Result tables¶
Every solve stores one Result per fault on the network, and the package
hands results out as Polars data frames: the res_*
accessors of Network, the study results, the thermal checks and the
importers. This page lists every column of every frame with its type, unit
and meaning.
The column names and types in the tables below are generated from the code
when this site is built — from the schema constants that pin the frames
(RES_BUSES_SCHEMA, gi.RES_FAULT_SCHEMA, CUT_FRAME_SCHEMA, …) or, where a
frame has no constant, from a frame built on a small network at build time.
A test compares the constants with the frames of a real solve, so a table
cannot describe a column the code no longer has.
Rules that hold for every frame¶
Units. Phasors are RMS values, currents in A, voltages in V, impedances
in Ω, angles in degrees; the column name ends with the unit (_A, _V,
_Ohm, _degree or _deg, _Hz, _s, _mm2). The time series of a
transient study are instantaneous values. See
Conventions and units.
Signs. Magnitudes do not depend on a sign convention, angles do. Earth
potentials, electrode currents and injections are reported in the earth-side
frame (a current that enters the earthing network at the source and leaves it
at the fault), branch currents for the physical fault, counted from
from_bus to to_bus — see
Signs and phase angles.
Frequencies and the RMS row. frequency_Hz is Float64 in every frame
of a solve. res_buses, res_branches and res_fault add one RMS row
per element that combines all frequencies as \(\sqrt{\sum_f |X(f)|^2}\); that
row has is_rms true and frequency_Hz null, and its angles, ratios and
impedances are null, because they have no RMS. res_all_impedances and the
decomposition frame have no RMS row. The exception are the comparison
frames of an outage study: there frequency_Hz is text — "50.0", or
"RMS" for the RMS row — because it is the key the scenarios are joined on.
Filter with pl.col("is_rms") in the frames of a solve and with
pl.col("frequency_Hz") == "RMS" in a comparison frame.
Two reduction factors. reduction_factor (in res_fault: r_epr) is
the EPR ratio with and without the inductive coupling — a property of the
line, blind to the electrodes, and not the reduction factor of EN 50522.
reduction_factor_current (in res_fault: r_current) is |I_E| / |I_F|,
the reduction factor r of EN 50522. They coincide only for ideally bonded
stations; see Which reduction factor is which.
Missing values. A quantity the result marks as undefined is null, never
a number: the current-based factor at a frequency without fault current, the
earthing impedance of a fault bus without an electrode in its earthing group
(diagnostic EARTHING_IMPEDANCE_UNDEFINED, see
Warnings and diagnostics). The schemas are pinned, so an empty
result is an empty frame with these columns, which can still be selected and
filtered.
import polars as pl
import groundinsight as gi
station = gi.BusType(name="station", system_type="Station", voltage_level=20.0,
impedance_formula="2.0")
cable = gi.BranchType(name="cable", grounding_conductor=True,
self_impedance_formula="(0.2 + j*2*pi*f*1.2e-3)*l",
mutual_impedance_formula="(j*2*pi*f*1.0e-3)*l")
net = gi.create_network(name="tables", frequencies=[50.0, 250.0])
for name in ("UW", "S1", "S2"):
gi.create_bus(name=name, type=station, network=net)
gi.create_branch(name="K1", type=cable, from_bus="UW", to_bus="S1", length=1.0, network=net)
gi.create_branch(name="K2", type=cable, from_bus="S1", to_bus="S2", length=1.0, network=net)
gi.create_source(name="infeed", bus="UW", values={50.0: 1000.0, 250.0: 50.0}, network=net)
gi.create_fault(name="F", bus="S2", network=net)
gi.run_fault(net, "F")
buses = net.res_buses(fault="F")
at_50_hz = buses.filter(pl.col("frequency_Hz") == 50.0) # one row per bus
rms = buses.filter(pl.col("is_rms")) # one row per bus, frequency_Hz null
print(buses.shape, at_50_hz.shape, rms["frequency_Hz"].null_count()) # (9, 10) (3, 10) 3
study = gi.run_outage_study(net, fault="F", scenarios=[gi.Outage(name="K2 out", disabled_branches=["K2"])])
compared = study.compare_buses()
print(compared.schema["frequency_Hz"]) # String
print(compared.filter(pl.col("frequency_Hz") == "RMS").height) # 6: 3 buses x 2 scenarios
Results of a solve¶
Network.res_buses(fault=None)¶
One row per bus and frequency plus one RMS row per bus, for one fault or for
every stored result. I_bus_A is the current through the bus's own electrode
into the soil; I_inj_A is the current of the earthing conductor at a source
or fault bus. Sizing an earthing conductor with I_bus_A underestimates it —
the thermal check of the node uses the right one for each element.
| Column | Type | Unit | Meaning |
|---|---|---|---|
bus_name |
String | – | name of the bus |
fault |
String | – | name of the fault the result belongs to |
frequency_Hz |
Float64 | Hz | frequency of the row; null on the RMS row |
is_rms |
Boolean | – | true on the one RMS row per element, which combines all frequencies as √Σ|X(f)|² |
EPR_V |
Float64 | V | earth potential rise of the bus, ResultBus.uepr_freq; RMS row: ResultBus.uepr |
EPR_degree |
Float64 | ° | angle of the EPR in the earth-side sign frame (see Conventions); null on the RMS row |
I_bus_A |
Float64 | A | electrode current: what the bus's own electrode passes into the soil, ResultBus.ia_freq; summed over all buses it is zero |
I_bus_degree |
Float64 | ° | angle of I_bus_A; null on the RMS row |
I_inj_A |
Float64 | A | current of the earthing conductor at a source or fault bus, ResultBus.i_inj_freq -- the source current at a source bus, the fault current at the fault bus, 0 elsewhere; the quantity a conductor is sized for |
I_inj_degree |
Float64 | ° | angle of I_inj_A; null on the RMS row |
Network.res_branches(fault=None)¶
One row per branch and frequency plus one RMS row per branch.
| Column | Type | Unit | Meaning |
|---|---|---|---|
branch_name |
String | – | name of the branch |
fault |
String | – | name of the fault the result belongs to |
frequency_Hz |
Float64 | Hz | frequency of the row; null on the RMS row |
is_rms |
Boolean | – | true on the one RMS row per element, which combines all frequencies as √Σ|X(f)|² |
I_branch_A |
Float64 | A | current of the earthing conductor (cable screen, earth wire) of the branch, ResultBranch.i_s_freq; counted positive from from_bus to to_bus for the physical fault |
I_branch_degree |
Float64 | ° | angle of I_branch_A; null on the RMS row |
Network.res_all_impedances()¶
One row per stored fault and frequency, no RMS row: the earthing impedance and both reduction factors at the fault location.
| Column | Type | Unit | Meaning |
|---|---|---|---|
fault_name |
String | – | name of the fault (this frame says fault_name, the others fault) |
fault_bus |
String | – | bus the fault sits on |
frequency_Hz |
Float64 | Hz | frequency of the row; the frame has no RMS row |
grounding_impedance_Ohm |
Float64 | Ω | earthing impedance Z_E of EN 50522 at the fault bus: the driving-point impedance of the earthing network seen from there (ResultGroundingImpedance.value, equal to z_earthing); null where it is undefined |
grounding_impedance_deg |
Float64 | ° | angle of Z_E |
reduction_factor |
Float64 | – | value: EPR at the fault bus with the inductive coupling over the EPR without it -- a property of the line, not the r of EN 50522 |
reduction_factor_current |
Float64 | – | value_current: |I_E| / |I_F|, the reduction factor r of EN 50522 |
Network.res_fault(fault)¶
The key figures of one fault, read from the stored result: one row per network
frequency plus one RMS row. The schema is gi.RES_FAULT_SCHEMA; this is the
frame the EN 50522 how-to and the command line
report.
| Column | Type | Unit | Meaning |
|---|---|---|---|
fault |
String | – | name of the fault |
fault_bus |
String | – | bus the result was computed for |
frequency_Hz |
Float64 | Hz | frequency of the row; null on the RMS row |
is_rms |
Boolean | – | true on the one RMS row per element, which combines all frequencies as √Σ|X(f)|² |
I_F_A |
Float64 | A | fault current I_F (3I_0 of EN 50522): the currents of the sources that reach the fault, times the fault scalings (ResultReductionFactor.i_fault); RMS row √Σ|I_F(f)|² |
I_F_degree |
Float64 | ° | angle of I_F; null on the RMS row |
EPR_fault_V |
Float64 | V | earth potential rise of the fault bus; RMS row: its stored RMS value |
EPR_fault_degree |
Float64 | ° | angle of that EPR; null on the RMS row |
EPR_max_V |
Float64 | V | largest earth potential rise of any bus at that frequency (RMS row: largest RMS value) |
EPR_max_bus |
String | – | the bus where EPR_max_V occurs |
r_epr |
Float64 | – | EPR-based reduction factor value -- not the r of EN 50522; null on the RMS row |
r_current |
Float64 | – | current-based reduction factor value_current = |I_E| / |I_F|, the r of EN 50522; null on the RMS row and where it is undefined |
I_E_A |
Float64 | A | earth-return current I_E (i_earth); RMS row √Σ|I_E(f)|² |
U_E_V |
Float64 | V | earthing voltage U_E of EN 50522: the EPR at the fault bus (u_earthing); RMS row √Σ|U_E(f)|², the value compared with U_Tp |
Z_E_Ohm |
Float64 | Ω | earthing impedance Z_E of EN 50522, the driving point of the earthing network at the fault bus (z_earthing); null on the RMS row |
Z_E_degree |
Float64 | ° | angle of Z_E; null on the RMS row |
n_diagnostics |
Int64 | – | number of records in Result.diagnostics, the same on every row |
Studies¶
SweepResult.buses(), .branches(), .impedances(), .cuts()¶
A parameter sweep stacks the frames of its points: buses() the rows of
res_buses, branches() those of res_branches (collected only with
run_sweep(..., collect_branches=True)), impedances() those of
res_all_impedances for the swept fault, and cuts() those of
CutAnalysis.to_polars() (only with cuts=). Each frame starts with the
column point (String, the SweepPoint.label) followed by one column per key
of SweepPoint.parameters — rho_f_points adds bus, rho_Ohm_m and
k1 … k5 — and then the columns of the frame it stacks, with the types
listed above. A frame with nothing collected is an empty frame without
columns. See Parameter sweeps and statistics.
OutageStudyResult.compare_buses() and .compare_branches()¶
Long format, one row per element, frequency, scenario and metric, with the
difference to a reference scenario (against=, by default the base case).
frequency_Hz is text here (see above).
| Column | Type | Unit | Meaning |
|---|---|---|---|
bus_name |
String | – | name of the bus |
frequency_Hz |
String | – | frequency as text ("50.0") or "RMS" -- the join key of the comparison, not a number |
metric |
String | – | the compared res_buses column, EPR_V unless columns= names others |
value |
Float64 | unit of the metric | the metric in this scenario |
scenario |
String | – | scenario label (base for the unmodified network) |
delta_vs_base |
Float64 | unit of the metric | value minus the reference scenario's value; the suffix is the reference label (against=) |
delta_pct_vs_base |
Float64 | % | 100 · delta / reference value; null where the reference value is 0 |
| Column | Type | Unit | Meaning |
|---|---|---|---|
branch_name |
String | – | name of the branch |
frequency_Hz |
String | – | frequency as text ("50.0") or "RMS" |
metric |
String | – | the compared res_branches column, I_branch_A unless columns= names others |
value |
Float64 | unit of the metric | the metric in this scenario |
scenario |
String | – | scenario label |
delta_vs_base |
Float64 | unit of the metric | value minus the reference scenario's value |
delta_pct_vs_base |
Float64 | % | 100 · delta / reference value; null where the reference value is 0 |
CutAnalysis.to_polars()¶
One row per direction (cut) and frequency of gi.analyze_cuts.
| Column | Type | Unit | Meaning |
|---|---|---|---|
fault |
String | – | the analysed fault |
fault_bus |
String | – | bus the fault sits on, the reference point of the decomposition |
cut |
String | – | name of the direction (a Cut, or the implicit rest / source_loop side) |
side_buses |
String | – | buses seen through that cut, comma-separated |
n_side_buses |
Int64 | – | number of buses on that side |
branches |
String | – | branches of the cut, comma-separated |
sides_are_disjoint |
Boolean | – | true when no two directions reach the same bus; the far-side currents are defined only then |
frequency_Hz |
Float64 | Hz | frequency of the row (no RMS row) |
Z_side_Ohm |
Float64 | Ω | parallel impedance of that direction, from source-free current division |
Z_side_deg |
Float64 | ° | its angle |
Z_local_Ohm |
Float64 | Ω | impedance of the fault bus's own electrode |
Z_parallel_Ohm |
Float64 | Ω | Z_local in parallel with every Z_side |
Z_driving_point_Ohm |
Float64 | Ω | driving-point impedance of the solved nodal system at the fault bus |
identity_residual |
Float64 | – | |Z_parallel − Z_driving_point| / |Z_driving_point|; grows when the decomposition misses a current path |
I_fault_A |
Float64 | A | injection at the fault bus |
I_local_A |
Float64 | A | part of it taken by the fault bus's own electrode |
I_shield_A |
Float64 | A | shield current leaving the fault bus in that direction |
I_shield_deg |
Float64 | ° | its angle |
current_share |
Float64 | – | |I_shield| / |I_fault| |
I_earth_A |
Float64 | A | soil current crossing the cut, summed over the far side; null when the directions overlap |
I_total_A |
Float64 | A | total current crossing the cut; null when the directions overlap |
r_side |
Float64 | – | |I_earth| / |I_total|, the earth-return share of that direction |
kcl_residual |
Float64 | – | |I_fault − I_local − Σ I_shield| / |I_fault|; zero confirms the split accounts for the whole fault current |
select_rho_f_from_catalog(...)¶
One row per catalogue entry, sorted by sort_by; one epr_<bus>_V column per
swept fault bus.
| Column | Type | Unit | Meaning |
|---|---|---|---|
name |
String | – | name of the catalogue entry |
k1 |
Float64 | Ω/(Ω·m) | coefficient of ρ in Z = k1·ρ + (k2 + j·k3)·f + (k4 + j·k5)·ρ·f |
k2 |
Float64 | Ω/Hz | coefficient of f, real part |
k3 |
Float64 | Ω/Hz | coefficient of f, imaginary part |
k4 |
Float64 | Ω/(Ω·m·Hz) | coefficient of ρ·f, real part |
k5 |
Float64 | Ω/(Ω·m·Hz) | coefficient of ρ·f, imaginary part |
max_epr_rms_V |
Float64 | V | largest RMS EPR over the swept fault buses |
admissible |
Boolean | – | max_epr_rms_V ≤ u_limit |
epr_<bus>_V |
Float64 | V | RMS EPR with the fault at that bus, one column per entry of bus_names |
summarize(frame, value, by=...) and classify(frame, value, edges)¶
summarize returns one row per group: the grouping columns, then n,
n_null, n_nan, mean, std, min, one column per quantile (p05,
p50, p95 by default) and max — read n_nan first, a NaN propagates into
the mean and the quantiles. classify returns its input with one String
column added (class unless name= says otherwise); a null or NaN value gets
a null class.
ResultTransient.to_polars()¶
Long format, one row per sample and signal.
| Column | Type | Unit | Meaning |
|---|---|---|---|
time_s |
Float64 | s | time of the sample |
signal_kind |
String | – | epr for a bus potential, i_branch for a branch current, source for a source waveform |
name |
String | – | the observed bus, branch or source |
value |
Float64 | V or A | instantaneous value (not RMS), in the earth-side frame of the stationary results |
run_reference_cases()¶
One row per closed-form reference case; see Verification and validation.
| Column | Type | Unit | Meaning |
|---|---|---|---|
case |
String | – | name of the reference case |
quantity |
String | – | the compared quantity, with its unit |
conditions |
String | – | conditions under which the closed form holds |
closed_form |
Float64 | unit of the quantity | value of the closed form |
model |
Float64 | unit of the quantity | value the solver computes |
rel_deviation |
Float64 | – | |model − closed form| / |closed form| |
tolerance |
Float64 | – | largest admitted relative deviation |
agrees |
Boolean | – | rel_deviation ≤ tolerance |
Thermal checks¶
check_conductor_limits(network, fault, ...)¶
One row per branch. The thermal columns are null for a branch whose type declares no material and cross-section; the currents are filled in anyway. See Thermal limits of earthing conductors.
| Column | Type | Unit | Meaning |
|---|---|---|---|
branch_name |
String | – | name of the branch |
I_s_rms_A |
Float64 | A | RMS of the earthing-conductor current over all frequencies, 0 Hz included |
I_dc_A |
Float64 | A | the 0 Hz component, taken out of the adiabatic check (THERMAL_DC_EXCLUDED) |
I_ac_rms_A |
Float64 | A | RMS of the alternating components, the I_k of the check |
i_p_A |
Float64 | A | peak current κ·√2·I_ac_rms, input for an electrodynamic check |
kappa |
Float64 | – | peak factor κ of IEC 60909-0 |
m |
Float64 | – | DC heat factor m of IEC 60909-0 |
n |
Float64 | – | AC heat factor n of IEC 60909-0 |
t_k_s |
Float64 | s | short-circuit duration T_k |
I_th_factor |
Float64 | – | √(m + n), the factor from I_ac_rms to I_th |
I_th_A |
Float64 | A | thermal equivalent short-time current I_ac_rms·√(m + n) |
material |
String | – | conductor material of the branch type, null when not declared |
cross_section_mm2 |
Float64 | mm² | cross-section of the branch type, null when not declared |
k |
Float64 | A·√s/mm² | material constant k of IEC 60949 for the initial and final temperatures |
I_admissible_A |
Float64 | A | admissible short-time current k·S/√t_k |
utilization |
Float64 | – | I_th / I_admissible |
within_limit |
Boolean | – | utilization ≤ 1; null when the branch type declares no thermal data |
check_node_limits(network, fault, ...)¶
One row per bus and element — earthing conductor and electrode.
| Column | Type | Unit | Meaning |
|---|---|---|---|
bus_name |
String | – | name of the bus |
element |
String | – | earthing_conductor (carries I_inj) or electrode (carries I_bus) |
I_rms_A |
Float64 | A | RMS of the element's current over all frequencies, before the split |
current_split |
Float64 | – | share of that current one physical conductor carries (*_current_split of the bus type) |
I_conductor_A |
Float64 | A | I_rms · current_split |
I_dc_A |
Float64 | A | the 0 Hz component, taken out of the adiabatic check |
I_ac_rms_A |
Float64 | A | RMS of the alternating components |
i_p_A |
Float64 | A | peak current κ·√2·I_ac_rms |
kappa |
Float64 | – | peak factor κ |
m |
Float64 | – | DC heat factor m |
n |
Float64 | – | AC heat factor n |
t_k_s |
Float64 | s | short-circuit duration T_k |
I_th_factor |
Float64 | – | √(m + n), the factor from I_ac_rms to I_th |
I_th_A |
Float64 | A | thermal equivalent short-time current |
material |
String | – | material declared for the element, null when not declared |
cross_section_mm2 |
Float64 | mm² | cross-section declared for the element |
k |
Float64 | A·√s/mm² | material constant k of IEC 60949 |
I_admissible_A |
Float64 | A | admissible short-time current k·S/√t_k |
utilization |
Float64 | – | I_th / I_admissible |
within_limit |
Boolean | – | utilization ≤ 1; null when the element is not declared |
Importers¶
preview_pandapower_import(net, ...)¶
One row per pandapower element that the import would keep or skip.
| Column | Type | Unit | Meaning |
|---|---|---|---|
kind |
String | – | bus, line, switch, trafo or impedance |
status |
String | – | keep or skip |
pp_index |
Int64 | – | row index in the pandapower table |
name |
String | – | name the element gets (or had) |
vn_kv |
Float64 | kV | nominal voltage of a bus, null for the other kinds |
from_bus |
String | – | first bus of a line or bond |
to_bus |
String | – | second bus of a line or bond |
length_km |
Float64 | km | length the branch gets |
in_service |
Boolean | – | pandapower's in_service, becomes active |
reason |
String | – | why a row is skipped, see the reason table on the I/O page |
read_shortcircuit_results(net, ...)¶
One row per bus of a case solved by pandapower.shortcircuit.calc_sc, in
amperes.
| Column | Type | Unit | Meaning |
|---|---|---|---|
pp_bus_index |
Int64 | – | pandapower bus index |
bus_name |
String | – | bus name, the key to the groundinsight network |
vn_kv |
Float64 | kV | nominal voltage |
fault_type |
String | – | fault type of the solved case, e.g. 1ph |
case |
String | – | max or min |
i_k_a |
Float64 | A | initial short-circuit current I_k'' (pandapower's ikss_ka in A) |
r1_ohm |
Float64 | Ω | positive-sequence resistance at the bus |
x1_ohm |
Float64 | Ω | positive-sequence reactance |
r0_ohm |
Float64 | Ω | zero-sequence resistance (earth faults) |
x0_ohm |
Float64 | Ω | zero-sequence reactance |
r_to_x |
Float64 | – | R/X of the fault loop; for 1ph the earth-fault loop (2R1 + R0)/(2X1 + X0) |
kappa |
Float64 | – | peak factor κ |
kappa_origin |
String | – | pandapower, iec_closed_form or unavailable |
t_k_s |
Float64 | s | short-circuit duration of the case |
n_factor |
Float64 | – | AC heat factor n |
m |
Float64 | – | DC heat factor m |
i_p_a |
Float64 | A | peak short-circuit current |
i_th_a |
Float64 | A | thermal equivalent short-time current |
apply_shortcircuit_characteristics(...)¶
The audit trail: one row per source that feeds the fault.
| Column | Type | Unit | Meaning |
|---|---|---|---|
fault_name |
String | – | the fault the characteristics were written for |
source_name |
String | – | a source that feeds it |
bus |
String | – | the source's bus |
frequency |
Float64 | Hz | frequency whose source value is meant |
i_k_total_a |
Float64 | A | I_k'' at the fault bus |
share |
Float64 | – | this source's share of it |
i_k_previous_a |
Float64 | A | the source value before the call |
i_k_a |
Float64 | A | the source's share of I_k'' |
r_to_x |
Float64 | – | loop R/X written onto the source |
kappa |
Float64 | – | κ written onto the source |
kappa_origin |
String | – | where κ came from |
t_k_s |
Float64 | s | short-circuit duration written onto the fault |
n_factor |
Float64 | – | AC heat factor written onto the fault |
values_updated |
Boolean | – | whether Source.values was overwritten (set_source_values=True) |
The ten input tables of Network.to_tables() and gi.network_from_tables
are listed on the I/O page.