The rules on this page change numbers when they are missed: a length in metres instead of kilometres, a peak value where an RMS value belongs, a phase angle read in the wrong frame, a missing fault scaling. Each rule is stated with an example that the test suite recomputes.

Units

Quantity Unit Where
branch length l, Branch.length km formulas, create_branch(length=...)
specific earth resistance rho Ω·m specific_earth_resistance of buses and branches, formulas
frequency f Hz, as float keys Network.frequencies, Source.values, Fault.scalings, result dictionaries; 0.0 is DC
currents A, RMS Source.values, result columns ending in _A
voltages, earth potential rise V, RMS uepr, EPR_V, u_earthing
impedances Ω per element (per-km value × l for a branch) formulas, grounding_impedance_Ohm, z_earthing
phase angles degrees, relative to the phasor reference of the sources result columns ending in _degree
time s ResultTransient.time_s, Fault.t_k_s
cross-sections, temperatures mm², °C thermal fields of the types

Phasors are RMS, waveforms are instantaneous

Every phasor in the stationary model is an RMS phasor: Source.values, the Thévenin voltage, and every phasor in the results. The RMS row of a result frame (is_rms true, frequency_Hz null) combines the frequencies as \(X_\text{RMS} = \sqrt{\sum_f |X(f)|^2}\), with the 0 Hz term entering with its full magnitude.

The transient solvers work with instantaneous values. The waveform factories in gi.waveforms take peak amplitudes: amplitude of sinusoidal_with_dc_offset and of damped_oscillation is the peak of the alternating part, dc_amplitude the initial value of the decaying offset, and step holds its amplitude as an instantaneous level. ResultTransient.epr_t and i_branch_t are instantaneous volts and amperes. To reproduce a stationary run with values={50.0: I}, drive the transient with amplitude=math.sqrt(2) * I:

import math
import groundinsight as gi

station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
                     impedance_formula="2.0")
line = gi.BranchType(name="line", grounding_conductor=True,
                     self_impedance_formula="(0.2 + j*2*pi*f*1.2e-3)*l",
                     mutual_impedance_formula="0")
net = gi.create_network(name="rms", frequencies=[50.0])
gi.create_bus(name="S", type=station, network=net)
gi.create_bus(name="F", type=station, network=net)
gi.create_branch(name="K", type=line, from_bus="S", to_bus="F", length=2.0, network=net)
gi.create_source(name="Q", bus="S", values={50.0: 1000.0}, network=net)  # 1000 A RMS
gi.create_fault(name="F1", bus="F", scalings={50.0: 1.0}, network=net)
stationary = gi.run_fault(net, "F1")

study = gi.TransientStudy(net, "F1")
study.set_source_waveform("Q", gi.waveforms.sinusoidal_with_dc_offset(
    amplitude=math.sqrt(2) * 1000.0, frequency_hz=50.0))  # peak of 1000 A RMS
study.set_observation(buses=["F"])
transient = study.solve(t_end=0.2, dt=1e-5, solver="fft")

The stationary EPR at F is 382.39 V (RMS). The RMS of the transient EPR over its last period is the same 382.39 V, and its peak is 540.8 V = √2 × 382.39 V. (The FFT solver reminds you with a TransientModelWarning that the window ends while the source is still on; for a steady-state comparison that is intended.) If a data source gives peak amplitudes, divide the alternating components by √2 before filling values; a DC component stays as it is.

Signs and phase angles

Magnitudes, RMS values, the reduction factors and the impedances do not depend on a sign convention. Phase angles and the signs of complex results do, and groundinsight uses two frames:

  • Phase and shield currents are reported for the physical fault: the phase current flows from the source to the fault, and ResultBranch.i_s_freq (I_branch_A, I_branch_degree) is the shield current counted positive from from_bus to to_bus.
  • Earth-side quantities — the potentials uepr_freq (EPR_V, EPR_degree, u_earthing), the electrode currents ia_freq (I_bus_A, I_bus_degree) and the injections i_inj_freq (I_inj_A, I_inj_degree) — are reported for a current that enters the earthing network at the source bus and leaves it at the fault bus. That is the reverse of the physical direction, so each of these phasors is the negative of its physical value: add 180° to read the physical phase angle.

Two buses show it. S (electrode 0.5 Ω) feeds 1000 A at 50 Hz to a fault at F (electrode 2 Ω) over a 5 km line with Z_s = (0.2 + 0.4j) Ω/km and Z_m = (0.05 + 0.35j) Ω/km:

import groundinsight as gi

s_type = gi.BusType(name="S", system_type="Substation", voltage_level=20.0,
                    impedance_formula="0.5")
f_type = gi.BusType(name="F", system_type="Station", voltage_level=20.0,
                    impedance_formula="2.0")
line = gi.BranchType(name="line", grounding_conductor=True,
                     self_impedance_formula="(0.2 + 0.4*j)*l",
                     mutual_impedance_formula="(0.05 + 0.35*j)*l")
net = gi.create_network(name="signs", frequencies=[50.0])
gi.create_bus(name="S", type=s_type, network=net)
gi.create_bus(name="F", type=f_type, network=net)
gi.create_branch(name="L", type=line, from_bus="S", to_bus="F", length=5.0, network=net)
gi.create_source(name="Q", bus="S", values={50.0: 1000.0}, network=net)
gi.create_fault(name="F1", bus="F", scalings={50.0: 1.0}, network=net)
result = gi.run_fault(net, "F1")

By hand, with the phase current I = 1000 A from S to F: the shield returns Is = I·(ZS + ZF + Zm)/(ZS + ZF + Zs) = 807.7 + 38.5j A from F to S, the soil carries IE = I − Is = 192.3 − 38.5j A, and the electrodes rise to uF = ZF·IE and uS = −ZS·IE.

Quantity Reported Physical (by hand) Relation
EPR at the fault bus F −384.6 + 76.9j V (168.7°) +384.6 − 76.9j V (−11.3°) negated
EPR at the source bus S 96.2 − 19.2j V −96.2 + 19.2j V negated
electrode current at F −192.3 + 38.5j A +192.3 − 38.5j A negated
injection at S / F +1000 A / −1000 A the fault current enters the earthing system at F negated
shield current of L (S → F) −807.7 − 38.5j A 807.7 + 38.5j A flowing from F to S same, counted from_bus → to_bus
phase current of L +1000 A 1000 A from S to F same

The EPR at the fault bus is therefore reported at about 180° from the source phasor when the earthing is mostly resistive. Model and assumptions describes the shield current in the earth-side frame — positive from to_bus to from_bus — which is the same physical current. The transient time series follow the earth-side frame of the stationary result: with a source waveform √2·I·sin(ωt) and mostly resistive earthing, the EPR at F is negative when the source current peaks.

Frequencies, source values and fault scalings

  • Network frequencies are floats; integer keys are converted. 0.0 is DC.
  • Source values are given per frequency. An active source that reaches the fault but has no value at any network frequency makes run_fault raise a ValueError that names the source, its keys and the network frequencies — it would contribute 0 A everywhere. A source that misses some network frequencies contributes 0 A at those and is announced once per source and run (InputWarning, code SOURCE_FREQUENCY_GAP). Keys outside the network frequencies are announced when the source is created (SOURCE_FREQUENCY_OUTSIDE_NETWORK) and ignored by the solve.
  • Fault scalings multiply every source current that feeds the fault, per frequency. scalings is optional: left out, None or {} means 1.0 at every frequency. A frequency missing from a non-empty mapping is also scaled with 1.0, and the run announces the gap once (InputWarning, code SCALINGS_INCOMPLETE). Give 0.0: 0.0 to keep a frequency, for example DC, out of a fault. Fault.scaling_at(frequency) returns the factor used.

Which reduction factor is which

Field Column of res_all_impedances() Definition Use
ResultReductionFactor.value reduction_factor EPR at the fault bus with coupling over EPR without coupling a property of the line: \(\lvert 1 - Z_m/Z_s \rvert\) for one line, independent of the fault-bus electrode
ResultReductionFactor.value_current reduction_factor_current \(\lvert I_E \rvert / \lvert 3I_0 \rvert\), earth current over fault current the reduction factor r of EN 50522

The two coincide only for ideally bonded stations. See Compare results with EN 50522 limits and Reduction factors and earthing impedance.

See also