Conventions and units¶
The rules on this page change numbers when they are missed: a length in metres instead of kilometres, a peak value where an RMS value belongs, a phase angle read in the wrong frame, a missing fault scaling. Each rule is stated with an example that the test suite recomputes.
Units¶
| Quantity | Unit | Where |
|---|---|---|
branch length l, Branch.length |
km | formulas, create_branch(length=...) |
specific earth resistance rho |
Ω·m | specific_earth_resistance of buses and branches, formulas |
frequency f |
Hz, as float keys |
Network.frequencies, Source.values, Fault.scalings, result dictionaries; 0.0 is DC |
| currents | A, RMS | Source.values, result columns ending in _A |
| voltages, earth potential rise | V, RMS | uepr, EPR_V, u_earthing |
| impedances | Ω per element (per-km value × l for a branch) |
formulas, grounding_impedance_Ohm, z_earthing |
| phase angles | degrees, relative to the phasor reference of the sources | result columns ending in _degree |
| time | s | ResultTransient.time_s, Fault.t_k_s |
| cross-sections, temperatures | mm², °C | thermal fields of the types |
Phasors are RMS, waveforms are instantaneous¶
Every phasor in the stationary model is an RMS phasor: Source.values, the
Thévenin voltage, and every phasor in the results. The RMS row of a result
frame (is_rms true, frequency_Hz null) combines the frequencies as
\(X_\text{RMS} = \sqrt{\sum_f |X(f)|^2}\), with the 0 Hz term entering with its
full magnitude.
The transient solvers work with instantaneous values. The waveform
factories in gi.waveforms take peak amplitudes: amplitude of
sinusoidal_with_dc_offset and of damped_oscillation is the peak of the
alternating part, dc_amplitude the initial value of the decaying offset, and
step holds its amplitude as an instantaneous level. ResultTransient.epr_t
and i_branch_t are instantaneous volts and amperes. To reproduce a stationary
run with values={50.0: I}, drive the transient with
amplitude=math.sqrt(2) * I:
import math
import groundinsight as gi
station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
impedance_formula="2.0")
line = gi.BranchType(name="line", grounding_conductor=True,
self_impedance_formula="(0.2 + j*2*pi*f*1.2e-3)*l",
mutual_impedance_formula="0")
net = gi.create_network(name="rms", frequencies=[50.0])
gi.create_bus(name="S", type=station, network=net)
gi.create_bus(name="F", type=station, network=net)
gi.create_branch(name="K", type=line, from_bus="S", to_bus="F", length=2.0, network=net)
gi.create_source(name="Q", bus="S", values={50.0: 1000.0}, network=net) # 1000 A RMS
gi.create_fault(name="F1", bus="F", scalings={50.0: 1.0}, network=net)
stationary = gi.run_fault(net, "F1")
study = gi.TransientStudy(net, "F1")
study.set_source_waveform("Q", gi.waveforms.sinusoidal_with_dc_offset(
amplitude=math.sqrt(2) * 1000.0, frequency_hz=50.0)) # peak of 1000 A RMS
study.set_observation(buses=["F"])
transient = study.solve(t_end=0.2, dt=1e-5, solver="fft")
The stationary EPR at F is 382.39 V (RMS). The RMS of the transient EPR over
its last period is the same 382.39 V, and its peak is 540.8 V = √2 × 382.39 V.
(The FFT solver reminds you with a TransientModelWarning that the window ends
while the source is still on; for a steady-state comparison that is intended.)
If a data source gives peak amplitudes, divide the alternating components by
√2 before filling values; a DC component stays as it is.
Signs and phase angles¶
Magnitudes, RMS values, the reduction factors and the impedances do not depend
on a sign convention. Phase angles and the signs of complex results do, and
groundinsight uses two frames:
- Phase and shield currents are reported for the physical fault: the phase
current flows from the source to the fault, and
ResultBranch.i_s_freq(I_branch_A,I_branch_degree) is the shield current counted positive fromfrom_bustoto_bus. - Earth-side quantities — the potentials
uepr_freq(EPR_V,EPR_degree,u_earthing), the electrode currentsia_freq(I_bus_A,I_bus_degree) and the injectionsi_inj_freq(I_inj_A,I_inj_degree) — are reported for a current that enters the earthing network at the source bus and leaves it at the fault bus. That is the reverse of the physical direction, so each of these phasors is the negative of its physical value: add 180° to read the physical phase angle.
Two buses show it. S (electrode 0.5 Ω) feeds 1000 A at 50 Hz to a fault at
F (electrode 2 Ω) over a 5 km line with
Z_s = (0.2 + 0.4j) Ω/km and Z_m = (0.05 + 0.35j) Ω/km:
import groundinsight as gi
s_type = gi.BusType(name="S", system_type="Substation", voltage_level=20.0,
impedance_formula="0.5")
f_type = gi.BusType(name="F", system_type="Station", voltage_level=20.0,
impedance_formula="2.0")
line = gi.BranchType(name="line", grounding_conductor=True,
self_impedance_formula="(0.2 + 0.4*j)*l",
mutual_impedance_formula="(0.05 + 0.35*j)*l")
net = gi.create_network(name="signs", frequencies=[50.0])
gi.create_bus(name="S", type=s_type, network=net)
gi.create_bus(name="F", type=f_type, network=net)
gi.create_branch(name="L", type=line, from_bus="S", to_bus="F", length=5.0, network=net)
gi.create_source(name="Q", bus="S", values={50.0: 1000.0}, network=net)
gi.create_fault(name="F1", bus="F", scalings={50.0: 1.0}, network=net)
result = gi.run_fault(net, "F1")
By hand, with the phase current I = 1000 A from S to F: the shield returns Is = I·(ZS + ZF + Zm)/(ZS + ZF + Zs) = 807.7 + 38.5j A from F to S, the soil carries IE = I − Is = 192.3 − 38.5j A, and the electrodes rise to uF = ZF·IE and uS = −ZS·IE.
| Quantity | Reported | Physical (by hand) | Relation |
|---|---|---|---|
EPR at the fault bus F |
−384.6 + 76.9j V (168.7°) | +384.6 − 76.9j V (−11.3°) | negated |
EPR at the source bus S |
96.2 − 19.2j V | −96.2 + 19.2j V | negated |
electrode current at F |
−192.3 + 38.5j A | +192.3 − 38.5j A | negated |
injection at S / F |
+1000 A / −1000 A | the fault current enters the earthing system at F |
negated |
shield current of L (S → F) |
−807.7 − 38.5j A | 807.7 + 38.5j A flowing from F to S | same, counted from_bus → to_bus |
phase current of L |
+1000 A | 1000 A from S to F | same |
The EPR at the fault bus is therefore reported at about 180° from the source
phasor when the earthing is mostly resistive. Model and assumptions
describes the shield current in the earth-side frame — positive from to_bus
to from_bus — which is the same physical current. The transient time series
follow the earth-side frame of the stationary result: with a source waveform
√2·I·sin(ωt) and mostly resistive earthing, the EPR at F is negative when the
source current peaks.
Frequencies, source values and fault scalings¶
- Network frequencies are floats; integer keys are converted.
0.0is DC. - Source values are given per frequency. An active source that reaches the
fault but has no value at any network frequency makes
run_faultraise aValueErrorthat names the source, its keys and the network frequencies — it would contribute 0 A everywhere. A source that misses some network frequencies contributes 0 A at those and is announced once per source and run (InputWarning, codeSOURCE_FREQUENCY_GAP). Keys outside the network frequencies are announced when the source is created (SOURCE_FREQUENCY_OUTSIDE_NETWORK) and ignored by the solve. - Fault scalings multiply every source current that feeds the fault, per
frequency.
scalingsis optional: left out,Noneor{}means 1.0 at every frequency. A frequency missing from a non-empty mapping is also scaled with 1.0, and the run announces the gap once (InputWarning, codeSCALINGS_INCOMPLETE). Give0.0: 0.0to keep a frequency, for example DC, out of a fault.Fault.scaling_at(frequency)returns the factor used.
Which reduction factor is which¶
| Field | Column of res_all_impedances() |
Definition | Use |
|---|---|---|---|
ResultReductionFactor.value |
reduction_factor |
EPR at the fault bus with coupling over EPR without coupling | a property of the line: \(\lvert 1 - Z_m/Z_s \rvert\) for one line, independent of the fault-bus electrode |
ResultReductionFactor.value_current |
reduction_factor_current |
\(\lvert I_E \rvert / \lvert 3I_0 \rvert\), earth current over fault current | the reduction factor r of EN 50522 |
The two coincide only for ideally bonded stations. See Compare results with EN 50522 limits and Reduction factors and earthing impedance.