Warnings and diagnostics

groundinsight reports a condition that changes how a result must be read — a heuristic phase-current split, a frequency the input does not cover, a reactance that has no meaning at 0 Hz — as a warning with a stable code, not as a log line. This page lists every code the package can produce: the warning class it is raised with, its severity, the elements it names, when it is raised and what to do about it. A test compares the page with the source code in both directions, so a code cannot be added without a row here.

How a diagnostic reaches you

Every package warning is an instance of a subclass of gi.GroundinsightWarning (itself a UserWarning) and carries three fields next to its message:

Field Meaning
code stable upper-case identifier; programs branch on it, never on the message text
severity info, warning or error (only the pre-flight check produces error)
elements the network elements concerned, as (kind, name) pairs, e.g. ("branch", "K2"); kinds are bus, branch, source, fault, bus_type, branch_type, network and switch (a pandapower switch, by its import label)

Where you find them:

  • During a solve. gi.run_fault and gi.solve collect every package warning of the run into Result.diagnostics, a list of gi.Diagnostic records with code, severity, category, message and elements. The record is made even when the warning is filtered out or shown only once, so the result always carries its full set; Network.res_fault counts them in n_diagnostics.
  • Around any other call (importing, creating elements, a thermal check, a transient study), collect them yourself with groundinsight.diagnostics.collecting(): with collecting() as records: .... The collection is per thread and per asyncio task, so two runs in parallel never see each other's records.
  • Before a solve. gi.check_network(net) returns the problems of a network as gi.Diagnostic records without raising; its codes are listed below.
  • In a front end. The service layer groundinsight.api passes the records on unchanged as DiagnosticDTO (code, severity, category, elements, message).

A worked example of all four: Diagnostics, logging and warnings.

As Python warnings they also follow the usual machinery: warnings.simplefilter("error", gi.ModelAssumptionWarning) turns a category into an exception (useful in CI), python -W error::groundinsight.DCLimitWarning does the same from the command line, and logging.captureWarnings(True) routes them into logging. Renamed parameters and deprecated attributes raise Python's own DeprecationWarning, which has no code.

Warning classes

Code Category Severity Elements Raised when What to do
GROUNDINSIGHT GroundinsightWarning warning – Default code of the base class (a UserWarning); every package warning is an instance of it. The package raises its subclasses with their own codes. Filter or catch gi.GroundinsightWarning to handle all package warnings at once.
MODEL_ASSUMPTION ModelAssumptionWarning warning – Default code of the class for results that rest on a modelling assumption or heuristic; the package raises it with the specific codes below. Read the specific code.
INPUT InputWarning warning – Default code of the class for input that is incomplete or inconsistent but can be solved; the package raises it with the specific codes below. Read the specific code.
FREQUENCY_ORDER NetworkFrequencyOrderWarning warning – Network.frequencies is not strictly increasing. The order is kept, but the FFT transient solver maps spectral bins by position. Sort the list, unless the order is intended.
DC_LIMIT DCLimitWarning warning – An impedance formula is evaluated at 0 Hz and the limit needs a decision: it has a pole (modelled as an open circuit — right for a series capacitance), it converges only slowly (the value reached is an approximation of the limit, e.g. sqrt(f) or log(f) terms), it carries a finite reactance (the 0 Hz bin takes the real part and drops the reactance), or it is zero (an ideal short: modelled with a stand-in of √ε times the smallest other impedance of the network). Only the 0 Hz bin is affected. Write reactances as j*2*pi*f*L so they vanish at DC; state a known DC value as a term without f; give an ideal bond a small resistance or merge its two buses. See Formula syntax: direct current.
TRANSIENT_MODEL TransientModelWarning warning coupled branches (FFT coupling case) The transient model is narrower than the input: the FFT solver ignores mutual coupling (the EPR comes out higher, i.e. conservative), the FFT window ends while the response still rings (the tail wraps around), the active fault carries scalings other than 1 (both solvers use the waveform as the literal injection), or a branch has |M_mutual| > L_self (almost always a unit slip). Use solver="state_space" for coupled networks; lengthen t_end or pass zero_pad=True; scale the waveform itself; check the units of the RLC formulas.

Codes raised during a solve

These are raised by gi.run_fault and gi.solve and stored in Result.diagnostics.

Code Category Severity Elements Raised when What to do
PHASE_PROXY ModelAssumptionWarning warning the branches of the mesh, the fault The phase network is meshed (a ring, parallel cables) and branches of the mesh have no phase_impedance_formula, so the phase current is split with proxy impedances (the screen self impedance, or the length). Broken screens are named. Declare phase_impedance_formula on the branch types — the reduced phase impedance, see Phase impedance for rings and meshes.
THEVENIN_COUPLING ModelAssumptionWarning warning the voltage sources A Thévenin (voltage) source away from the fault bus reaches the fault while a coupled branch has a mutual impedance. The coupling is driven by the source's Norton current instead of its loop current; in the reference cases the EPR came out 6–38 % too low, i.e. unconservative. Model the infeed as a current source with the fault current of a short-circuit calculation, or treat the EPR as a lower bound.
SCALINGS_INCOMPLETE InputWarning warning the fault Fault.scalings is a non-empty mapping that misses network frequencies; those are scaled with 1.0 (full contribution). Once per run. Also reported by gi.check_network. Give every network frequency a scaling; 0.0 excludes a frequency. Leaving scalings out means 1.0 everywhere, without a warning.
SOURCE_FREQUENCY_GAP InputWarning warning the source A source that reaches the fault has no value at some network frequencies and contributes 0 A there. Once per source and run. Also reported by gi.check_network. Complete Source.values, or accept the gap deliberately. A source with a value at no network frequency is an error (ValueError).
SOURCE_WITHOUT_PHASE_PATH ModelAssumptionWarning warning the source, the fault A source reaches the fault through the earthing network but has no phase-conductor connection to the fault bus. Its current is still injected, as if it returned entirely through soil and screens (reduction factor 1 for its share, no coupling). Check the topology and the active flags; a phase path needs branches that carry a phase conductor.
EARTH_GROUP_UNDEFINED ModelAssumptionWarning warning the fault, the fault bus No electrode carries more than numerical noise (1e-9 of the fault current), so there is no earth-return current: i_earth and value_current are None. Usually a fault on the bus of the only source, or a network without electrodes; check the excitation.
FAULT_AT_FEEDING_BUS ModelAssumptionWarning info the fault, the fault bus The fault sits on the bus of every source that feeds it: the fault current closes through that station's own earthing back to the source, nothing is injected into the earthing network, EPR and earth-return current are zero, and both reduction factors are None. U_E is 0 V; Z_E is still the driving-point impedance. Recorded in Result.diagnostics only (groundinsight.diagnostics.note), never raised as a Python warning. Nothing to fix for the station itself; to study what the surrounding network sees, place the fault at another bus or add the other infeeds.
EARTH_GROUP_SPREAD ModelAssumptionWarning warning the fault, the fault bus The electrode currents are spread in angle, so the split into the group that feeds the soil and the group that returns the current is less sharp than usual; I_E and value_current describe the dominant direction. Read r_current with care; compare with the EPR itself.
REDUCTION_FACTOR_UNDEFINED ModelAssumptionWarning warning the fault, the fault bus The EPR of the fault bus without coupling is zero to numerical precision (or the solve without coupling fails), so the EPR-based factor value has no reference and is None at that frequency. Expected for a fault without a path to earth at that frequency; the EN 50522 factor value_current is unaffected.
EARTHING_IMPEDANCE_UNDEFINED ModelAssumptionWarning warning the fault, the fault bus, the buses of its earthing group No bus connected to the fault bus through screens has an electrode, or the fault bus reaches the earthing network only through a Thévenin loop: z_earthing and Z_G are None. Give the earthing group an electrode; a Thévenin loop is not an earthing impedance.
PARALLEL_COEFFICIENT_DEFAULT ModelAssumptionWarning warning the sources Legacy mode phase_current_mode="paths": a source reaches the fault over several paths whose parallel_coefficient is left at the default, so each path carries the full current. Use the default mode "auto", or set the coefficients.

DC_LIMIT and FREQUENCY_ORDER can appear in Result.diagnostics as well, when an impedance is evaluated during the run; see Warning classes.

Codes raised outside a solve

These are raised by the function named in the row; collect them with collecting() around the call.

Code Category Severity Elements Raised when What to do
SOURCE_FREQUENCY_OUTSIDE_NETWORK InputWarning warning the source create_source, create_voltage_source or Network.add_source get values at frequencies the network does not solve; they are ignored. Also reported by gi.check_network. Add the frequency to Network.frequencies, or drop the value.
THERMAL_DATA_INCOMPLETE InputWarning warning the branches or buses, the fault check_conductor_limits / check_node_limits: a type declares half of its thermal data (a material without a cross-section, or the reverse), so within_limit is null for it. Declare both, or neither.
THERMAL_DC_EXCLUDED ModelAssumptionWarning warning the branches or buses, the fault The 0 Hz component is left out of the adiabatic check, because m already carries the DC content of an alternating fault current. A genuine direct current during T_k adds about I_dc² to I_th²; the message quotes the increase. If a direct current really flows during the fault (DC railway, rectifier), check with the increased I_th.
SC_KAPPA_MIXED ModelAssumptionWarning warning the sources, the fault resolve_fault_sc_characteristics: the sources feeding the fault have different R/X; the non-linear IEC 60909 factors are applied once, with the aggregated κ. Use the transient solver for an exact result with mixed R/X.
SC_DATA_INCOMPLETE InputWarning warning the sources, the fault resolve_fault_sc_characteristics: sources that carry part of the current have no IEC 60909 data; κ is that of the others. Set i_k_a, r_to_x or kappa on every source.
SC_KAPPA_MISSING InputWarning warning the buses read_shortcircuit_results: neither ip_ka nor a usable R/X is available for a bus. Complete the zero-sequence data in pandapower (x0x_max, r0x0_max, r0_ohm_per_km, …).
SC_KAPPA_OUT_OF_RANGE InputWarning warning the bus read_shortcircuit_results: pandapower's ip_ka/ikss_ka imply a κ outside (1, 2]. Check the pandapower case.
SC_ROW_AMBIGUOUS InputWarning warning the fault, the bus apply_shortcircuit_characteristics: several rows match the fault bus; the first is used. Pass pp_bus= or bus_name=.
SC_SPLIT_EQUAL InputWarning warning the sources, the fault apply_shortcircuit_characteristics: the sources inject nothing at the frequency, so I_k'' is split equally. Set the relative infeed shares first.
SC_VALUE_REPLACED InputWarning warning the fault apply_shortcircuit_characteristics replaced a different t_k_s or n_factor of the fault with the value of the short-circuit case. Pass the value explicitly if the previous one was intended.
SC_VOLTAGE_SOURCE_SKIPPED InputWarning warning the source apply_shortcircuit_characteristics: a voltage source keeps its values. Model the infeed as a current source if its share should be written.
IMPORT_BUS_SKIPPED InputWarning warning the bus from_pandapower / preview_pandapower_import: a bus has no usable vn_kv. Fix vn_kv in pandapower.
IMPORT_LINE_SKIPPED InputWarning warning the branch A line is a self-loop, or its length cannot be imported. Fix the line in pandapower.
IMPORT_LENGTH_DEFAULT InputWarning warning the branch A line has no usable length_km and gets the fallback of 1 km. Set length_km; every impedance of the branch scales with it.
IMPORT_SWITCH_NOT_IMPORTED InputWarning warning the buses the switches would bond Closed bus-to-bus switches were not imported because ImportDefaults.switch_branch_type is not set; a bus behind such a switch is isolated and reads 0 V. Set switch_branch_type.
IMPORT_LINE_SWITCH_OPEN InputWarning info the branch, the switches from_pandapower: a line has an open line switch (et="l") and is imported with an open phase conductor (phase_impedance_formula = "nan"); it carries no fault current, its screen stays connected at both ends. Nothing, if the screen is bonded at both stations; set the branch inactive if it is interrupted as well.
IMPORT_ELEMENT_NOT_IMPORTED InputWarning warning – Transformers and impedance elements are not modelled and were left out. Check the preview; model the connection by hand if it matters.
IMPORT_VOLTAGE_LEVEL_MISMATCH InputWarning warning the bus type The default bus type declares another voltage level than voltage_level_kV. Use a bus type written for the imported level.
IMPORT_EMPTY InputWarning warning the network The import produced no bus or no branch — usually a wrong voltage_level_kV. Check voltage_level_kV against net.bus.vn_kv.
TRANSIENT_SOURCE_NOT_CONNECTED InputWarning warning the sources TransientStudy.solve(solver="fft"): a source with a waveform has no galvanic connection to the fault bus and injects nothing. Check the topology.
TRANSIENT_BRANCH_SKIPPED InputWarning warning the branches State-space solver: branches without R_self/L_self are left out. Declare R_self_formula and L_self_formula on the branch types.
TRANSIENT_COUPLING_SKIPPED TransientModelWarning warning the voltage sources State-space solver: the coupling is modelled for current sources only. Use current sources for coupled studies.
TRANSIENT_RESISTIVE_COUPLING_IGNORED TransientModelWarning warning the branches State-space solver: R_mutual/M_mutual on branches without L_self are ignored. Give those branches an inductance.
TRANSIENT_PHASE_SPLIT ModelAssumptionWarning warning the coupled branches State-space solver on a meshed network: the phase split is taken at f_eval and depends on frequency here, so a DC offset and harmonics are split as at f_eval (below 1 % of the peak on a mixed cable/line ring). Accept, or compare with run_fault at the frequencies of interest.
PROJECT_FILE_LEGACY_ENCODING InputWarning warning the network load_network_from_json read a file that is not UTF-8 (written by 0.6.0 or earlier on a non-UTF-8 system) with the platform encoding. Save it again; the new file is UTF-8.
LEGACY_EARTHING_DEFINITION InputWarning info the fault A result stored before U_E and Z_E were redefined at the fault bus is loaded: its old values moved to u_earthing_group / z_earthing_group, and U_E, Z_E and Z_G stay empty. A record in Result.diagnostics, not a Python warning. Run the fault again.

Codes of the pre-flight check

gi.check_network(net, fault=None) returns these as records of category InputWarning (the three codes it shares with the solve — SCALINGS_INCOMPLETE, SOURCE_FREQUENCY_GAP, SOURCE_FREQUENCY_OUTSIDE_NETWORK — are listed above). An error means that run_fault would raise or would return an answer that does not describe the network; a warning that the network solves but part of the input has no effect.

Code Category Severity Elements Raised when What to do
NOT_A_NETWORK InputWarning error – The argument is not a Network. Pass a network.
CHECK_FAILED InputWarning error the network A check raised on an unforeseen malformation; the other checks still ran. Read the message; it names the check.
ELEMENT_INVALID InputWarning error the entry An entry of buses, branches, sources or faults is not an element of the expected type. Rebuild the entry through the API.
FREQUENCIES_INVALID InputWarning error the network Empty frequency list, duplicates, non-finite or negative values (an in-place edit bypasses the validator). Assign a valid list to Network.frequencies.
NO_ACTIVE_BUS InputWarning error the network No bus is active. Activate the buses.
NO_SOURCE InputWarning error the network The network has no source. Add a source.
NO_FAULT InputWarning error the network The network has no fault. Add a fault.
FAULT_UNKNOWN InputWarning error the fault The fault= argument names no fault of the network. Check the name.
BRANCH_UNKNOWN_BUS InputWarning error the branch A branch end names a bus that does not exist; the solver would drop the branch. Fix the reference.
SOURCE_UNKNOWN_BUS InputWarning error the source A source names a bus that does not exist; the solver would ignore it. Fix the reference.
FAULT_UNKNOWN_BUS InputWarning error the fault A fault names a bus that does not exist. Fix the reference.
FAULT_BUS_INACTIVE InputWarning error the fault, the bus A fault sits on an inactive bus. Activate the bus or move the fault.
SOURCE_BUS_INACTIVE InputWarning warning the source, the bus A source sits on an inactive bus and injects nothing. Activate the bus if the source should feed.
IMPEDANCE_MISSING InputWarning error the element An element of the nodal system has no impedance at a network frequency. Re-derive it (assign the type again) or complete the dictionary.
FORMULA_ERROR InputWarning error the element No stored impedance, and the type formula cannot be evaluated. Fix the formula; see Formula syntax.
IMPEDANCE_NOT_PASSIVE InputWarning error the element An impedance that is inverted is zero, too small to invert or has a negative real part. Check the formula at the lowest ρ, frequency and length of the model.
IMPEDANCE_NOT_FINITE InputWarning error the element An impedance is NaN at a network frequency. Fix the formula or the stored value.
SOURCE_FREQUENCY_NONE InputWarning error the source A source has a value at none of the network frequencies (run_fault raises a ValueError). Give it values at the network frequencies.
SOURCE_VALUE_NOT_FINITE InputWarning error the source A source value is NaN or infinite at a network frequency. Fix the value.
FAULT_NOT_REACHED InputWarning warning the fault No source reaches the fault over active elements; every potential is 0 V. Correct for an outage that islands the fault bus; otherwise check the topology.
ISOLATED_BUS InputWarning warning the bus An active bus has no active branch to another active bus. Connect it or deactivate it.
FLOATING_ISLAND InputWarning error the buses of the island Buses joined by grounding conductors have no electrode and therefore no reference to earth; their potential is undefined and run_fault refuses the network. Give one bus of the group an electrode.

Errors

Conditions that leave no meaningful answer raise instead of warning:

  • ValueError — invalid input or a violated model rule: an unknown element name, a formula the guard refuses, a non-passive impedance, a source without a value at any network frequency, a group of buses without a path to earth ("Singular admittance matrix … no path to reference earth"), a project file with a newer schema_version than the running release supports.
  • RuntimeError — a state that does not allow the call: no started database session for the module-level helpers, a database written by an older release opened with migrate=False, res_fault for a fault without stored result. gi.StudyCancelled, raised when a study's should_cancel() answers true, is a RuntimeError too.
  • TypeError — a value of the wrong type for a model field, or a callback that is not callable.
  • ImportError — a function of the optional pandapower extra without pandapower installed; the message names the extra.