Model and assumptions¶
This page explains the physical and numerical model that groundinsight
implements. It is aimed at readers who want to understand why the code
returns the numbers it returns — for example to validate results against
measurements or analytical expressions. The pages next to it go deeper into
single parts of the model: impedance formulas,
phase currents in rings and meshes,
reduction factors and the earthing impedance,
splitting the network and the location response and
direct current.
Problem statement¶
Consider a power grid composed of substations (buses) and the cables and overhead lines (branches) that connect them. Each bus possesses a grounding grid tying it to remote earth; each branch carries a grounding conductor (cable shield, overhead-line earth wire) that is bonded to the grids of its two terminals. A single-phase-to-ground fault at one bus drives a fault current back towards the source. That current splits into two parallel paths:
- the local earth path through the grounding grid at the fault bus, and
- the metallic return path through the grounding conductor(s) of the connecting branches.
The split depends on the impedances of both paths and on the mutual coupling between the faulted phase and the grounding conductor that runs alongside it. The resulting EPR, the reduction factor and the grounding impedance are the quantities of interest.
Objects¶
groundinsight represents the grid with four Pydantic models:
Bus— a node. Carries a grounding impedance \(Z_{\text{B}}(\rho_E, f)\) that couples the bus to remote earth.Branch— an edge between two buses with a self impedance \(Z_{\text{self}}(\rho_E, f, l)\) (series impedance of the grounding conductor) and a mutual impedance \(Z_{\text{mutual}}(\rho_E, f, l)\) (coupling between faulted phase and grounding conductor).Source— a current source anchored at a bus. Holds a dictionary that maps each frequency to the injected phasor current.Fault— a marker at a bus. Holds an optional dictionary of frequency-dependent scaling factors applied to the source currents; a frequency without an entry is scaled with 1.0.
Bus and branch properties are derived from reusable types (BusType,
BranchType) whose impedances are parameterised by formula strings. The
formulas are parsed with SymPy, turned into lambdify callables and evaluated
for every network frequency — see
Impedance formulas and where they come from.
Nodal-admittance formulation¶
All computations take place per frequency \(f\) in the phasor domain.
groundinsight assembles an admittance matrix \(Y(f)\) of size \(N\times N\)
(where \(N\) is the number of buses):
Each entry can be switched off by setting grounding_conductor=False on the
corresponding branch, which is useful for modelling insulated shields.
The right-hand-side vector \(\underline{i}(f)\) holds the source injections scaled by the active fault's frequency scaling and — crucially — the mutual-coupling contributions. For every branch that carries phase current a Norton equivalent is added: the phase current \(I_{\text{phase}}\) driving the branch induces a shield current of magnitude \(I_{\text{mut}} = I_{\text{phase}}\,Z_{\text{mutual}}/Z_{\text{self}}\), injected as \(-I_{\text{mut}}\) at the from bus and \(+I_{\text{mut}}\) at the to bus. The phase currents come from a solve on the phase-conductor network, which divides the source current between the routes of a ring or a mesh — see Phase currents in rings and meshes.
The EPR vector is then
Numerically the system is solved with SciPy's sparse LU decomposition
(scipy.sparse.csc_matrix + splu) — this scales well to meshed
low-voltage networks with thousands of buses. The path enumeration of the
legacy phase-current mode does not; see
Path finding and the legacy mode.
The source current enters the earthing network at the source bus and leaves it at the fault bus. That is the reverse of the physical fault current, which flows from the source through the phase conductor to the fault and returns through soil and shields, so the potentials and electrode currents come out with the opposite sign of their physical values; magnitudes, RMS values, reduction factors and impedances are not affected. Conventions and units gives the two frames with a worked two-bus example.
Derived quantities¶
Once \(\underline{u}(f)\) is known for every frequency, three result families are computed: the earth potential rise and the branch currents (below), and the reduction factors and the grounding impedance (Reduction factors and earthing impedance).
Earth potential rise (EPR)¶
The per-frequency bus voltages are stored as ComplexNumber entries on
ResultBus objects. RMS values across all frequencies are computed via
Branch currents¶
For every branch and frequency the current through the grounding conductor is
where the second term accounts for the Norton source representing the
mutual coupling (compute_branch_currents).
Mind the frame: the potentials \(u\) in the numerator are the earth-side
potentials of the solve, the negatives of the physical ones, so
\(u_{\text{to}} - u_{\text{from}}\) is the physical \(u_{\text{from}} -
u_{\text{to}}\). ResultBranch.i_s is therefore the physical shield current,
counted positive from from_bus to to_bus — the same direction as the phase
current. In the earth-side frame the same number reads as a current from
to_bus towards from_bus. A shield that carries the return current of a
phase current flowing from from_bus to to_bus shows a negative i_s;
Conventions and units
works this through on a line.
Active flag and outage studies¶
Both Bus and Branch carry a boolean active field (default
True). The flag has a clean physical interpretation:
- An inactive
Busis removed from the nodal system entirely. Its row and column drop from \(Y(f)\) and the bus contributes nothing to the right-hand-side vector \(\underline{i}(f)\). - An inactive
Branchbehaves as an open circuit: no contribution to the admittance matrix, no Norton-equivalent injection from the mutual coupling, and a zero current in the result.
The phase-conductor network leaves inactive elements out in the same way,
and so does PathFinder when it enumerates source-to-fault paths for the
legacy mode, so the per-path Norton bookkeeping stays consistent. The flag
is round-tripped through SQLite and JSON; existing payloads load
with active=True for every element, which keeps backwards
compatibility intact.
That makes maintenance scenarios, planned outages, broken shields
and N-1 contingencies expressible without rebuilding the network.
The groundinsight.simulation.outage sub-package wraps this into
two convenience entry points:
outage_context(network, outage)— context manager that flips the listed elements toactive=Falsefor the duration of awithblock and restores the previous state (including the cached path list) afterwards.run_outage_study(network, fault, scenarios=[...])— executes the base case plus one fault calculation perOutagescenario and returns anOutageStudyResultwhosecompare_buses(...)/compare_branches(...)accessors yield long-format Polars DataFrames with absolute and relative deltas against a chosen reference scenario.
Inverse rho analysis¶
The forward solve answers "given \(\rho_E\), what is the EPR?" The
sister inverse question — "how large can \(\rho_E\) become before
the EPR at the fault bus exceeds a limit \(u_{\text{limit}}\)?" — is answered by
groundinsight.analysis.find_max_rho_scaling. It log-bisects a
uniform scaling factor \(c\) of Bus.specific_earth_resistance on a
user-selected bus set, re-evaluates each BusType.impedance_formula
through the existing SymPy machinery and triggers run_fault at
every trial value. The output is the largest verified admissible
\(c\) — a factor for which \(|U_\text{EPR}(f)|_{\text{RMS}} \le u_{\text{limit}}\)
was actually measured — together with the EPR at that point and the
per-bus \(\rho_{\max} = c\,\rho_0\). The original \(\rho\) values are
restored via a finally block, so the network is unchanged after the
call. A frequency-dependent variant (find_max_rho_f_scaling)
extends the same idea to two-parameter rho-f curves.
The limit is an earth potential rise, not a touch voltage: the EPR is an upper bound of the touch voltage, and how a permissible touch voltage turns into a limit for the EPR is the subject of Compare results with EN 50522 limits.
"Verified admissible" and "maximal" are not the same claim, and the
result distinguishes them. A bisection can also end because the
entire bracket was admissible (the true maximum lies above
c_bounds[1] and was never determined) or because the iteration cap
was reached before the bracket closed. In both cases the returned
\(c\) is still a factor that satisfies the limit — it is simply not the
largest one. The status and converged keys carry that
distinction, and c_bracket gives the interval that provably
contains the true threshold; an infinite upper bound is the
machine-readable form of "widen c_bounds". Only a converged result
is a maximum in the sense the question asks for.
The scaling acts on the soil resistivity of the selected buses only. A
branch whose formulas contain rho — Carson's earth-return term, for
instance — keeps its own Branch.specific_earth_resistance. For a Carson
formula that matters: its reactance grows by
\(\omega \cdot 2\cdot10^{-4} \ln\sqrt{10} = 0.072\ \Omega/\text{km}\) per decade
of \(\rho\) at 50 Hz, about 11 % of the screen-loop reactance of the cable in
Bus and branch types from data sheets.
Transient simulations¶
The phasor-domain pipeline above answers the stationary question.
For non-sinusoidal fault currents (fault inception, DC offset
asymmetry, clearing, switching transients) the
groundinsight.simulation.transient sub-module adds a time-domain
layer on top of the same network model. Two solver paths are
available: an FFT-based path that re-uses the existing
impedance_formula of BusType and BranchType per FFT bin, and a
state-space ODE path that consumes the lumped RLC fields
(R_formula, L_formula, C_formula, R_self_formula,
L_self_formula, C_self_formula, R_mutual_formula,
M_mutual_formula) and integrates with scipy.signal.lsim. Source
waveforms come from the groundinsight.simulation.waveforms
library (step, sinusoidal_with_dc_offset,
damped_oscillation) or from any user-supplied vectorised callable
f(t) -> values. See Transient simulation for the
derivations and the transient-simulations reference
for the full API.
Assumptions and limits of the model¶
Every result rests on the following assumptions. An assessment has to check that they fit the installation; Verification and validation lists what has been checked against what.
- Quasi-stationary phasors. One linear solve per frequency with lumped elements: no travelling waves, no soil ionisation, no frequency dependence other than what the formulas contain. The transient solvers drop the phasor assumption, not the lumped one.
- Lumped electrodes in homogeneous soil. Every bus is one impedance to
remote earth; neighbouring electrodes do not couple resistively; the soil
is one
rhoper bus and per branch. The model gives earth potential rises, not touch or step voltages and not the potential on the surface. - One-way coupling. The phase currents are determined first, on the phase-conductor network, and then drive the shields; the shields do not act back on the split. That is exact when the ratio \(k = Z_m/Z_s\) is the same on every branch of each mesh of the phase network, and an approximation otherwise — see When the split is exact.
- One phase conductor. The phase network contains the faulted conductor only. In a ring the healthy phases form closed loops of their own, and the currents the fault induces in them are not modelled. The size of that effect has not been quantified.
- Current sources for the stationary solve. A Thévenin source
(
create_voltage_source) couples to the shields with \(E/Z_\text{src}\) instead of its actual loop current; where branches with mutual coupling carry its phase current,run_faultwarns (ModelAssumptionWarning, codeTHEVENIN_COUPLING), and the EPR at the fault can come out too low. Model the infeed as a current source carrying the prospective fault current for stationary studies. - A source on the fault bus counts as fault current. The current-based
reduction factor divides by the sum of all sources that feed the fault,
including one that sits on the fault bus itself, whose current never
reaches the earthing network. With 1000 A from a remote infeed and 500 A
from a source on the fault bus,
value_currentis two thirds of its value without the local source, while the earth current \(I_E\) is the same. For the reduction factor of the line, dividei_earthby the remote infeed yourself; see Reduction factors. - Bus ρ only in the inverse analysis.
find_max_rho_scalingandfind_max_rho_f_scalingscale the soil resistivity of buses; branch formulas keep theirs (see Inverse rho analysis). - Signs in the earth-side frame. Potentials and electrode currents are reported as the negatives of their physical values (Conventions and units).
- The formulas are the user's. The package checks a formula's syntax, its symbols and that the impedance it gives is passive, not whether it describes the conductor it is attached to (Impedance formulas).
Worked example¶
The full physical model behind the equations above maps onto the Python API in a single block:
Illustrative values
The formulas below are round numbers chosen to make the example short, not the data of a real cable or electrode. Bus and branch types from data sheets derives them for a real cable.
import groundinsight as gi
net = gi.create_network(name="demo", frequencies=[50.0, 250.0])
bus_type = gi.BusType(
name="SubstationBus", system_type="Substation",
voltage_level=20.0,
impedance_formula="rho * 0.01 + j * f * 1/50 * 0.1",
)
cable_type = gi.BranchType(
name="MSCable", grounding_conductor=True,
self_impedance_formula="(0.25 + j * f * 0.012) * l",
mutual_impedance_formula="(0.0 + j * f * 0.012) * l",
)
gi.create_bus(name="b0", type=bus_type, network=net)
gi.create_bus(name="b1", type=bus_type, network=net)
gi.create_branch(name="ln", type=cable_type,
from_bus="b0", to_bus="b1", length=5.0, network=net)
gi.create_source(name="src", bus="b0",
values={50.0: 1000.0, 250.0: 200.0}, network=net)
gi.create_fault(name="F1", bus="b1",
scalings={50.0: 1.0, 250.0: 1.0}, network=net)
gi.run_fault(network=net, fault="F1")
print(net.res_all_impedances()) # Z_E and both reduction factors per frequency
The Network API hides every step listed in the next section behind
run_fault; the results are exposed as Polars DataFrames via
net.res_buses(fault="F1"), net.res_branches(fault="F1") and
net.res_all_impedances().
Summary of the calculation pipeline¶
run_fault(network, fault) executes the following steps (see
network_operations.run_fault and ElectricalNetwork for details):
set_active_fault— select the target fault.- Find the sources that reach the fault through the active network — a
breadth-first search; paths are enumerated only in the legacy
phase_current_mode="paths". build_electrical_network— create anElectricalNetworkhelper that holds the numerical arrays: \(Y(f)\), and \(\underline{i}(f)\) with the source injections and the Norton injections of the coupling. The phase currents behind the latter come from a solve on the phase-conductor network per source and frequency. The input checks ofrun_fault(source values per frequency, fault scalings) run here.solve_network— solve the linear system per frequency (sparse LU).compute_branch_currents— derive branch currents from \(\Delta u\) plus Norton contributions.compute_reduction_factors— re-solve without mutual Norton sources and take the EPR ratio at the fault bus (value); sum the electrode currents of the earth group for the current-based factor (value_current); record \(U_E\), \(Z_E\) and \(I_E\).compute_grounding_impedance— the driving-point impedance of the earthing network at the fault bus, per frequency.
The persistent state of the calculation (sparse matrices, vectors) lives on
a private ElectricalNetwork attribute of the Network instance, so
re-solving after topology changes only requires a fresh run_fault call.
Conditions found on the way that change how a result must be read are
collected in Result.diagnostics.