an ordinary solve at f = 0; only the input needs care.
- Network:
frequencies=[0.0], or a mixed list such as[0.0, 50.0]— the 0 Hz bin is independent, and a study with both returns the same 50 Hz answer as one with 50 Hz alone. - Current source: a real value at
0.0, e.g.values={0.0: 1000.0}. - Voltage source:
voltageandsource_impedancewith a0.0entry; the source impedance needs a real part, a purely inductive one is zero at DC. - Fault: no
0.0key needed (1.0 by default);0.0: 0.0keeps DC out of a fault. The IEC 60909 characteristics (i_k_a,r_to_x,kappa) describe an alternating current and have no meaning in a DC study.
How a formula is read at 0 Hz. The value is the limit for \(f \to 0\),
found by approaching on 1e-6, 1e-7, 1e-8 Hz:
- a reactance written as
j*2*pi*f*Lvanishes, and the Carson earth-return terms of a cable tend to their limit (zero for the mutual impedance) — nothing to announce; - a constant reactance such as
+ j*0.2has no reading at DC: the 0 Hz bin keeps the real part and drops the reactance, with aDC_LIMITwarning (DCLimitWarning) when the element is created; - a pole — a series capacitance \(1/(j\omega C)\) — is an open circuit;
- an exact zero — a purely inductive bond — is an ideal short circuit,
which the nodal system cannot invert. The element gets a stand-in of
\(\sqrt{\varepsilon_\text{mach}}\,Z_\text{min} = 1.49\cdot10^{-8}\,Z_\text{min}\),
where \(Z_\text{min}\) is the smallest other impedance of the network at
0 Hz, and the run says so (
DC_LIMITinResult.diagnostics). Only the 0 Hz bin is affected.
dc = gi.create_network(name="dc_chain", frequencies=[0.0])
for name, z in (("A", "0.8"), ("B", "12.0"), ("C", "3.5")):
gi.create_bus(name=name, network=dc, type=gi.BusType(
name=f"electrode {name}", system_type="Station", voltage_level=20.0, impedance_formula=z))
bond = gi.BranchType(name="bond", grounding_conductor=True, # purely inductive: 0 at DC
self_impedance_formula="j*2*pi*f*1e-6*l", mutual_impedance_formula="0")
conductor = gi.BranchType(name="conductor", grounding_conductor=True,
self_impedance_formula="0.35*l", mutual_impedance_formula="0")
gi.create_branch(name="AB", type=bond, from_bus="A", to_bus="B", length=1.0, network=dc)
gi.create_branch(name="BC", type=conductor, from_bus="B", to_bus="C", length=1.0, network=dc)
gi.create_source(name="injection", bus="A", values={0.0: 1000.0}, network=dc) # DC, real
gi.create_fault(name="F", bus="C", network=dc)
dc_result = gi.run_fault(dc, "F")
dc_potentials = {bus.name: bus.uepr_freq[0.0].real for bus in dc_result.buses}
stand_in = next(d for d in dc_result.diagnostics if d.code == "DC_LIMIT")
dc_substitute_ohm = float(stand_in.message.split("modelled with ")[1].split(" Ohm")[0])
Check it by hand. In the chain above (electrodes 0.8 Ω, 12 Ω and 3.5 Ω, bond A–B purely inductive, 0.35 Ω from B to C, 1000 A injected at A, fault at C) the stand-in is \(1.49\cdot10^{-8} \cdot 0.35\ \Omega = 5.2\cdot10^{-9}\ \Omega\). The exact answer merges A and B into one node with \(0.8 \parallel 12 = 0.75\ \Omega\): \(u_{AB}\,(1/0.75 + 1/0.35) - u_C/0.35 = 1000\) and \(u_C\,(1/3.5 + 1/0.35) - u_{AB}/0.35 = -1000\) (the package's earth-side frame) give \(u_A = u_B = 57.07\) V and \(u_C = -266.30\) V — what the solve reports. Prefer the merge when the potential difference across an ideal bond is part of what you report, or give the bond a small honest resistance, which also removes the warning.
What is refused. An impedance that is inverted — an electrode, a
conductor with grounding_conductor=True, a source impedance — may not have a
negative real part, nor a real part of \(-\infty\) at 0 Hz (a log(f) term
without a factor f), nor be NaN; above 0 Hz it may not be zero either. Each
raises a ValueError that names the element, the frequency and the formula.
+inf (the formula "nan") stays legal everywhere: it is the open end.
with collecting() as constant_reactance: # '+ j*0.2' does not vanish at DC
gi.create_branch(name="CA", network=dc, from_bus="C", to_bus="A", length=1.0,
type=gi.BranchType(name="fixed X", grounding_conductor=True,
self_impedance_formula="0.35*l + j*0.2",
mutual_impedance_formula="0"))
try: # log(f) runs to minus infinity at DC: refused for an electrode
gi.create_bus(name="D", network=dc, type=gi.BusType(
name="log", system_type="Station", voltage_level=20.0, impedance_formula="1 + log(f)"))
except ValueError as refused:
log_refused = str(refused).split(". ")[1]
The reasoning behind these rules — the three kinds of singularity at 0 Hz, the measured accuracy of the stand-in — is in the explanation of direct current; the formula side is summarised in Formula syntax. Every transient study contains a 0 Hz bin as well: Transient simulation.
Output¶
f / Hz I_F / A U_E / V r
50 1000.0 569.67 0.0966
250 60.0 21.61 0.0610
350 40.0 11.62 0.0493
RMS 1002.6 570.20 -
50 Hz only (scalings 1/0/0): U_E, total RMS = 569.67 V
scaling missing at 350 Hz: ['SCALINGS_INCOMPLETE']
source value missing at 350 Hz: ['SOURCE_FREQUENCY_GAP']
source without a network frequency: ValueError: Source 'infeed' at bus 'UW' reaches fault 'F' but carries values only at 16.7 Hz, none of the network frequencies (50 Hz, 250 Hz, 350 Hz)
source value at 150 Hz: ['SOURCE_FREQUENCY_OUTSIDE_NETWORK']
DC chain: u_A = 57.07 V, u_B = 57.07 V, u_C = -266.30 V
DC stand-in for the bond: 5.215e-09 Ohm (DC_LIMIT)
constant reactance at 0 Hz: ['DC_LIMIT']
log(f) electrode at 0 Hz: ValueError: Its real part is minus infinity at 0 Hz
The DC potentials are in the package's earth-side sign frame (see Signs and phase angles).